SK, SD and SWIFT™Wireless SLC Device Installation

7.6 Addressing SK Devices

All SK devices are addressed using the two rotary dials that appear on the device board. Use the ONES rotary dial to set the ones place in
a one or two digit number, and use the TENS rotary dial to set the tens place in a two or three digit number.
The control panel recognizes when an SK detector or SK module is installed. For this reason, SK detectors can be assigned any unique
address from 1 to 99, and SK modules can be assigned any unique address from 1 to 99. There can be an SK detector using address 1 and
an SK module using address 1. 0 is an invalid address.
Example 1: To select device address 35, turn the ONES rotary dial to 5 and the TENS rotary dial to 3 as shown in Figure 7.4.

7.7 Wiring SK Detectors

This section describes how to install SK heat and smoke detectors. See Table 7.1 for a list of detectors. Refer to the detectors' installation
instructions for more detailed information.
Wiring SK detectors:
1.
Wire device bases as shown in Figure 7.5.
2.
Set the address for each device as described in Section 7.8.

7.8 Wiring SD SLC Detectors

The information in this section applies to SD models. See Table 7.2 for list of detectors.
Wiring SD Detectors
1.
Wire device bases as shown in Figure 7.6.
78
All dials labeled for ONES
or TENS position.
Figure 7.4 SK SLC Device Addressing Using Rotary Dials
Figure 7.5 Heat and Smoke Detector Connection to the Panel.
6808 Manual — P/N LS10146-001SK-E:C 09/28/2017