Opcgpio general purpose i/o option module
Hide thumbs Also See for AF-600 FP Series:

Advertisement

1.2.2 Digital inputs - Terminal X30/1-4
Parameters for set-up: E-53, E-54 and E-55
Number of digital
Voltage level
inputs
3
0-24 V DC
1.2.3 Analog voltage inputs - Terminal X30/10-12
Parameters for set-up: AN-3#, AN-4# and DR-76
Number of analog voltage inputs
2
1.2.4 Digital outputs - Terminal X30/5-7
Parameters for set-up: E-56 and E-57
Number of digital outputs
2
1.2.5 Analog outputs - Terminal X30/5-8
Parameters for set-up: AN-6# and DR-77
Number of analog outputs
1
AF-650 GP and AF-600 FP OPCGPIO General Purpose I/O Option Module
Voltage levels
PNP type:
Common = 0 V
Logic "0": Input < 5 V DC
Logic "0": Input > 10 V DC
NPN type:
Common = 24 V
Logic "0": Input > 19 V DC
Logic "0": Input < 14 V DC
Standardized input signal
0-10 V DC
Output level
0 or 24 V DC
Output signal level
0/4 - 20 mA
Tolerance
± 28 V continuous
± 37 V in minimum 10 sec.
Tolerance
Resolution
± 20 V continuously
10 bits
Tolerance
± 4 V
Tolerance
± 0.1 mA
Max. Input impedance
Approx. 5 k ohm
Max. Input impedance
Approx. 5 K ohm
Max.impedance
≥ 600 ohm
Max.impedance
< 500 ohm