ABB NBRA-6 Series Installation And Startup Manual page 15

Braking choppers
Table of Contents

Advertisement

Braking
ACS 600
Chopper
Type
Type
(continued)
690 V a.c. Units:
-0009-6
NBRA-663
-0011-6
NBRA-663
-0016-6
NBRA-663
-0020-6
NBRA-663
-0025-6
NBRA-664
-0030-6
NBRA-664
-0040-6
NBRA-666
-0050-6
NBRA-666
-0060-6
NBRA-666
-0070-6
NBRA-666
-0100-6
NBRA-667
-0120-6
NBRA-667
-0140-6
NBRA-669
-0170-6
NBRA-669
-0210-6
NBRA-669
-0260-6
NBRA-669
-0320-6
NBRA-669
-0400-6
NBRA-669
-0490-6
2xNBRA-669 2x(2xSAFUR125F500)
-0610-6
2xNBRA-669 2x(2xSAFUR210F575)
-0760-6
2xNBRA-669 2x(2xSAFUR200F500)
R
Resistance value for the listed resistor type. Note: This is also the minimum allowed resistance value for the braking
resistor.
E
Energy pulse that the resistor assembly will withstand (400 s duty cycle). This energy will heat the resistor element
R
from 40 °C to the maximum allowable temperature.
P
Continuous power (heat) dissipation of the resistor when placed correctly. Energy E
Rcont
A
Conductor cross-sectional areas for the copper cable to be used for connecting the braking resistor and the chopper
(or the chopper and the ACS 600). The cable should have a concentric conductor (screen). The standard cables with
three-phase conductors and a concentric conductor are given. A two-conductor screened cable may also be used if
available.
P
Maximum braking power of the ACS 600 equipped with the standard chopper and the standard resistor. The drive and
BRmax
the chopper will withstand this braking power for one minute every ten minutes. Note: The braking energy transmitted
to the resistor during any period shorter than 400 seconds may not exceed E
* The SACE04RE40 resistor consists of four resistor elements connected in parallel. The resistance of one element is 160 ohm.
The SACE15RE13 resistor consists of four resistor elements connected in parallel. The resistance of one element is 52 ohm.
The SACE15RE22 resistor consists of four resistor elements connected in parallel. The resistance of one element is 88 ohm.
The SAFUR resistors consist of several resistor elements. The resistance of one element is 8 ohm
The NBRA-653 and -663 are to be installed outside the converter module. Their degree of protection is IP54.
The NBRA-654, -655, -656, -657, -664, -666 and -667 are to be installed inside the converter module.
The NBRA-658, -659 and -669 are to be installed outside the converter module. Their degree of protection is IP00.
All braking resistors are to be installed outside the converter module.
The SACE braking resistors are built in an IP21 metal housing.
The SAFUR braking resistors are built in an IP00 metal frame.
Installation and Start-up Guide for NBRA-6xx
Braking Resistor(s)
Type
SACE08RE44
SACE08RE44
SACE08RE44
SACE15RE22
SACE15RE13
SACE15RE13
SACE15RE13
SAFUR90F575
SAFUR90F575
SAFUR90F575
SAFUR80F500
SAFUR125F500
SAFUR210F575
SAFUR200F500
SAFUR200F500
2xSAFUR125F500
2xSAFUR210F575
2xSAFUR200F500
R
E
P
R
Rcont
[ohm]
[kJ]
[kW]
44.0
210
1
44.0
210
1
44.0
210
1
22.0
420
2
13.0
435
2
13.0
435
2
13.0
435
2
8.0
1800
4.5
8.0
1800
4.5
8.0
1800
4.5
6.0
2400
6
4.0
3600
9
3.4
4200
10.5
2.7
5400
13.5
2.7
5400
13.5
2.0
7200
18.0
1.7
8400
21.0
1.35
10800
27.0
2x2.0
2x7200
2x18.0
2x1.7
2x8400
2x21.0
2x1.35
2x10800
2x27.0
Chapter 2 – Overview
Cable
(Copper)
A
No. of
2
Elements*
[mm
]
2
3x6+6
2
3x6+6
2
3x6+6
4
3x6+6
4
3x6+6
4
3x6+6
4
3x25+16
9
3x25+16
9
3x25+16
9
3x35+16
12
3x70+16
18
3x70+35
21
see Table 2-2
27
see Table 2-2
27
see Table 2-2
2x18
see Table 2-2
2x21
see Table 2-2
2x27
see Table 2-2
2x(2x18) see Table 2-2
2x(2x21) see Table 2-2
2x(2x27) see Table 2-2
dissipates in 400 seconds.
R
.
R
.
Braking
Power
P
BRmax
[kW]
8.5
12.9
13.8
19.8
29.1
35.0
40.2
53.0
65.4
80.1
94.4
132.5
158.1
193.4
228.5
275.9
346.7
403.7
524.2
658.7
767.0
2-5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents