Toshiba 4200FA Installation Planning Manual

Toshiba power supply - ups user manual
Hide thumbs Also See for 4200FA:

Advertisement

TOSHIBA
Installation Planning Guide for 15-80kVA UPS
UPS kVA/ kW Rating
15 kVA/12 kW
25 kVA/ 20 kW
30 kVA/ 24 kW
50 kVA/ 40 kW
80 kVA / 64 kW
Maximum Input Power
Demand
kVA
PF
Amps
15
>0.97
45.7
25
>0.97
76.3
30
>0.97
92.4
50
>0.97
152.6
80
>0.98
244.3
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
kVA
Amps
15
41.6
25
69.4
30
83.3
50
138.8
80
222.1
Battery Capacity Required
for Full Load Output
kVA
kWB
15
13.33
25
22.22
30
26.67
50
44.44
80
71.11
Rated Output Power
kVA
PF
Amps
15
0.8
41.6
25
0.8
69.4
30
0.8
83.3
50
0.8
138.8
80
0.8
222.1
Rev. 1.03
Standard System: 208v Input, 208/120V Output
General Mechanical Information
Dimensions
(W x D x H)
Inches
20 x 36.25 x 59.85
20 x 36.25 x 59.85
20 x 36.25 x 59.85
35.59 x 38.19 x 59.39
44 x 31 x 74
Primary AC Input (208V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
60 AT
90 AT
125 AT
200 AT
300 AT
Suggested External
Overcurrent Protection
Amps
60 AT
90 AT
110 AT
175 AT
300 AT
Battery Input (288VDC Nominal)
Maximum Discharge
Suggested External
at Full Load Output
Overcurrent Protection
Amps DC
61.7
102.8
125 AT
123.0
175 AT
205.7
225 AT
329.2
400 AT
AC Output (208/120V 3-Phase / 4-Wire)
Suggested External
Overcurrent Protection
Amps
60 AT
90 AT
110 AT
175 AT
300 AT
Page 1 of 2
4200FA XT UPS
Weight
Lbs.
900
910
915
2,548
2,200
Suggested Minimum Feeder
Wire Size Per Phase
AWG or kcmil at 75º C Temp. Rating
(1) x 8
(1) x 4
(1) x 3
(1) x 1/0
(1) x 300
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG at 75º C Temp. Rating
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) x 4/0
(1) x 4/0 / (1) x 400
Suggested Minimum Feeder
Wire Size Per Phase
Amps
AWG or kcmil at 75º C Temp. Rating
90 AT
(1) x 6
(1) x 2
(1) x 1
(1) x 4/0
(2) x 3/0
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) x 4/0
(1) x 4/0 / (1) x 400
Approximate Full-Load Heat Loss
kBTU's / Hr
5.7
7.6
9.1
17.7
40.0
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
70
70
70
70
70
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
4200FA-IPG-208v-XT1

Advertisement

loading

Summary of Contents for Toshiba 4200FA

  • Page 1 Suggested External Rated Output Power Overcurrent Protection Amps 41.6 69.4 83.3 138.8 222.1 Rev. 1.03 4200FA XT UPS General Mechanical Information Weight Lbs. Inches 2,548 2,200 Suggested Minimum Feeder Wire Size Per Phase Amps AWG or kcmil at 75º C Temp. Rating...
  • Page 2: Important Notes

    12. Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered Professional Engineer within your local area for proper size selections. TOSHIBA Corporate Web Site: Group Web Site: Rev. 1.03 4200FA XT UPS INTERNATIONAL CORPORATION 13131 West Little York Road Houston, TX 77041 Telephone: 800.231.1412; 713.466.0277 Fax: 713.896.5212 www.tic.toshiba.com...