Technical specifications

General technical data
Table 5- 1
General technical data
Line frequency
Product standard
Overload capacity
Specific technical data
Table 5- 2
Technical data of line filter 380 V – 480 V 3 AC
Article No.
Rated voltage
Rated current I
R
Power loss
Line/load connection
L1, L2, L3, L1', L2', L3'
PE connection
Degree of protection
Dimensions
Width
Height
Depth
Weight
Line filter
Operating Instructions, 05/2017, A5E32844996B AE
47 ... 63 Hz
EN 61800-5-1
1.60 x I
for 3 s followed by
R
1.36 x I
for 60 s followed by
R
1.00 x I
for 240 s
R
6SL3000-0BE33-
1AA0
V
A
400
kW
0.047
M10 connecting
lugs
M8
IP00
mm
360
mm
240
mm
116
kg
12.7
6SL3000-0BE35-
0AA0
380 V 3 AC –10% to 480 V 3 AC +10% (-15% < 1 min)
600
0.06
M10 connecting
lugs
M10
IP00
390
265
140
19.9
6SL3760-0MR00-
0AA0
1200
0.106
M12 connecting
lugs
M10
IP00
425
265
148
25
5