Haier N Series Service Manual page 54

Wall mounted type dc inverter free match
Hide thumbs Also See for N Series:
Table of Contents

Advertisement

. .4 Outdoor DC fan motor fault
Outdoor display
Method of
malfunction detection
Malfunction detection
conditions
Conditions
Supposed
Causes
Troubleshooting
may be occurred.
Check whether Terminal on the outdoor
mainboard is well inserted.
LED1 flash 9 times
DC fan motor is detected by checking the fan running condition and so on
when the data of EEPROM is error or the EEPROM is damaged
DC fan motor protection dues to the DC fan motor faulty
DC fan motor protection dues to faulty PCB
* Caution Be sure to turn off power switch before connect or disconnect connector,
Is it normal?
Yes
Electrify the machine again and turn it
on in the Cool state with the remote
controller. check whether motor can
run
Yes
Measure the voltage between 3 and 6 of
the terminal about 0-5v.
Is it normal?
N0
the motor of the outdoor unit is damaged and
needs replacing.
NO
Reinsert the terminals
NO
Measure the voltage between 1 and 3 of the terminal of
fan motor on the mainboard about DC310V, Measure
the voltage between 3 and 4 of the terminal about
DC15V. Measure the voltage between 5 and 3 of the
terminal about 1-6v.
Yes
Is it normal?
Yes
The mainboard of the outdoor unit is
damaged and needs replacing
Service diagnosis
or parts damage
N0
Domestic air conditioner