Interlocks; Control Power/Potential Transformers - Toshiba JK 400 Series Instruction Manual

Ampere medium voltage controllers fixed type 7.2kv maximum
Hide thumbs Also See for JK 400 Series:
Table of Contents

Advertisement

Basic Installation and Operation Guide
JK 400 Series Fixed Controllers

Interlocks

Circumvent the handle interlock by pushing a screwdriver through the slot and operate the handle several times.
Hazardous Voltage. Turn off and lock out Primary and Control power.
Check that the CPI electrical interlock (microswitch) operates each time the handle is moved. The CPI (control
power interlock) should close approximately 10° before the handle reaches the full ON position. As the handle
is moved from ON to OFF, the CPI switch should open by the time the handle has moved approximately 10° or
one inch (Fig. 49).
Refer to the GENERAL DESCRIPTION section for the location of the handle mechanical interlocks and the CPI
electrical interlock.
Fig. 49 Interlock Sequence Check

Control Power/Potential Transformers

Wipe off the surface of the transformers (Fig. 50).
Check the condition of the primary fuses and fuse clips. Check all screws
for tightness.
Fig. 50 Inspect Transformer(s)
33
TOSHIBA