1.3.2 Copyright This document may be duplicated and distributed only with the express permission of Siemens, and may be passed on only to authorized persons or companies with the required technical knowledge. 1.3.3 Quality assurance These documents were prepared with great care.
POC is available. Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
The mounting and installation guide provides all the information needed by the Purpose aforementioned personnel for: The proper mounting and wiring of Desigo TRA in the installation box and connections to the plant. An overview of the room automation station product range and its design is provided for general understanding.
Building services Connected plants and systems, including: Heating, equipment ventilation and air conditioning plants, electrical systems, etc., as well as electrical areas (switches, buttons, lighting groups, blinds). 8 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Introdution 2013-02-23...
Page 9
For details see SSA (Setup & Service Assistant) Commissio- ning, CA111050. • Wireless connections: A KNX gateway integrates wireless EnOcean devices (room units, sensors, buttons). 9 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Introdution 2013-02-23...
• Third-party regulations, e.g. by the general contractor or building owner. System-specific regulations Safety The electrical safety for building automation and control systems by Siemens Building Technologies is essentially based on safely separating low voltage from mains voltage. Application as per SELV or PELV pursuant to HD 384 "Electrical installation of SELV, PELV buildings"...
Page 11
This overvoltage must be diverted to the earth to limit the damage. This may be achieved with the help of gas-filled surge arrestors, varistors and diodes as well as capacitors and chokes. Specialized companies (e.g. Siemens, Phoenix) combines these elements into protective components to provide optimum protection for various systems. Mains filter Spikes and high-frequency interference may occur in areas with high levels of interference.
The supply terminals of the PXC3... (terminals 7 and 8) bare a max current of supply AC 24 V 10 A, otherwise the pins get too warm. An external T10 A fuse is compulsory 12 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Important information on safety...
25 27 ± min. 25 min. 3 The room automation station may also be attached to a wall if used without TX-I/O Wall mounting modules. 14 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Installation box TRA 2013-02-23...
Construction, stability and sealing meet applicable execution regulations at the plant's location. Ambient • Desigo TRA is designed for an ambient temperature conditions of -5 - 50°C. PXC3...: 45°C for certain mounting positions, see below. Please make sure that the installation box is sufficiently ventilated to ensure compliance with the ambient temperature for all devices.
This results in the following distance of the standard rails/cable ducts: 90 mm (module width) + (b = cable duct width) + 2 x ≥30 mm (available space for wiring). 16 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
• Screen connection terminals must be used and suitable installation space be provided to this end (see drawing on Page 19). Using screens to power the TX-I/O modules: See TX-I/O engineering and Exception installation, CM110562. 17 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Installation box TRA 2013-02-23...
• The cable screens must be properly connected to the ground to achieve a solid level of screening (see below). • Island bus extension, see: TX-I/O engineering and installation, CM110562) 18 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
Page 19
The screen rail cannot be used to relieve cable strain. Screen connection with screen connection terminals Screen connection terminals Screen rail support rail Avoid screen braid. 19 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Installation box TRA 2013-02-23...
• A external fuse of max. 10 A is planned to protect circuits on the PCB of the PL- Link I/O Block. TXM1.6RL can switch lighting groups up to 10 A. Fusing max. 16 A. See data sheet N8177. 21 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Wiring of field devices (without bus)
Tightening torque Set the torque to 0.5-0.6 Nm or 50-60 Ncm when using electrical screwdriver on the connection terminals. 22 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Wiring for AC 24 V and island bus...
10 A fuse holder in the PXC3 10 A fuse holder in power module. 10 A fuse holder in the bus interface module. 23 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Wiring for AC 24 V and island bus...
(terminals 7 and 8, for additional AV 24 V (only if the sum of 10 A at consumers) terminals 5 and 6 is not exceeded) 24 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Wiring for AC 24 V and island bus 2013-02-23...
Page 25
50 VA 25 VA 10 VA AWG16 2.50 mm 320 VA 160 VA 80 VA 40 VA 16 VA AWG14 Notes 25 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies Wiring for AC 24 V and island bus 2013-02-23...
Page 26
26 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
• The island bus extension modules (U4, U5) may be anyplace in their TX-I/O row. For signal quality reasons, however, the best place is directly after the power supplying device 27 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
The next devices, if in line topology, are disconnected from the network. For secure operation of the system it is recommended to supply each room automation station separately with AC 24 V. 28 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
The internal bus power supply must be switched off in ABT when an external bus power supply is used. Default = "Auto Detection". 30 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies PL-Link room bus...
PSU is allowed to be operated in parallel with other PSUs. Refer to the technical specifications. The recommended new Siemens power supply units (see below) are admitted for parallel operation. • A minimum cable distance is required between two PSU, see section 9.3.
N1 .. N7 Bus devices Device with screw terminals T branch with bus terminals Device with spring cage Branching and terminals connection variants PL+ PL- N1 .. N8 Bus devices 32 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies PL-Link room bus 2013-02-23...
Max. 350 m. • Distance between two PSU operated in parallel Min. 200 m. Min. 0 m for the new Siemens power supply modules recommended in section Fehler! Verweisquelle konnte nicht gefunden werden.. • Distance between bus devices Max. 700 m.
After switching on operating voltage, you must check whether bus power from the Bus power supply PXC3 or the PSU is available. 34 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies PL-Link room bus...
In this case the internal bus power supply must be disabled via ABT, as parallel operation of the internal supply with external supplies is not admissible. 64 devices in a PL-Link network. Max. number of devices 35 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies PL-Link room bus...
However, ring topologies are not allowed. topologies Tree topology (with stub lines) Line topology (with loops) DALI DALI N1 .. N7 Operational devices 36 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies DALI network 2013-02-23...
Applying a voltage between DA+ / DA+ or between DA– / DA– will destroy the DALI PCB! This is particularly the case when the AC 24 V supply plug is connected to the DALI socket. 37 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies DALI network...
PXC3… devices do not have a connection for bus cable screens. Bus power supply Bus power through the PXC3… room automation DC 16 V, 128 mA. station (for max. 64 DALI devices) 38 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies DALI network 2013-02-23...
• Repeater available for extensions. • Uni and bidirectional communications. Low energy demand. • High data transmission rate of 125 kbps. • Low "data overhead". • ASK modulation. 39 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
Page 40
N1662 (Gateway EnOcean/KNX). Current room device data are sent only every ca. 15 minutes to consume as little energy as possible. However, this signal, a so-called presence signal, is always 40 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
1) Sending a radio signal ca. every 15 minutes (average). 2) Typical value depending on prior charging of energy cell. As brightness is hard to evaluate, we recommend control measurements using a device to measure illuminance. 41 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks...
Whether illuminance on the wall is actually 200 lx, depends in large measure on local conditions. We recommend conducting reference measurements using a luxmeter. A device with battery backup can be used is illuminance is insufficient (see Section 11.3). 43 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks...
Check sensitive medical devices using this frequency range in a case-by-case STOP Caution! basis. For detailed information, see the description of the radio signal modules available Used together with third- party receivers for download at: http://www.enocean-alliance.org/de/home. 44 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
Ca. 10 m Max. 1 wall walls Geringe Dämpfung Fire protection walls, The radio signal is isolated Hohe Dämpfung Empfänger elevator shafts, Empfänger stairwells, supply areas 45 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
• Vertical through 1-2 room corners depending on fixtures and antenna execution. • Learning by EnOcean devices can greatly increase availability. A receiver can work with multiple, received signals. 46 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks...
Fire protection walls, elevator shafts, stairwells and supply areas should be considered shielding. You can eliminate shielding by repositioning the transmitter and/or receiver Solution antenna from the silent zone or using a repeater. 47 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
(see image below). A patch antenna cannot normally be mounted directly in cement or in direct proximity to metal. One exception is the "metal patch antenna MCA 1890MP“ by the Hirschmann company. The flat antenna can be attached discretely 48 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
(computer, audio and video systems) must be at least 50 cm. The distance of the EnOcean receiver to other high frequency transmitters should be at least 50 cm. The transmitter position is non-critical. 49 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks...
Faulty connection from previously installed devices can also be reviewed. The RF telegrams and disruptive RF signals are displayed in the relevant frequency range. Additional information available at: http://www.enocean-alliance.org/de/home. 50 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks...
STEP 1: Floor plan and compass • Fire protection walls STEO 2: Draw relevant • Elevator shafts, stairwells and other supply areas RF shielding on the floor plan 51 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
Page 52
Even if carefully planned, the field strength measuring device should be used on site to test ranges. Unfavorable conditions can be improved through more suitable re-positioning of the devices or through the use of a repeater. 52 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies...
EPM 100, but not wireless phone, etc., at least 50 cm from the VALID LED. EnOcean receiver). b) Jammer (continuous transmission). Eliminate jammer. 53 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
Page 54
Invalid EnOcean telegrams are Jammer exists. occasionally received. Eliminate jammer. One of the two LO/HI LEDs is occasionally lit on EPM 100, but not the VALID LED. 54 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...
PL-Link or KNX network. Type Stock number Name EnOcean gateways RXZ97.1/KNX S55842-Z101 Gateway EnOcean/KNX See description of the gateway datasheet [12]. Engineering KNX page ORKS 55 / 56 Siemens Mounting and installation CM111043en_03 Building Technologies EnOcean RF networks 2013-02-23...