Mitsubishi Electric Melsec iQ-R Series User Manual page 35

Laser displacement sensor control module for programmable controller
Hide thumbs Also See for Melsec iQ-R Series:
Table of Contents

Advertisement

Processing method of the cable terminal
Strip the cable sheath from the tip for the strip length.
Attach the bar solderless terminal to the stripped area.
(1)
(1) Strip length
A recommended strip length is 13mm.
Wiring to terminal block
■Connecting a cable
Fully insert a wire having a bar solderless terminal into a wire insertion opening, and push the wire in. After inserting the wire,
pull it lightly to check that it is securely clamped.
6
Incomplete connections may cause short circuit, fire, or malfunction.
■Disconnecting a cable
Push in the open/close button of the wire to be disconnected using a flathead screwdriver. Pull out the wire with the open/
close button pushed in.
6 INSTALLATION AND WIRING
33
6.2 Wiring Method

Advertisement