  • Page 2 SIMATIC, SIMATIC HMI, SIMATIC NET, SIROTEC, SINUMERIK and USS are registered trademarks of Siemens AG. Any other names used in this document may be brand names, the use of which by third parties for their own purposes may infringe the rights of the legal owners.
  • Page 3  WARNING Siemens products may only be used for the applications indicated in the catalog and in the relevant technical description. If third-party products and components are used, these must be recommended or approved by Siemens. To ensure trouble-free and safe operation of the products, they must be appropriately transported, stored, assem- bled, installed, commissioned, operated and maintained.
  • Page 4 This functional description contains the description of the software application valid at the time of publica- tion of the manual. We reserve the right to describe changes in the functionality of the software applica- tion in a special product information document. SIPLUS RIC IEC on S7 V1.5 Page 4 of 28 ©SIEMENS AG 2013...
  • Page 5: Table Of Contents

    Block parameter with its default assignment and short comment ......... 24 3.1.2.3. Parameter and functions details: ................... 24 3.1.2.4. Additional references for the processing of commands / setpoint commands ....28 SIPLUS RIC IEC on S7 V1.5 Page 5 of 28 ©SIEMENS AG 2013...
  • Page 6: General

    IEC nod with the software SIPLUS RIC Application IEC on S7 V1.5. The present description has to be perceived as a supplement of the SIPLUS RIC IEC on S7 manual V1.5. You’ll receive the blocks in the form of a SIMATIC block library.
  • Page 7: Application Blocks For Nodal Functionality

    The FB161 and FB166 blocks described here are application blocks performing Master as well as Slave functions. For more detailed information about Slave and Master blocks we refer you to the SIPLUS RIC IEC on S7 manual V1.4. Notice! All application blocks are designed exclusively for the OB1 priority level.
  • Page 8: Nodal Blocks Maosli / Slomai

    MAo_… FB_100 -> e.g. Master-blocks (MA) (FC14xff) S7_IEC_M101 L1_xy FB_100 -> e.g. L2_xy S7_IEC_M104 MA_Org_Asdu_1 L7_T101_104_B (FB12x) L1_xy L2_xy L7_T101_104_B P_Application (Master) All blocks are multiple usable. SIPLUS RIC IEC on S7 V1.5 Page 8 of 28 ©SIEMENS AG 2013...
  • Page 9 ‚S7_IEC_Config’ of the Master protocol version like the MAi-blocks. Notice! All application blocks are designed exclusively for the OB1 priority level. The FB100 communication blocks ('S7_IEC_Config') also have to be operated in priority level OB1! SIPLUS RIC IEC on S7 V1.5 Page 9 of 28 ©SIEMENS AG 2013...
  • Page 10: Nodal Block For The Monitoring Direction Maosli

    IEC-Slave. MAoSLi_MD_pDB MD is the abbreviation for Monitoring Direction. This is the signaling resp. monitoring direction (subordinated Station  SIPLUS RIC IEC on S7  control station) MAoSLi_MD_pDB pDB is the abbreviation for parameterizable by DB (option) The available MAoSLi-functional blocks are shown in the following overview.
  • Page 11: Nodal Block Maosli_Md_Pdb (Fb161)

     Optional assignable parameter block for Individual quantity structure Address conversion (of the information object address) parameterizable threshold for measured values per information possibility of image access (diagnosis / further processing) SIPLUS RIC IEC on S7 V1.5 Page 11 of 28 ©SIEMENS AG 2013...
  • Page 12: Block Parameter With Its Default Assignment And Short Comment

    Number of information, actually placed in the No_used_IMs image data block Signals that the number of Images has been New_Image BOOL FALSE increased within this cycle SIPLUS RIC IEC on S7 V1.5 Page 12 of 28 ©SIEMENS AG 2013...
  • Page 13: Parameter And Functions Details

    Via this pointer resp. the data range behind values like ASDU address, actual time stamp, send buffer etc. are taken over from ORG block as well as general interroga- tions are processed. SIPLUS RIC IEC on S7 V1.5 Page 13 of 28 ©SIEMENS AG 2013...
  • Page 14 Bit 2 Bit 1 Bit 0 Type Def. With the default adjustment (B#16#7F) all information except for the integrated totals (IT) are transmitted after an interrogation command. SIPLUS RIC IEC on S7 V1.5 Page 14 of 28 ©SIEMENS AG 2013...
  • Page 15 NOTICE! Please note the permissible valuation of the block parameters. They are not mandatory checked for plausibility. Incorrect inputs can cause unpredictable responses and incor- rect functions. SIPLUS RIC IEC on S7 V1.5 Page 15 of 28 ©SIEMENS AG 2013...
  • Page 16: General Notes About Function And Handling Of The Block

    The values contained in ‚IM_Value‘ have to be read as Dword / Dint or Real Measured values in ‚IM_Value‘ are always available as Real value in Simatic format, independ- ent like from receive value. SIPLUS RIC IEC on S7 V1.5 Page 16 of 28 ©SIEMENS AG 2013...
  • Page 17 W#16#A1 Para_DB_Type not change Global. Array [1..10] Internal use: Last processed info - do not 22.0 B#16#0 Internal BYTE change ! 12.0 32.0 END_STRUCT END_STRUCT (12 BYTE) SIPLUS RIC IEC on S7 V1.5 Page 17 of 28 ©SIEMENS AG 2013...
  • Page 18 !!! These values are parameter and can be adjusted !!! Note: Changes have to be performed always in the ‚Data view’, and not in the ‚Declaration view' (except dimensioning of the array). SIPLUS RIC IEC on S7 V1.5 Page 18 of 28 ©SIEMENS AG 2013...
  • Page 19 You find supported values in the corresponding chapters for block description Internal used. Don’t change the identification for this parameter DB! Para_DB_Type Internal used. Lastly processed information – don’t change! Internal SIPLUS RIC IEC on S7 V1.5 Page 19 of 28 ©SIEMENS AG 2013...
  • Page 20 With P_Threshold_Value it is possible to parameterize an individual threshold for measured values. Without specification (default = 0.0) an optional global thresh- old specified at the block input ‚Threshold_Val_ME‘ is effective. Value_Last Internally use Threshold_Memory Internally use SIPLUS RIC IEC on S7 V1.5 Page 20 of 28 ©SIEMENS AG 2013...
  • Page 21 S7_IEC_Config parameter ‚More_Info_available’ and ‚Next_Info’ the data performance per OB1 cycle can be in- creased. This with minor increase of the cycle time. SIPLUS RIC IEC on S7 V1.5 Page 21 of 28 ©SIEMENS AG 2013...
  • Page 22: Nodal Block For The Command Direction Slomai

    SLoMAi_CD_pDB CD is the abbreviation for Command Direction, this is the Command resp. control direction (Control center  SIPLUS RIC IEC on S7  subordinated station) SLoMAi_CD_pDB pDB is the abbreviation for parameterizable by DB (option) The available SloMAi functional blocks can be seen in the following overview Block Block-No.
  • Page 23: Nodal Block Slomai_Cd_Pdb (Fb166)

    Output for external evaluation of an active input command existing  Function (output) independent from received TK  Command storage and serial output of the buffered commands possible (number according to ‚Cmd_Buffer_Dim) SIPLUS RIC IEC on S7 V1.5 Page 23 of 28 ©SIEMENS AG 2013...
  • Page 24: Block Parameter With Its Default Assignment And Short Comment

    100000000 (eight zeros) has to be en- tered. I.e. If the parameters have to be taken from the DB1301 the value L#100001301 has to be entered. SIPLUS RIC IEC on S7 V1.5 Page 24 of 28 ©SIEMENS AG 2013...
  • Page 25 NOTICE! Please note the permissible valuation of the block parameters. They are not mandatory checked for plausibility. Incorrect inputs can cause unpredictable responses and incor- rect functions. SIPLUS RIC IEC on S7 V1.5 Page 25 of 28 ©SIEMENS AG 2013...
  • Page 26 !!! These values are parameter and can be adjusted !!! Note: Changes have to be performed always in the ‚Data view’, and not in the ‚Declaration view' (except dimensioning of the array). SIPLUS RIC IEC on S7 V1.5 Page 26 of 28 ©SIEMENS AG 2013...
  • Page 27 IEC101/104 information object address (IOA) for the transfer of the command mes- sage to the destination. If ‚0‘ is specified her, the transfer is carried out with the re- ceived address. SIPLUS RIC IEC on S7 V1.5 Page 27 of 28 ©SIEMENS AG 2013...
  • Page 28: Additional References For The Processing Of Commands / Setpoint Commands

    Master is cleared. This avoids the delayed output of commands which were activated during an identified connection failure. The corresponding commands have to be initiated new if necessary. SIPLUS RIC IEC on S7 V1.5 Page 28 of 28 ©SIEMENS AG 2013...