Properties
● Technical properties
– Fail-safe digital module for use in the S7-1500 automation system and in the
– PROFIsafe
– PROFIsafe address type 2
– Supports the RIOforFA-Safety profile (on S7-1500 F-CPUs)
– 8 output PM-switching or PP-switching in 2 channel groups (SIL3/Cat.4/PLe)
– Supply voltage L+
– Output current per output 2 A
– Source output (PM/PP-switching)
– Suitable for solenoid valves, DC contactors and signal lamps
– Status display RUN (green LED)
– Status display module diagnostics (red LED)
– Status display channel status/channel diagnostics per output (green/red LED)
– Status display supply voltage (green LED)
– Diagnostics, e.g., short-circuit/wire break/load voltage missing, channel-specific
– Channel-specific or module-wide passivation
● Supported functions
– Firmware update
– I&M identification data
The fail-safe performance characteristics in the technical specifications apply for a mission
time of 20 years and a repair time of 100 hours. If a repair within 100 hours is not possible,
switch off the supply voltage of the affected module before 100 hours expires. The module
switches off independently after the 100 hours have expired.
Follow the repair procedure described in section Diagnostic alarms (Page 46).
Accessories
The following accessories are supplied with the module and can also be ordered as spare
part:
● Labeling strips
● U-connector
● Universal front cover
● Electronic coding element
Digital output module F-DQ 8x24VDC/2A PPM (6ES7526-2BF00-0AB0)
Manual, 01/2016, A5E03858037-AA
ET 200MP distributed I/O system.