Introduction 1.Introduction 1.1 Model name explanation Apply toT1; 220~240V50HZ/1ph DC inverter Heat pump & R32 refrigerant Version number Europe Platform of outdoor units: 40 platform Nominal cooling capacity (9000BTU/h) Type of outdoor unit : U (normal type) The maximum combination number Apply toT1;...
Page 4
Introduction 1.2 Safety Cautions Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “Caution” items can also lead to serious accidents under some conditions if they are not followed.
Page 5
Introduction Warning Do not repair the electrical components with wet hands . Working on the equipment with wet hands can cause an electrical shock Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Page 6
Introduction Warning Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire. Be sure to use the specified cable to connect between the indoor and outdoor units.
Page 7
Introduction Caution Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks. Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and remains around the unit, it can cause a fire.
Page 8
Introduction Caution Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock. If the installation platform or frame has corroded, replace it.
Specification Heat Type ML fin- 7HI-HX tube exchanger Row*stage*fitch 2*26*1.4 TECHNICAL SPECIFICATIONS-OTHERS Refrigerant type Refrigerant charge 0.95 Refrigerant Maximum allowable distance circuit between indoor an outdoor Maximum allowable level difference Refrigerant control liquid 6.35 Piping connections 9.52 (external diameter) drain Heat insulation type Both liquid and Gas pipes Max.
Wiring diagrams 6.Printed Circuit Board Connector Wiring Diagram Connectors PCB (1) (Outdoor Control PCB) Connector for power N and L Connector for ground CN23 Connector for DC POWER 15Vand 5V to the module board Connector for CN2,CN1 on the module board CN10 CN22 Connector for fan moto...
Page 14
Wiring diagrams PCB (2) (Module PCB for 09-12K ) CN10 Connector for the DC power 5V and 15V form the control PCB CN11 Connector for communicate between the control board and the module board P (CN1) Connector for capacitance board N (CN5) LI (CN7), Connector for reactor...
Functions and control 7.Outdoor Functions and Control 7.1 Main functions and control specification 7.1.1 The operation frequency of outdoor unit and its control 7.1.1.1 The operation frequency control of compressor The operation frequency scope of compressor Mode Minimun operation frequency Maximun operation frequency Heating 25Hz...
Page 20
Functions and control affected by the environment, and they have nothing to do with the ability of the indoor unit. Refrigeration/dehumidification mode: Serial No. Temperature scope Frequency limitation Wh_c<16 Max_hz1 23HZ Wh_c<22 Max_hz1 27HZ Wh_c<28 Max_hz1 35HZ Wh_c<32 Max_hz2 51HZ Wh_c<40 Max_hz3 69HZ...
Page 21
Functions and control When heating, it is needed to satisfy F-MIN-r (compressor’s Min_hz)< F<F-MAX-r (compressor’s Max_hz) 7.1.2 The outdoor fan control (Exchange fan) When the fan is changed among every airflow speed (including stop blowing), in order to avoid the airflow speed from skipping frequently, it must be kept under each mode for over 30 seconds, and then it can be changed to another mode (when refrigerating, the time is changed to 15 seconds).
Page 22
Functions and control value of the middle 2 values), take the mean value. Abnormal stop Decreasing the frequency rapidly 1HZ/second Decreasing the frequency slowly (1HZ/10seconds) The frequency doesn’t change. Increasing the frequency (1HZ/10second) Increasing the frequency 1HZ/1second TTC>=115 lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the indoor, others don’t last.
Page 23
Functions and control Increasing slowly Keeping the frequency Decreasing slowly Decreasing rapidly Stop The compressor stops for more than 3 minutes, Tpg_indoor> 9 , the compressor recovers. 7.2 Value of Thermistor Ambient Sensor, Defrosting Sensor, Pipe sensor R25 =10K 3% B25 /50 =3700K 3% Temp.( ) Max.(K ) Normal(K )
Service diagnosis 10.Service Diagnosis 10.1 Caution for Diagnosi The operation lamp flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.
Page 33
Service diagnosis 10.3 Problem Symptoms and Measures Symptom Check Item Details of Measure Check the power supply. Check to make sure that the rated voltage is supplied. None of the units operates Check the indoor PCB Check to make sure that the indoor PCB is broken Operation A power failure of 2 to 10 cycles can stop air conditioner Check the power supply.
Page 34
Service diagnosis 10.4 Error Codes and Description indoor display Code indication Indoor Reference Outdoor fault description displaying Page (LED1 flash panel code times) indication Indoor and Communication fault between indoor and Page .41 Outdoor outdoor units Room temperature sensor failure Page .33 Indoor Malfunction Heat-exchange sensor failure...
Page 35
Service diagnosis 10.4.1 Thermistor or Related Abnormality Indoor Display E1: Room temperature sensor failure E2: Heat-exchange sensor failure outdoor display F21 LED1 flash 10 times Defrost temperature sensor failure F7 LED1 flash 11 times Suction temperature sensor failure F6 LED1 flash 12 times Ambient temperature sensor failure F25 LED1 flash 13 times Discharge temperature sensor failure Method of The temperatures detected by the thermistors are used to determine thermistor errors...
Page 36
Service diagnosis 10.4.2 EEPROM abnormal Indoor Display E4: indoor EEPROM error Indoor display F12: Outdoor EEPROM error; Outdoor LED1 flash 1 times Method of The Data detected by the MCU are used to determine MCU Method of Malfunction Malfunction Detection Malfunction Malfunction when the data of EEPROM is error or the EEPROM is damaged...
Page 37
Service diagnosis Check whether Terminal on the outdoor mainboard is well inserted. Fasten the connection Is it normal? Power on the unit and turn into Cool mode. check whether the motor can running 1.Measure whether the voltage between 1 and 3 of the motor socket on the PCB is DC310V approx.
Page 38
Service diagnosis IPM protection dues to the compressor faulty Supposed IPM protection dues to faulty PCB of IPM module Causes Compressor wiring disconnected * Caution Be sure to turn off power switch before connect or disconnect connector, Troubleshooti else parts damage may be occurred. Turn on the unit.
Page 39
Service diagnosis Supposed Faulty IPM Module Faulty compressor Causes Faulty power supply * Caution Be sure to turn off power switch before connect or disconnect connector, or parts Troubleshooti damage may be occurred. Electrify the machine again and turn it on with the remote controller, If malfunctions IPM Module is damaged and are reported before or upon the compressor...
Page 40
Service diagnosis The outdoor PCB is broken Supposed The IPM module is broken Causes Communication wiring disconnected * Caution Be sure to turn off power switch before connect or disconnect connector, or else Troubleshooti parts damage may be occurred. 1) Check whether plug of MODULE COM and MODULE POWER on the outdoor PCB and IPM module is tight connected 2) Check whether the connection of P &...
Page 41
Service diagnosis Malfunction An voltage signal is fed from the voltage detection circuit to the microcomputer Detection Conditions Supposed Supply voltage not as specified. Causes The IPM module is broken. Troubleshooti * Caution Be sure to turn off power switch before connect or disconnect connector, or else parts damage may be occurred.
Page 42
Service diagnosis The Discharge temperature control is checked with the temperature being detected Method of by the Discharge pipe thermistor Malfunction Detection when the compressor discharge temperature is above 110 Malfunction Detection Conditions Electronic expansion valve defective Faulty thermistor Supposed Faulty PCB Causes Troubleshooti...
Page 43
Service diagnosis 10.4.10 The communication fault between indoor and outdoor Indoor display E7:Outdoor display LED1 flash 15 times Method of Communication is detected by checking the indoor PCB and the outdoor PCB Malfunction Detection Malfunction The outdoor PCB broken leads to communication fault Detection The indoor PCB broken leads to communication fault Conditions...
Page 44
Service diagnosis 10.4.11 Loss of synchronism detection Inverter side current detection is abnormal Outdoor Display F11:LED1 flash 18 times F28:LED1 flash 19 times Method of The position of the compressor rotor can not detected normally Malfunction Detection when the wiring of compressor is wrong or the connection is poor; Malfunction or the compressor is damaged Detection...
Page 45
Service diagnosis 10.3.12 High work-intense protection Outdoor display LED1 flash 21 times Method of High work-intense control is activated in the heating mode if the temperature being sensed by the heat exchanger thermistor exceeds the limit. Malfunction Detection Malfunction Activated when the temperature being sensed by the heat exchanger Detection rises above 63 twice in 30 minutes.
Page 66
Circuit diagrams Sincere Forever Haier Group Edited by : Shi haiyan Haier Industrial Park, No.1, Haier Road Zhang chenglong 266101, Qingdao, China_ Signed by : wang caiping Http //www.haier.com Approved by: Yang wenjun Domestic air conditioner...
Page 67
Wall Mounted Type DC Inverter FREE MATCH NEW40-Series SERIES:NEW40...
Page 68
Remove of front panel Outdoor unit Step Procedure Points 1.Features Loosen the service Be careful not to cover screw and cut your finger by remove the service the fins of the cover. heat exchanger Domestic air conditioner...
Page 69
Step Procedure Step Procedure Points Step Procedure Points Points 2. Remove the panels. Loosen the 7 screws and lift the top panel Loosen the screws of the panel. Pull and remove the front panel. Domestic air conditioner...
Page 70
Step Procedure Points Remove the fixting screws, then lift the electrical box Domestic air conditioner...
Page 71
Remove the air filters and horizontal flap Step Procedure Points Loosen the fixting screws and remove back protect net . Loosen the fixting screws and remove the side panel. Domestic air conditioner...
Page 72
Remove the casing Step Procedure Points Loosen the fixting screws and remove the side panel. Loosen the fixting screws and remove the cross beam. Domestic air conditioner...
Page 73
Step Procedure Points Loosen the fixting screws remove the fan Loosen the fixting screws and lift the fan motor. Domestic air conditioner...
Page 74
Release stepping motor (2type) Step Procedure Points Remove fixing screws,then lift the fan motor bracket Cut down and pull out compressor and remove Domestic air conditioner...
Page 75
Removal of Heat Exchanger Step Procedure Points Loosen the marked fixing screws Loosen the fixting hook remove heat exchanger Domestic air conditioner...