Service instructions for contractors
Control unit
Control 8313

Advertisement

Table of Contents
loading

Summary of Contents for Bosch Control 8313

  • Page 1 Service instructions for contractors Control unit Control 8313...
  • Page 2: Table Of Contents

    Submenu Thermal disinfection ....36 Calling up the service menu..... . 14 Control 8313 – 6720859567 (2017/03)
  • Page 3: Explanation Of Symbols And Safety Instructions

    23.3.2 Explanation of symbols ......51 correctly. Defects must be remedied immediately. 23.3.3 Explanation of symbols, portal settings ... .53 ▶ Before commissioning the heating system, read these instructions carefully. Control 8313 – 6720859567 (2017/03)
  • Page 4 ▶ Explain that conversions and repairs must only be carried out by a competent person. ▶ Point out the need for inspections and maintenance for safe and environmentally-compatible operation. ▶ Leave the installation instructions and the operating instructions with the user for safekeeping. Control 8313 – 6720859567 (2017/03)
  • Page 5: Product Information

    For a description of this function, refer to the technical documentation This product contains proprietary software by Bosch (licensed for the module. according to the Bosch standard licensing conditions) and Open Source Determined use Software (licensed according to the Open Source licensing conditions).
  • Page 6: Modules And Their Function

    • Flue gas test • Reset (e.g. high limit safety cut-out, SAFe) FM-SI Due to the length of the SI connecting lead, the safety module should be mounted at slot 1. Control 8313 – 6720859567 (2017/03)
  • Page 7: Central Module Zm5313

    • ICOM Water treatment guide for commercial heating systems. • Country-specific regulations to protect potable water (e.g. DVGW Code of practice W551– Drinking water protection) • Manufacturer's technical Codes of Practice (e.g. in the catalogue) • National standards and regulations Control 8313 – 6720859567 (2017/03)
  • Page 8: Installation

    If other instructions for components are disregarded, the heating system may develop faults or be damaged due to incorrect connections/settings. ▶ Follow the directions in all instructions for the components that are to be installed. Control 8313 – 6720859567 (2017/03)
  • Page 9: User Interface Connections (Hmi)

    User interface connections Slide type insert for SD card CAN-BUS connection (no function, provided for subsequent functions) Modbus-RTU connection for Bosch/Bosch CHP module EMS connection (connection for EMS heat source with its own basic control (control panel)) Address setting of control unit...
  • Page 10: Connection To A Ems Heat Source

    (e.g. because the plug-in connector has not been inserted), the components assigned to this module are not switched on (e.g. pumps). This malfunction cannot be detected at the user interface itself as the display and control functions are independent of the 230 V voltage. Control 8313 – 6720859567 (2017/03)
  • Page 11: Operation Of The Control Unit

    Reset button (e.g. high limit safety cut-out, SAFe) Chimney sweep button (for Flue gas test) Manual operation key USB connection (e.g. for service purposes) LED status display Data plate F1-, F2 circuit breaker [10] ON/OFF switch Control 8313 – 6720859567 (2017/03)
  • Page 12: Function Buttons And System Status

    Display of Internet connection accompanied by an explanation. Display of system components Advanced functions for heating circuit, DHW Display of time [10] Press field to switch between display types on the display [11] Information menu Control 8313 – 6720859567 (2017/03)
  • Page 13: Operating The Appliance

    Name of safety equipment Free Allocated If parameters are linked to settings, a temperature, for example, can only Cancel be selected/modified if the function is set to On. Save Fields that are not active are highlighted in grey. Control 8313 – 6720859567 (2017/03)
  • Page 14: Calling Up The Service Menu

    The parameters for defining the conditions under which the flue gas test is carried out are shown in the display. ▶ Setting parameters (e.g. modulation). ▶ Tap Save. The heat source is operated at the set output. Control 8313 – 6720859567 (2017/03)
  • Page 15: Key For Manual Operation, Emergency Operation

    The LED status display lights up yellow. Manual operation The “manual operation” operating mode can be set and adjusted for every function separately. ▶ Observe the operating instructions of the control unit. Control 8313 – 6720859567 (2017/03)
  • Page 16: Commissioning

    Address setting of control unit Jumper for activating the Modbus-RTU terminating resistance Jumper for activating the CAN-BUS terminating resistance Battery CR2032 Network connection 2 (CBC-BUS) [10] Network connection 1 (Internet, Modbus TCP/IP, CBC-BUS) [11] USB connection Control 8313 – 6720859567 (2017/03)
  • Page 17: Menu Structure

    Shows the faults in the heating system. The user interface can only display the faults for the chapter 11.3, page 32 control unit it is connected to. Chapter 20.5, page 45 and chapter 20.6, page 45 Table 5 Main menu Control 8313 – 6720859567 (2017/03)
  • Page 18: General Characteristic Data

    Slot for boiler module installation of the modules for slot A Slot 1...4 None Slots for function modules and auxiliary modules Module selection The installed modules can be selected from a list. Table 7 Module selection menu Control 8313 – 6720859567 (2017/03)
  • Page 19: Boiler Parameters

    Boiler temperature No/Yes 5 K is added to the desired set value for the boiler increase at low loss temperature, so that the set value can be reached header quickly and safely. Control 8313 – 6720859567 (2017/03)
  • Page 20: Settings Of The Safety Equipment

    Max-pressure1/2 = maximum pressure must be jumpered. Neutralisation limiter 1 or 2 STB 2 safe. Min-pr.WMS = minimum pressure limiter or low water indicator STB2 Safety = 2nd safety temperature limiter Table 9 Safety equipment settings Control 8313 – 6720859567 (2017/03)
  • Page 21: Heating Circuit Data

    The heating circuit is regulated via the flow temperature of the heat source if no heating circuit mixing valve is installed. No heating circuit mixing valve is entered for heating circuit 00. Control 8313 – 6720859567 (2017/03)
  • Page 22 Display of faults for a pump via 1/2 and external display for pump changeover via 1/3. WF1/2 and External fault display for pump WF1/2 and external heating/ setback mode WF1/3 WF1/3 Table 10 Basic settings of heating circuits Control 8313 – 6720859567 (2017/03)
  • Page 23: Heating Curve, Operating Mode

    This setting is only recommended if no remote between the actual and set temperature control has been installed inside the living space.  Chapter 12.1.3, page 33 This adjustment effects a parallel displacement of the heating curve. Control 8313 – 6720859567 (2017/03)
  • Page 24 For the settings of the setback Automatic heating mode types, refer to  Chapter 12.1.2, page 33. mode. Automatic setback mode Holiday Table 13 Settings for the operating modes of the Radiator/Underfloor Heating heating curve Control 8313 – 6720859567 (2017/03)
  • Page 25 -50...17...50 °C The heating circuit is switched off when the set outside temperature is exceeded and switched back on when it is undercut. Table 15 Settings for the operating modes of the Holiday heating curve Control 8313 – 6720859567 (2017/03)
  • Page 26: Frost Protection

    2...12...24 h Setting the time that must elapse (e.g. in the event of a power failure) in order still to be able to continue the drying process successfully. Table 17 Menu Heating circuit > Screed drying Control 8313 – 6720859567 (2017/03)
  • Page 27: Domestic Hot Water

    Terminals WF1 and WF3 charging Thermal disinfection Off/On Further settings required ( Chapter 9.5.1, page 28)! Circulation Off/On DHW is immediately available at the draw-off Further settings required points. ( operating instructions)! Table 19 DHW settings Control 8313 – 6720859567 (2017/03)
  • Page 28: Thermal Disinfection

    You can uncouple the control units with the field Continue and retain the coupling with the field Cancel Cancel. Time overrun xxx Second Modbus communication With Heartbeat Without Heartbeat Allow write permission Providing data from substations Heat requirement via Modbus Control 8313 – 6720859567 (2017/03)
  • Page 29: Lock Screen

    The default password is 0000 be locked by a 4-digit password. ( Chapter 18, page 43). Main menu Service menu (Service) Reset ▶ Change password. You can enter your own password here. Table 22 Lock screen Control 8313 – 6720859567 (2017/03)
  • Page 30: Information On The General Data Main Menu

    Athens –2 Berlin –15 Brussels –10 Budapest –12 Bucharest –20 Frankfurt/Main –14 Hamburg –12 Helsinki –24 Istanbul –4 Copenhagen –13 Lisbon London –1 Madrid –4 Marseilles –6 Control 8313 – 6720859567 (2017/03)
  • Page 31: External Heat Requirement

    0...10 V inputs of a control unit are connected. An open input The start value (start-up point) of the curve is set to 0.6 V with a positive corresponds to 0 V and thus to an output demand of e.g. 100 %. curve ( Fig. 15). Control 8313 – 6720859567 (2017/03)
  • Page 32: Information On The Boiler Parameters Main Menu

    43.0 28.7 21.5 129.0 64.5 43.0 32.2 1000 172.0 86.0 57.3 43.0 1500 258.0 129.0 86.0 64.5 2000 343.9 172.0 114.6 86.0 Table 24 Recommended flow rates for sizing the boiler circuit pump PK [m/h] Control 8313 – 6720859567 (2017/03)
  • Page 33: Information On The Heating Circuit Data Main Menu

    Fig. 17 Views of operating modes – Contacts WF1 and WF3 open = setback mode Display in the service menu Display as heating circuit Manual operation Manual heating mode Auto Manual setback mode Advanced functions Holiday Control 8313 – 6720859567 (2017/03)
  • Page 34 This change does not affect the other parameters. If you reselect the the Auto and Manual setback mode operating modes are not affected. If you reselect the function, the value is displayed again. function, the value is displayed again. Other settings do not affect the value. Control 8313 – 6720859567 (2017/03)
  • Page 35: Setback Types

    Minimum flow temperature Maximum flow temperature Settings for the parameters: Heating curve Standby mode Operating mode Design temperature Cancel Heating Limit (Summer from / Outdoor Setback) Save [10] Room temperature [11] Outdoor temperature Control 8313 – 6720859567 (2017/03)
  • Page 36: Submenu Screed Drying

    Prerequisites for screed trying with a heating circuit without mixer: • Floor standing condensing boiler with no requirement for the minimum boiler temperature • The heat intake when drying must be greater than the minimum boiler output Control 8313 – 6720859567 (2017/03)
  • Page 37: Information On The Reset Main Menu

    The lead boiler (Master) has the control unit address 0. ▶ Insert LAN cable in the LAN2 connection ( Fig. 13, [10], page 16). ▶ Set the address switch ( Fig. 13, [5], page 16) to 0. Control 8313 – 6720859567 (2017/03)
  • Page 38: Control Unit Coupling

    Press field to access the selected control unit in the system overview or in the control unit overview Once started, the coupling process runs in the background. To network the control units: Control 8313 – 6720859567 (2017/03)
  • Page 39 Network connection is active, connection with router is active, no connection with server • Visible and red Network connection is active, no connection with router and server • Not visible Network connection is not active Control 8313 – 6720859567 (2017/03)
  • Page 40: Set Up Access To Mec Remote Portal

    • Password (The password must be at least 12 characters long in Confirm your acceptance of the following:"I accept the Conditions keeping with Bosch rules, and include at least one special character of use. If you are a consumer, you have the right to revoke in in addition to upper and lower case letters.)
  • Page 41: Accessing The Mec Remote Portal

    ▶ Fill out the relevant fields. [19] System ▶ Tap Send field. The new login data is sent to the stored e-mail address. ▶ Tap the field. The change mask opens. ▶ Make changes in the fields and confirm. Control 8313 – 6720859567 (2017/03)
  • Page 42: User Settings

    Resetting the password To reset the password: ▶ Tap Unlock/reset password field. An e-mail is sent to the stored email address. ▶ Open e-mail and click on the link provided. ▶ Assign new password and save. Control 8313 – 6720859567 (2017/03)
  • Page 43: Information On The Function Check Main Menu

    12:00 0010008709-001 Fig. 33 DHW Function test Cylinder primary pump Circulation pump Off/On Cylinder primary pump status Circulation pump status Once the Function test is complete, the activated system components are switched back off. Control 8313 – 6720859567 (2017/03)
  • Page 44: Information On The Monitor Data Main Menu

    ▶ Save. ▶ Insert service adapter into the USB port ( Fig. 5, [6], page 11). ▶ Open web browser and enter “cbc.bosch”. The user interface of the control unit is mirrored on the computer. The control unit can only be operated by one person.
  • Page 45: Fault History

    ▶ Check whether Actuator No has been • The FM-MM module or the control unit is selected ( Tab. 10, page 22). faulty. ▶ Replace the module if necessary. Control 8313 – 6720859567 (2017/03)
  • Page 46 ▶ Find the cause of the high limit safety cut- triggered • The high limit safety cut-out has responded. out trigger (e.g. check control unit functions). • The control unit is faulty. ▶ Remedy the cause. Control 8313 – 6720859567 (2017/03)
  • Page 47 • Each address must only be assigned once in ▶ Each address must only be assigned once disrupted the CAN-BUS network. in the CBC-BUS network. Control functions requiring data exchange via the CBC-BUS can no longer be executed. Control 8313 – 6720859567 (2017/03)
  • Page 48: Cleaning The Control Unit

    To dispose of old electrical or electronic devices, you should use the return and collection systems put in place in the country concerned. Batteries must not be disposed together with your household waste. Used batteries must be disposed of in local collection systems. Control 8313 – 6720859567 (2017/03)
  • Page 49: Appendix

    10 ... 600) Maximum switching current • Pump outputs Temperature sensor NTC sensor Ø External optional function WF Potential-free input DC/mA Contact load 5/10 1) Max. cable length 10 m Table 29 FM-MM function module specifications Control 8313 – 6720859567 (2017/03)
  • Page 50: Sensor Curves

    –10 54889 SAFe burner control unit –5 42069 32506 25313 19860 15693 12486 10000 8060 6536 5331 4372 3605 2989 2490 2084 1753 1480 1258 1070 Table 32 Pressure drop values of 53xx temperature sensor Control 8313 – 6720859567 (2017/03)
  • Page 51: Explanation Of Symbols And Keys

    Selection or display of hot water production data. Measured room temperature Display of measured room DHW circulation time program Adjustment or display of time temperature program (e.g. for the heating circuits or the DHW circulation pump) Control 8313 – 6720859567 (2017/03)
  • Page 52 Burner starts Display number of burner Advanced functions Additional setting options for starts the heating circuit, DHW, etc. Max. boiler temperature Display of temperature set as Actuator Status display of mixing valve the maximum value Control 8313 – 6720859567 (2017/03)
  • Page 53: Explanation Of Symbols, Portal Settings

    Change the settings or system data. Mirror system data Transfer control unit view to User settings Customising the portal settings the monitor Exit portal End access to the control unit Table 36 Explanation of symbols, portal settings Control 8313 – 6720859567 (2017/03)
  • Page 56 Bosch Thermotechnik GmbH Junkersstrasse 20-24 D-73249 Wernau www.bosch-thermotechnology.com...