  • Page 1 Sensors EasyAir SNS300 Design-in Guide Single, compact, cost-effective luminaire control Philips EasyAir SNS300 August 2019...
  • Page 2: Table Of Contents

    Limited functions of Philips Field Apps Mechanical design-in Mounting to a luminaire Wiring diagram with Philips Xitanium SR LED driver 12 Labeling for field installation and commissioning 14 Recommendations to design a luminaire around EasyAir SNS300 with good RF signal...
  • Page 3: Introduction To This Guide

    Introduction to this guide Thank you for choosing the Philips EasyAir SNS300. In this guide, luminaire manufacturers will find the information required to design this product into a luminaire and configure it to suit specific applications. This design-in guide covers sensor functionality, mechanical mounting and wiring details.
  • Page 4: Warnings And Instructions

    Warnings and instructions • EasyAir SNS300 must be used only with a Philips Xitanium SR LED driver. • Do not apply mains power directly to the sensor. • Do not cover the sensor during operation or mount the sensor recessed.
  • Page 5: Introduction Of Easyair Sns300

    With the added Zigbee functionality, EasyAir SNS300 can now be an integral part of networks also based on the Zigbee standard. A program is under development by Philips to qualify third-party network systems for use with EasyAir SNS300.
  • Page 6: Product Characteristics

    2.5m to 3m. NFC antenna Device model/version information and MAC address can be read out using the Philips Field Apps (EasyAir SNS300 NFC). NFC is the set of protocols that enables electronic devices to establish radio...
  • Page 7: Motion Detector

    Therefore, it is recommended not to use EasyAir SNS300 in outdoor, parking or industrial applications. Please refer to the EasyAir SNS300 datasheet for coverage area details. Figure 1. Motion detection area. H: ceiling height. Minor movement detection area: X1 by Y1. Major movement detection area: X2 by Y2.
  • Page 8 If such shield is not needed in the application, it can be easily pulled out from the sensor or left inverted. Design-in Guide - EasyAir SNS300 April 2019 August, 2019...
  • Page 9: Light Sensor

    120 140 160 180 200 220 240 260 280 Lighting control Calibration and lighting control is done by the Figure 4. Sensor mounting height from window sill (Y) vs. sensor horizontal distance from window sill (H). coordinating network system. August, 2019 Design-in Guide - EasyAir SNS300 April 2019...
  • Page 10: Limited Functions Of Philips Field Apps

    Limited functions of Philips Field Apps The EasyAir SNS300 NFC App can be used to read out model/version information of SNS300 and the MAC address. The EasyAir SNS300 IR App can be used to reset the network settings of individual sensor.
  • Page 11: Mechanical Design-In

    Max sheet metal thickness is 1mm. Note: Please make sure the the EasyAir SNS300 RF antenna is not covered by metal. August, 2019 Design-in Guide - EasyAir SNS300...
  • Page 12: Wiring Diagram With Philips Xitanium Sr Led Driver

    >=600V/90C. NEUTRAL SGND Strip wire to 3/8”. LINE NFC ANTENNA Connectors (non-polarized) Figure 5. Wiring diagram with Philips Xitanium SR driver. Applicable wires Xitanium SR LED driver Wire Range Number of Conductors / Insulation Conductor AWG# Diameter of a Conductor...
  • Page 13 Wire insertion Wire distance for remote mounting It is recommended to keep the wire distance from sensor to Philips Xitanium SR LED driver less than 50 feet and meet the wire gauge requirement to guarantee the performance. 5°~ 7° Angle Max [ Inserting solid conductors via push-in terminal ] Figure 8.
  • Page 14: Labeling For Field Installation And Commissioning

    Also be sure to include instructions to the installer for proper handling of these labels during luminaire installation. Design-in Guide - EasyAir SNS300 April 2019 August, 2019...
  • Page 15: Recommendations To Design A Luminaire Around

    EasyAir SNS300 with good RF signal It is recommended to have one side metal wall distance from EasyAir SNS300 antenna side wall > 100mm (assuming other metal walls are far away, see figure 11, then luminaire to luminaire distance can be >...
  • Page 16: Sensor Spacing Recommendations

    The occupancy detection area is determined by the following aspects: a. Orientation of the sensors b. Height at which the sensors are mounted See below a snippet from EasyAir SNS300 datasheet describing occupancy sensing Height Minor Movement Major Movement For example: 2.4 m...
  • Page 17: Installing Easyair Sns300 With Ceiling Mount Bracket (Sns300Cmp)

    Installing EasyAir SNS300 with ceiling mount bracket (SNS300CMP) The ceiling mount bracket SNS300CMP is premounted with the EasyAir SNS300 and the cable. The strain relief is already part of the CMP300. Drill 63.5 mm hole in the ceiling for installation of the SNS300CMP bracket. For more details on cut-out and mounting, refer the figures below.
  • Page 18: Easyair Sns300 With Multiple Philips Xitanium Sr Led Drivers (1:N Application)

    The regular DALI drivers have basic insulation on the DALI interface as safety barrier. The SR drivers / bridge have double insulation on the SR interface. As EasyAir SNS300 devices do not have additional insulation barriers, it means that using DALI drivers via SR bridge maintains the double insulation level.
  • Page 19: Contact Details

    Contact details Philips EasyAir SNS300 Product information: www.lighting.philips.co.uk/oem-emea/products/ easy-to-integrate-wireless-sensors.html Or contact your local Philips sales representative. August, 2019 Design-in Guide - EasyAir SNS300 April 2019...
  • Page 20: Disclaimer

    Disclaimer ©2018 Philips Lighting Holding B.V. All rights reserved. Note that the information provided in this document is subject to change. This document is not an official testing certificate and cannot be used or construed as a document authorizing or otherwise supporting an official release of a luminaire.
  • Page 21 The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract. Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.