Terminal Connection Diagrams - Mitsubishi Electric FR-F820-00046 Instruction Manual

Hide thumbs Also See for FR-F820-00046:
Table of Contents

Advertisement

3
WIRING
3.1

Terminal connection diagrams

 FM type
Sink logic
Main circuit terminal
Control circuit terminal
Three-phase
AC power
supply
Control input signals
(No voltage input allowed)∗3
Forward rotation start
Reverse rotation start
Start self-holding selection
Multi-speed
selection
Second function selection
Terminal 4 input selection
(Current input selection)
Contact input common
(Common for external power supply transistor)
24V external power
Common terminal
Frequency setting signals (Analog)
Frequency setting
potentiometer
1/2W1kΩ∗6
Terminal 4 input
(Current input)
Connector for plug-in option connection
Safety stop signal
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common

For the FR-F820-03160(75K) or higher, the FR-F840-01800(75K) or higher, always connect a DC reactor (FR-HEL), which is available as an option. (To select a DC
reactor, refer to
page
25, and select one according to the applicable motor capacity.)
When a DC reactor is connected to the FR-F820-02330(55K) or lower or the FR-F840-01160(55K) or lower, if a jumper is installed across the terminals P1 and P/+,
remove the jumper before installing the DC reactor.

When using separate power supply for the control circuit, remove the jumper between R1/L11 and S1/L21.

The function of these terminals can be changed with the input terminal assignment (Pr.178 to Pr.189). (Refer to

Terminal JOG is also used as the pulse train input terminal. Use Pr.291 to choose JOG or pulse.

Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input a voltage, set the voltage/current input switch OFF. To input a current,
set the voltage/current input switch ON. Terminals 10 and 2 are also used as a PTC input terminal. (Pr.561) (Refer to the Instruction Manual (Detailed).)

It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.

Do not use terminals PR and PX. Do not remove the jumper connected to terminals PR and PX.

The function of these terminals can be changed with the output terminal assignment (Pr.195, Pr.196). (Refer to

The function of these terminals can be changed with the output terminal assignment (Pr.190 to Pr.194). (Refer to

The terminal F/C (FM) can be used to output pulse trains as open collector output by setting Pr.291.

Not required when calibrating the scale with the operation panel.

No function is assigned in the initial status. Assign the function using Pr.186 CS terminal function selection. (Refer to
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, separate the main circuit cables at the input side from
the main circuit cables at the output side.
• After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting
holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
• Set the voltage/current input switch correctly. Incorrect setting may cause a fault, failure or malfunction.
DC reactor
(FR-HEL)∗1
Jumper
Earth
(Ground)
P1
P/+
MC
MCCB
R/L1
Inrush current
S/L2
limit circuit
T/L3
ON
R1/L11
Jumper
∗2
S1/L21
OFF
Main circuit
Earth
(Ground)
Control circuit
STF
STR
STP(STOP)
RH
High speed
RM
Middle speed
RL
Low speed
∗4
JOG
Jog operation
RT
MRS
Output stop
RES
Reset
AU
CS
∗12
SD
24V
PC
24VDC power supply
+24
supply input
SD
Voltage/current
∗5
input switch
10E(+10V)
ON
OFF
10(+5V)
2
3
DC0 to 5V
Initial value
2
2
DC0 to 10V selectable
DC0 to 20mA
5
1
(Analog common)
DC0 to ±10V
Initial value
Auxiliary
(+)
1
DC0 to ±5V selectable
(-)
input
DC4 to 20mA
Initial value
(+)
4
DC0 to 5V
selectable
(-)
DC0 to 10V
connector 1 connector 2
connector 3
Shorting
24V
wire
PC
S1
S2
Output shutoff
circuit
SIC
SD
FR-F820-00770(18.5K) to 01250(30K),
FR-F840-00470(22K) to 01800(75K)
DC reactor
(FR-HEL)∗1
Brake unit
(Option)
Jumper
Jumper
Earth
(Ground)
PX∗7 PR∗7 N/-
P1
P/+
U
V
W
EMC filter
ON/OFF
connecter
Relay output∗8
C1
B1
Relay output 1
(Fault output)
A1
C2
B2
Relay output 2
A2
RUN
Open collector output∗9
Running
SU
Up to frequency
IPF
Instantaneous
power failure
OL
Overload
FU
Frequency detection
SE
Open collector output common
Sink/source common
PU
connector
F/C
+
USB A
(FM)
∗10
connector
4
Calibration
resistor ∗11
SD
∗5
USB
mini B
AM
(+) Analog signal output
connector
(0 to ±10VDC)
5
(-)
∗5
TXD+
Data
TXD-
∗5
transmission
RXD+
Data
RXD-
reception
SG
GND
Terminating
5V
VCC
resistor
(Permissible load current 100mA)
So
Safety monitor output
SOC
Safety monitor output common
Terminal connection diagrams
Brake unit
(Option)
P3
PR∗7 N/-
Motor
M
Earth (Ground)
-
Indicator
(Frequency meter, etc.)
Moving-coil type
1mA full-scale
RS-485 terminals
page
18.)
page
18.)
page
18.)
page
18.)
WIRING
5