SINGLE Technical Data Book SINGLE MSP Duct for Europe (R410A, HP) Model : AC∗∗∗MNMSEH/EU(Indoor Unit) , AC∗∗∗MXASEH/EU(Outdoor Unit)
Page 2
History Version Modification Date Remark Ver.1.0 Release Single TDB for Europe 17.01.03 Ver.1.1 Modify the SCOP data from 3.85 W/W to 3.8 W/W 17.08.04...
Page 8
Sound values of multi combination are theoretical values based on sound results of individual installed units. 3) These products contain R410A(GWP=2,088) which is fluorinated greenhouse gas. • In case you want to know more information regarding capacity and correction, please refer to capacity table TDB on pvi.samsung.com site.
4. Summary Table Indoor Units Performance Characteristics Capacity Airflow Sound Pressure Level Sound Power Level Model Code Weight Fan Speed Cooling Heating (CMM) (dBA) (dBA) (kg) (kW) (kW) Max. High 15.0 AC052MNMSEH 30.0 Std. Mid. 14.2 Min. 0.95 0.66 13.5 Max.
Page 10
4. Summary Table Outdoor Units Performance Characteristics Capacity Sound Pressure Level(dBA) Net Size Net Weight Airflow Sound Power Level Model Code (WxHxD , mm) (kg) (CMM) (dBA) Cooling Heating AC052MXASEH 790 x 548 x 285 37.5 AC071MXASEH 880 x 798 x 310 53.0 AC100MXASEH 880 x 967 x 320...
7. Center of Gravity 7. Center of Gravity Indoor Units Units : mm [inches] Model AC052MNMSEH 1150 AC071MNMSEH AC100MNMSEH 1150 AC120MNMSEH 1200...
Page 21
7. Center of Gravity Outdoor Units AC052MXASEH Units : mm [inches] [ 9-1/16 ] [ 6-5/16 ] Hold location of fondation bolt Hold location of fondation bolt [ 24-1/16 ] [ 12-3/8 ] AC071MXASEH Units : mm [inches] [ 9-7/8 ] [ 5-15/16 ] [ 13-3/8 ] [ 26 ]...
Page 22
7. Center of Gravity Outdoor Units AC100MXASEH Units : mm [inches] [ 8-5/8 ] Hold location of foundation bolt Hold location of [ 6-7/8 ] foundation bolt [ 25-3/8 ] [ 13-3/8 ] AC120MXASEH Units : mm [inches] [ 6-5/16 ] [ 8-1/8 ] Hold location of fondation bolt [ 24-3/8 ]...
9. Sound Data Indoor units Sound Pressure level Unit: dB(A) MODEL Discharge Suction Duct Duct AC052MNMSEH AC071MNMSEH AC100MNMSEH AC120MNMSEH Microphone • NR Curve 1) AC052MNMSEH 2) AC071MNMSEH NR 65 NR 65 NR 60 NR 60 NR 55 NR 55 High NR 50 NR 50 High...
Page 29
9. Sound Data Indoor units Sound Power level Unit: dB(A) NOTE MODEL Power • Specifications may be subject to change without prior notice. AC052MNMSEH - Sound power level is an absolute value that a sound source generates. AC071MNMSEH - dBA = A-weighted sound power level. - Reference power : 1pW.
Page 30
9. Sound Data Outdoor Units Sound Pressure level Unit: dB(A) MODEL Cooling Heating AC052MXASEH Microphone AC071MXASEH AC100MXASEH AC120MXASEH Front • NR Curve 1) AC052MXASEH 2) AC071MXASEH NR 90 NR 90 NR 85 NR 85 NR 80 NR 80 NR 75 NR 75 NR 70 NR 70...
Page 31
9. Sound Data Outdoor Units Sound Power level Unit: dB(A) NOTE MODEL Power • Specifications may be subject to change without prior notice. AC052MXASEH - Sound power level is an absolute value that a sound source generates. AC071MXASEH - dBA = A-weighted sound power level. - Reference power : 1pW.
12. Operation Range Outdoor Unit Indoor Unit Indoor Unit Mode Temperature(DB) Temperature(DB) Humidity(RH) Cooling -15°C ~ 50°C 18°C ~ 32°C 80% or less Heating -20°C ~ 24°C 30°C or less Drying -15°C ~ 50°C 18°C ~ 32°C 80% or less NOTE •...
14. Installation Indoor Unit Step 1 Checking and preparing accessories Thermal insulation Insulation drain (1) sponge A (1) The following accessories are supplied with the indoor unit. The type and quantity may differ, depending on the specifications. User manual (1) Installation manual (1) Thermal insulation Cable-tie (8)
Page 42
14. Installation Indoor Unit Step 4 Installing the indoor unit • You must have 20 mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from When deciding on the location of the air conditioner with the the vibration of indoor unit may bother the user.
Page 43
14. Installation Indoor Unit CAUTION CAUTION • Ensure that the ceiling is strong enough to support the • For proper drainage of condensate, give a 3mm slant to weight of the indoor unit. Before hanging the unit, test the the left or right side of the unit which will be connected strength of each attached suspension bolt.
Page 44
14. Installation Indoor Unit Step 5 Purging inert gas from the indoor unit Step 6 Cutting and flaring the pipes From factory the unit is supplied and set with a pre-charge 1 Make sure that you have the required tools available. (pipe of nitrogen gas.
Page 45
14. Installation Indoor Unit 5 Check that the flaring is correct, referring to the Outer diameter (D) Torque (N•m) illustrations below for examples of incorrect flaring. Ø6.35 mm 14 ~ 18 Ø9.52 mm 34 ~ 42 Ø12.70 mm 49 ~ 61 Ø15.88 mm 68 ~ 82 Ø19.05 mm...
Page 46
14. Installation Indoor Unit Step 8 Performing the gas leak test 2 Wind insulating tape around the pipes and drain hose avoiding compressing the insulation too much. To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant pipe using a leak detector for R-410A.
Page 47
14. Installation Indoor Unit Step 10 Installing the drain hose and drain pipe 5 Select the insulation of the refrigerant pipe. • Insulate the gas side and liquid side pipe, noting the 1 Push the supplied drain hose as far as possible over the insulation thickness that must differ according to the drain socket.
Page 48
14. Installation Indoor Unit Step 11 Performing the drainage test Without the drain pump Prepare a little water about 2 liter. 1 Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m. 1 Pour water into the base pan in the indoor unit as shown in figure.
Page 49
14. Installation Indoor Unit Step 13 Optional: Installing external controller Accessories (SPI module : MSD-EAN1) Refer to the SPI module(MSD-EAN1) installation manual for Accessories (External controller : MIM-B14) the more information. External Controller PCB Case Haness Wire Haness Wire Screw Step 14 Connecting the power and communication cables CAUTION...
Page 50
14. Installation Indoor Unit • Since it has the external power supply, refer to the outdoor unit installation manual for MAIN POWER. Indoor Unit 1(L) 2(N) CAUTION 1(L) 2(N) • When installing the indoor unit in a computer room or a server room, use the double shielded communication cable (tape aluminum / polyester braid + copper) of FROHH2R type.
Page 51
14. Installation Indoor Unit 1 Press the User Set button. Model AC120MNMSEH/EU (Main Menu) will be displayed, and you can press the Static Pressure Option Code for Indoor Unit [ ]/[ ] buttons to select No. 8, which will set the Easy Tuning.
Page 52
14. Installation Indoor Unit Step 16 Setting the indoor unit option code 1 Press the buttons at the same time for more than 3 seconds and then a Main menu will be displayed. In order to set the indoor unit option code use the wired remote controller and follow the directions below.
Page 53
14. Installation Indoor Unit Step 17 Setting indoor unit addresses and NOTE installation options • Press the button anytime during setup to exit without setting. Set the indoor unit address and installation option with • Address will not be applied if you don't press button.
Page 54
14. Installation Indoor Unit Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX Option SEG1 SEG2 SEG3 SEG4 Use of external Explanation PAGE MODE temperature sensor Indication Details Indication Details Indication Details RESERVED Indication Disuse and Details Option SEG5 SEG6 SEG7 SEG8 Explanation Use of central control PAGE Use of drain pump Indication...
Page 55
14. Installation Indoor Unit Option SEG17 SEG18 SEG19 SEG20 control of a remote Explanation Buzzer control Number of hours using filter PAGE controller Indication Details Indication Details Indication Details Indication Details Use of 1000 Hour 0 or 1 Indoor 1 buzzer Indication and Details...
Page 56
Outdoor Unit CAUTION 200 mm Air Guide Duct (This product is not provided by Samsung) • Depending on the condition of power supply, unstable power or voltage may cause malfunction of the parts or control system. (At the ship or places using power supply •...
Page 57
14. Installation Outdoor Unit Outdoor unit dimensions A Type AC052MXASEH 2000 300 or 600 or or more more more or more B Type AC071MXASEH When installing more than 1 outdoor unit (Unit: mm) 1500 3000 3000 or more or more or more or more or more...
Page 58
14. Installation Outdoor Unit Step 2 Fixing the outdoor unit in place CAUTION Install the outdoor unit on a rigid and stable base to prevent • The outdoor unit must be installed according to the disturbance from any noise caused by vibration. When specified distances in order to permit accessibility from installing the unit at a height or in a location exposed to each side, to guarantee correct operation, maintenance,...
Page 59
14. Installation Outdoor Unit CAUTION AC120MXASEH (Unit : mm) Anchor bolt hole • When installing an air guide duct, be sure to check the following: ‐ The screws do not damage the copper pipe. ‐ The air guide duct is fixed firmly on the guard fan. Step 3 Connecting the power cables, communication cable, and controllers You must connect the following three electrical cables to the...
Page 60
14. Installation 14. Installation Outdoor Unit Air conditioning system examples CAUTION When using earth leakage circuit breaker (ELCB) for a single • If the outdoor unit is installed in a location vulnerable to phase an electric leak or submergence, make sure to install an ELCB.
Page 61
14. Installation 14. Installation Outdoor Unit • Devices disconnected from the power supply should be CAUTION completely disconnected in the condition of overvoltage category. • You should connect the power cable into the power cable terminal and fasten it with a clamp. •...
Page 62
14. Installation Outdoor Unit Connecting the outdoor-to-indoor power cable and the NOTE communication cable • Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely. • Ground wire for the indoor unit and outdoor unit For connecting the power and connection cable must be clamped to a soft copper tin- communication cables...
Page 63
14. Installation Outdoor Unit Step 4 Optional: Extending the power cable Tightening torque (kgf • cm) 1 Prepare the following tools. 12.0 to 18.0 20.0 to 30.0 Tools Spec Shape • 1N · m = 10 kgf · cm Crimping pliers MH-14 CAUTION Connection sleeve...
Page 64
14. Installation Outdoor Unit 4 Using a crimping tool, compress the two points and flip CAUTION it over and compress another two points in the same location. • Make sure that the connection parts are not exposed to outside. • The compression dimension should be 8.0. •...
Page 65
14. Installation Outdoor Unit Step 5 Connecting the refrigerant pipe Maximum allowable length Items Single installation AC071MXASEH Applicable outdoor unit models AC052MXASEH AC100MXASEH AC120MXASEH Total pipe length (L Main pipe (L Max. distance among indoor units (D) Max. length after branch Max.
Page 66
14. Installation Outdoor Unit Step 6 Optional: Cutting and flaring the pipes 5 Check that the flaring is correct, referring to the illustrations below for examples of incorrect flaring. 1 Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool, and pipe holder) 2 If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90°...
Page 67
14. Installation Outdoor Unit 2 Referring to the illustration below, tighten the flare nut on 5 Purge the air from the system using vacuum pump for section D first manually and then with a torque wrench, about 10 minutes. applying the following torque. •...
Page 68
14. Installation Outdoor Unit Indoor Unit Indoor Unit Outdoor Unit Balance Vacuum Pump Unit tCO2e Gas side stop valve (service port)) Liquid side stop valve (service port) Refrigerant type GWP value Important information regulation regarding the R-410A 2088 refrigerant used •...
Page 69
14. Installation Outdoor Unit Calculating the quantity of refrigerant to add The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist. When installing the outdoor unit only Interconnection pipe length (m) Model...
Page 70
14. Installation Outdoor Unit 2 Select the insulation of the refrigerant pipe. AC120MXASEH • Insulate the gas side and liquid side pipe referring to Drain cap (3EA) the thickness according to the pipe size. Drain plug (1EA) • Less than Indoor temperature of 30°C and humidity of 85% is the standard condition.
Page 71
14. Installation Outdoor Unit 1 Select an earthing electrode that complies with the 2 Check the indoor unit. specifications given in the illustration. a Check that you have connected the power and 2 Connect the flexible hose to the flexible hose port. communication cables correctly.
Page 72
14. Installation Outdoor Unit 6 View mode: When the K4 switch is pressed, you can see information about our system state as below. K4 short Display contents SEG1 SEG2 SEG3 SEG4 Unit push Order frequency Hundreds digit Tens digit Units digit Current frequency Hundreds digit Tens digit...
Page 73
14. Installation Outdoor Unit 7 DIP switch option b Set the address in SEG3 and SEG4 by pressing the K2 switch shortly. Option SEG1 SEG2 SEG3 SEG4 Function Channel The address is set address automatically. The address is set 00 to 15 manually.
Page 74
14. Installation Outdoor Unit Relocating the indoor and outdoor units 3 Tighten the cap securely. Tightening torque 1 Pump down refrigerant. See Pumping down refrigerant Outer Diameter (mm) on page 73. Charging port cap Body cap (N•m) (N•m) 2 Remove the power cord. 20 to 25 Ø6.35 3 Disconnect the assembly cable from the indoor and...
Page 76
Compatible interface module MIM-N01 Others External contact MIM-B14 interface module S-Converter MIM-C02N Wireless signal receiver MRK-A10N Duct type only • In case you want more information about the accessories, please refer to the control and accessories TDB on pvi.samsung.com site.
Page 77
Ver.1.1 Samsung Electronics Co., LTD. B2B PM / SE Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677 Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com Images and data in this book may subject to change without prior notice.