•
Press 3 from the configure
menu to select "Auto "Learn".
The display will respond with
the message :
•
To proceed with "Auto Learn", press the YES key. The system will confirm your command with the message
"Program Running" on the display. It may take up to half a minute to learn a complete loop. Each possible
sensor address is checked to see if any detector is installed at that address. If a detector has been installed,
the panel determines the type of the detector. If more than one detector is located at a single address, or the
detector type code is invalid, a warning message will appear on the display.
•
Do not press any key until the display changes from the "program running" message.
•
Once the system has finished
learning, it will respond with a
display giving a summary of
the detectors found on the
loop. For example.
•
This display should be checked, against the installation sheets, to ensure that the system has found the
correct number of devices.
•
Pressing any key then restores the display to the normal commissioning menu.
•
The Auto Learn sequence can be used as many times as required and does not affect the text description
used to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the "Devices" option to obtain
detailed information on the device type and to see the address of each device found on the loop.
5.6.2
Zones
•
The Zone function is identical to the routines described in Signaling Loops Section.
5.6.3
Devices
•
The "Devices" option presents detailed information for the various types of peripheral device fitted on the
bus.
Item
Description
1
Address
2
Zone
3
Location Text
4
Device Type
5
Analog Signal
Table 11: Device Information
The device signal from the card is fixed at 16. It will drop to 0 if communications or power to the
card is lost.
© 2002 Radionics
Figure 10: Location of Device Information
D8024/D10024A Operation and Installation Guide
Page 27
D8024/D10024A
Programming
50616B