OneWireless XYR 6000 Transmitters Quick Start Guide 34-XY-25-21 Revision 12 February 2013 Honeywell Process Solutions...
Page 2
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and specifications in this document are subject to change without notice.
Page 3
Configuration, authentication and operation are covered in other documents. Honeywell does not recommend using devices for critical control where there is a single point of failure or where single points of failure result in unsafe conditions. OneWireless is targeted at open loop control, supervisory control, and controls that do not have environmental or safety consequences.
Page 4
For more contact details for Europe, Asia, North and South Americas, please see back page. World Wide Web Honeywell Process Solution Support Online: www.honeywellprocess.com/ Elsewhere Call your nearest Honeywell office. See back page for details. Training Classes Honeywell Automation College: http://www.automationcollege.com OneWireless XYR 6000 Transmitters Quick Start Guide...
Page 5
Chassis Ground: Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements. continued Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 6
ACMA and RSM. This mark is equal to the CE Mark used in the European Union. N314 directly under the logo is Honeywell’s unique supplier identification number. The INMETRO (Brazil) mark means the tested and meets applicable...
Liechtenstein Bulgaria Lithuania Cyprus Malta Czech Republic Netherlands Denmark Norway Estonia Poland Finland Portugal France Romania Germany Slovakia Greece Slovenia Hungary Spain Iceland Sweden Ireland Switzerland Italy United Kingdom Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
CSA E60079-15: 2002 CSA E61241-0: 2002 CSA E61241-1: 2002 FM 3600: 1998 FM 3610: 1999 FM 3611: 2004 FM 3615: 2006 ANSI/ ISA 12.12.02: 2003 UL 50:2003 UL 916:1998 OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Page 13
Universal I/O Enclosure: IP66 Standards Used: EN 60079-0 : 2006 EN 60079-1 : 2004 EN 60079-11 : 2007 EN 60079-26 : 2007 EN 61241-0 : 2006 EN 61241-1 : 2004 Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 15
ABNT NBR IEC 60529:2009 IEC 61241-1 : 1999 IEC 61241-0 : 1999 *See individual Product manuals as defined on page iii for exact Models ** At time of Printing Certification was pending. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Special precautions shall be taken to prevent the surface of the antenna of the XYR 6000 Wireless Transmitter from being electrostatically charged. Maximum Working Pressure: See individual Product manuals as defined on page iii OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Installations in France must limit EIRP to 10dBm, for operating modes utilizing frequencies in the range of 2,454 – 2,483.5MHz. Japanese Restrictions For locations in Japan the transmitter power is restricted to 12.14dBm/Mhz {(32mW (15.4 dBm)] maximum EIRP including the antenna. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 18
1. Introduction Radio Certifications OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
STUW700 STUW701 STTW8x0 CETW6000M Note: Add 8.0 pounds (3.6 kg) to any model equipped with the stainless steel housing option (Model Selection Guide Table IV selections A3 or SH) Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Dimensions For Flange and Remote Seal transmitter dimensions, obtain appropriate installation drawing using Installation drawing number tables on page 16 as a guide. Figure 2-1 Temperature/DI/Multi DI/HLAI/Corrosion transmitter dimensions OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Position bracket on 2-inch (50.8 mm) pipe and install “U” bolt around pipe and through holes in bracket. Secure with nuts and lockwashers provided. Figure 2-7 Common bracket orientations OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Smaller “U” bolt. In flush flange, extended flange and pseudo flange pressure transmitter applications, the transmitter bolts directly to the process connection (tank spud) and no bracket is required. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
11 feet (3.4 meters) above the lower remote seal. Note: The combination of tank vacuum and capillary head effect should not exceed 9 psi (300 mmHg) absolute Figure 2-8 Remote Seal mounting OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Torque Screwdriver • 1.5 mm hex key Procedure WARNING Risk of death or serious injury by explosion. Do not open transmitter enclosure when an explosive gas atmosphere is present. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Display adjustment Step Action Honeywell recommends that the transmitter be removed from service and moved to a clean area before servicing. Loosen the M3 locking set screw on the display end-cap. See item 1 in Figure 2-10. Unscrew and remove the end cap.
Blow-Down Piping Piping To Low Pressure To High Pressure Side of Transmitter Side of Transmitter To Waste To Waste 21010 Figure 3-1 Typical 3-valve manifold and blow-down piping arrangement Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
As a general rule there is a 56 degree C drop (100 degrees F) in the temperature of the process for every foot (305 mm) of ½ inch uninsulated piping. OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12...
Chemical Tee, Saddle and Sanitary process connections. Dimensions of bolt circle and serrated gasket face conform to ASME B 16.5 Dimensions of bolt circle and serrated gasket face conform to EN 1092 Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Be sure all the valves in the blow-down lines are closed tight after the initial blow-down procedure and each maintenance procedure after that. Mount transmitter vertically to assure best accuracy. Position the spirit balance on pressure connection surface of AP body. Figure 3-3 Flange Mounting OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
For terminal connections see info starting on page 55. Plug battery connector into batteries. See page 47. Close rear end cap and cable gland. Tighten M3 locking screw on the rear end cap. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Close rear end cap and cable gland. Tighten M3 locking screw on the rear end cap. To voltage/current source. See wiring diagrams for all models on pages 30 and 31. Figure 3-8 Universal I/O Connection Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Note: any combination of the above are allowed. For example: PV1 is a DI, PV2 is 4-20mA, PV3 is 0-20mA. Or PV1 is 0-20mA, PV2 is a T/C, PV3 is 0-20mA OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Note: any combination of the above are allowed. For example: PV1 is a DI, PV2 is 4-20mA, PV3 is DO. Or PV1 is 4-20mA, PV2 is a T/C, PV3 is DO Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 42
Jumper wires the same gauge and stranding as the switch wires are required for all switch input combinations. Switches shall be isolated from each other and from earth ground to avoid common mode noise problems. OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Correct Pipeline Position Probe can be located at any point on the pipeline but should always be immersed in the corrosive material. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 44
Installed in a Condensate Flash Tank A condensate flash tank is also a good application. OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Page 45
In this case it is advisable to select the electrodes to be the same material as the pump’s impeller. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
(fps). Stronger flow might damage probes with three finger electrodes and interfere with the reading. If the flow rate exceeds the recommendation, a different probe style may be required. OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Feed probe wiring through the cable gland and connect to terminal block. See Figure 3-9. For terminal connections see info starting on page 55. Plug battery connector into batteries. Close rear end cap and cable gland. Figure 3-9 Corrosion transmitter with remote probe Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
If electrostatically charged, discharge of the antenna shroud to a person or a tool could possibly ignite a surrounding hazardous atmosphere. OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
If your model has the integral straight antenna (Figure 4-2) you can adjust its position by rotating the transmitter housing. (See page 20.) Typically, pointed straight up gives best performance but your installation may vary. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
If anything such as a wire or mast does come in contact with a power line, DON’T TOUCH IT OR ATTEMPT TO MOVE IT. Instead, save your life by calling the power company. Don’t attempt to erect antennas or towers on windy days. OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Add this length to the length of your tower or mast and then double this total for the minimum recommended safe distance. CAUTION If you are unable to maintain this safe distance, stop and get professional help. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Antennas are provided with a mast mounting kit consisting of a mounting bracket and two U-bolt clamps. This kit allows you to mount the antenna to masts with outside diameters (O.D.) from 1.25 inches (3.2 centimeters) to 2 inches (5.1 centimeters). Honeywell recommends that a 1.5 inch (3.8 centimeter) or larger tubing mast be used.
Page 53
12 inches (30 cm) be formed close to the XYR 6000. This will minimize ice and water buildup on the transmitter itself. Tighten cables by hand only; do not use tools or you could overtighten. To lightning arrestor & antenna 12”/30cm Drip loop Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Attach antenna to mast mounting bracket as shown using supplied hardware. Adjust antenna to desired tilt and lock into place using the antenna tilt adjustment nut. Figure 4-3 Directional antenna mounting OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Secure the lead-in wire to a lightning arrestor and mast ground wire to the building with stand- off insulators spaced from 4 feet (1.2 meters) to 8 feet (1.8 meters) apart. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 56
The lightning arrestor sold by Honeywell features a bulkhead N-Female connector with a rubber “O”-ring seal which can be used for mounting through an enclosure wall. The lightning arrestor can also be mounted using the included stainless steel mounting bracket.
Risk of death or serious injury from explosion or fire. • If IS Battery Pack, Honeywell 50047517-501, has been installed in the Wireless Transmitter, the transmitter enclosure maybe opened when an explosive gas atmosphere is present. Otherwise, do not open transmitter enclosure when and explosive gas atmosphere is present.
Procedure It is the User/Installer’s responsibility to install the XYR 6000 Wireless Transmitters in accordance with national and local code requirements. IS Battery Holder, 50025288-502 Figure 5-1: Battery assembly OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
(3.5 – 5.3 Lb-in). Re-connect battery connector. Honeywell recommends lubricating the end cap O-ring with a Silicone Grease such as Dow Corning #55 or equivalent before replacing the end cap. Screw the end cap back on and tighten the M3 locking screw.
3, to 0.4 to 0.6 N-M (3.5 – 5.3 Lb-in). Reconnect the Battery Pack connector Honeywell recommends lubricating the end cap threads with a silicone grease such as Dow Corning #55 or equivalent before replacing the end cap Screw the cap back on and tighten the M3 locking screw...
Onewireless User Interface. For more information, please reference the OW R210 Wireless Device Manager User’s Guide (OW-CC0020). See Getting Started with Honeywell OneWireless Solutions for more information. Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide...
Page 64
5. Start up Provisioning OneWireless XYR 6000 Transmitters Quick Start Guide Revision 12 February 2013...
Use the following drawings and accompanying notes and text for hazardous locations. Any deviation from the installation requirements could void the certification. For non-hazardous locations you can use the same drawings without the accompanying notes and text. EC Declaration of Conformity Revision 12 OneWireless XYR 6000 Transmitters Quick Start Guide February 2013...
Page 116
ASIA PACIFIC EMEA NORTH AMERICA SOUTH AMERICA (TAC) Honeywell Process Solutions, Honeywell Process Solutions, Honeywell do Brasil & Cia hfs-tac- Phone: + 80012026455 or +44 Phone: 1-800-423-9883 Phone: +(55-11) 7266-1900 support@honeywell.com (0)1202645583 Or 1-800-343-0228 FAX: +(55-11) 7266-1905...