ABB LLT100 Functional Safety Manual page 29

Hide thumbs Also See for LLT100:
Table of Contents

Advertisement

Series LLT100
Lidar Sensors
80 N Main St
Sellersville, PA 18960
T-013, V5R1
Certificate / Certificat / Zertifikat /
ABB 1704094 C001
Systematic Capability: SC 2 (SIL 2 Capable)
Random Capability: Type B Element
SIL 2 @ HFT=0; Route 1
PFH/PFD
avg
must be verified for each application
Systematic Capability:
The product has met manufacturer design process requirements of Safety
Integrity Level (SIL) 2. These are intended to achieve sufficient integrity
against systematic errors of design by the manufacturer.
A Safety Instrumented Function (SIF) designed with this product must not
be used at a SIL level higher than stated.
Random Capability:
The SIL limit imposed by the Architectural Constraints must be met for
each element.
IEC 61508 Failure Rates in FIT*
Device
ABB LLT100
* FIT = 1 failure / 10
9
hours
SIL Verification:
The Safety Integrity Level (SIL) of an entire Safety Instrumented Function (SIF)
must be verified via a calculation of PFH/PFD
architectures, proof test interval, proof test effectiveness, any automatic
diagnostics, average repair time and the specific failure rates of all products
included in the SIF. Each element must be checked to assure compliance with
minimum hardware fault tolerance (HFT) requirements.
The following documents are a mandatory part of certification:
Assessment Report: ABB 17-04-094 R001 V1R0
Safety Manual: AA019031-01 Rev A LLT100 SIL Safety Manual
and Architecture Constraints
λ
λ
SD
SU
0
356
considering redundant
avg
H
λ
λ
DD
DU
705
113
Page 2 of 2
Document status
29