Specifications - Siemens 985-047 Operating Instructions Manual

Actuator commissioning tool
Table of Contents

Advertisement

Specifications

Power Requirements
Commissioning Tool
Plug-in Transformer (provided)
Input DC Feedback
0 to 30 Vdc
Electrical Connection
Screw Terminals
Transformer Jack
Input Impedance
Voltmeter
Output Signal
AC Power
Resistive
Proportional
Floating Control
Bias
Accuracy
 2% of full scale at 77°F (25°C)
Resolution
0.1 Vdc, 0.1 mA
Auxiliary Switch
Provides 24 Vac at 4 mA to auxiliary switch contacts (dry contacts only).
Testing
Response Time
Proportional, Voltage
Proportional, Current
Ambient Conditions
Operating
Storage
Dimensions
Commissioning Tool (overall)
(H x W x D)
Transformer
Carrying Case
Weight
Commissioning Tool
Transformer
Carrying Case
Total Shipping Weight
5.4 lb (2.5 kg)
The performance specifications are nominal and conform to acceptable industry standards. Siemens Building Technologies, Inc.
shall not be liable for damages resulting from misapplication or misuse of its products.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models
as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. ©
2009 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
U.S.A.
24 Vac nominal (20 to 30 Vac) at 50/60 Hz, 3 VA, Class 2
120 Vac at 60 Hz
24 to 12 AWG
0.08 in. (2.11 mm) diameter pin, 0.25 in. (6.35 mm) diameter plug
1 Megohm (nominal)
24 Vac nominal (20 to 30 Vac), 25 VA maximum (Terminals 1 and 2).
Output AC voltage is equivalent to the input AC voltage and
frequency.
0 to 135 ohms ±7%, 2W or 0 to 1k ohms ±5%, 2W (Terminals 3, 4,
and 5).
Voltage — 0 to 10 Vdc (500 ohms minimum); 0 to 20 Vdc
(6.8k ohms minimum) (Terminals 2 and 3);
Current — 0 to 20 mA (680 ohms maximum) (Terminals 2 and 3).
24 Vac nominal (20 to 30 Vac), 25 VA maximum (Terminals 2, 3,
and 4). Output AC voltage is equivalent to the input AC voltage and
frequency.
5 Vdc with 330 ohm series resistor (Terminal 6).
0 to 20 Vdc in 20 seconds
0 to 20 mA in 20 seconds
–4 to 122°F (–20 to 50°C); 10 to 90% RH, non-condensing
–40 to 158°F (–40 to 70°C); 5 to 95% RH, non-condensing
7.7 in. x 4.5 in. x 2.2 in. (196 mm x 113 mm x 55 mm)
4.2 in. x 3.0 in. x 2.4 in. (107 mm x 76 mm x 61 mm)
10.4 in. x 12.7 in. x 4.2 in. (263 mm x 322 mm x 107 mm)
0.9 lb (0.4 kg)
1.7 lb (0.8 kg)
2.0 lb (0.9 kg)
Your feedback is important to us. If you have
comments about this document, please send them
to
sbt_technical.editor.us.sbt@siemens.com
129-287
Operating Instructions
Rev. 1, October, 1999
Document No. 129-287
Printed in the U.S.A.