Installation Planning Guide for 15-80kVA UPS
UPS kVA/ kW Rating
15 kVA/12 kW
25 kVA/ 20 kW
30 kVA/ 24 kW
50 kVA/ 40 kW
80 kVA / 64 kW
Maximum Input Power
Demand
kVA
PF
Amps
15
>0.97
45.7
25
>0.97
76.3
30
>0.97
92.4
50
>0.97
152.6
80
>0.98
244.3
Optional Alternate AC Input (208/120V 3-Phase / 4-Wire)
Maximum Input Power
Demand
kVA
Amps
15
41.6
25
69.4
30
83.3
50
138.8
80
222.1
Battery Capacity Required
for Full Load Output
kVA
kWB
15
13.33
25
22.22
30
26.67
50
44.44
80
71.11
Rated Output Power
kVA
PF
Amps
15
0.8
41.6
25
0.8
69.4
30
0.8
83.3
50
0.8
138.8
80
0.8
222.1
Rev. 1.03
Standard System: 208v Input, 208/120V Output
General Mechanical Information
Dimensions
(W x D x H)
Inches
20 x 36.25 x 59.85
20 x 36.25 x 59.85
20 x 36.25 x 59.85
35.59 x 38.19 x 59.39
44 x 31 x 74
Primary AC Input (208V 3-Phase / 3-Wire)
Suggested External
Overcurrent Protection
Amps
60 AT
90 AT
125 AT
200 AT
300 AT
Suggested External
Overcurrent Protection
Amps
60 AT
90 AT
110 AT
175 AT
300 AT
Battery Input (288VDC Nominal)
Maximum Discharge
Suggested External
at Full Load Output
Overcurrent Protection
Amps DC
61.7
102.8
125 AT
123.0
175 AT
205.7
225 AT
329.2
400 AT
AC Output (208/120V 3-Phase / 4-Wire)
Suggested External
Overcurrent Protection
Amps
60 AT
90 AT
110 AT
175 AT
300 AT
Page 1 of 2
4200FA XT UPS
Weight
Lbs.
900
910
915
2,548
2,200
Suggested Minimum Feeder
Wire Size Per Phase
AWG or kcmil at 75º C Temp. Rating
(1) x 8
(1) x 4
(1) x 3
(1) x 1/0
(1) x 300
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG at 75º C Temp. Rating
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) x 4/0
(1) x 4/0 / (1) x 400
Suggested Minimum Feeder
Wire Size Per Phase
Amps
AWG or kcmil at 75º C Temp. Rating
90 AT
(1) x 6
(1) x 2
(1) x 1
(1) x 4/0
(2) x 3/0
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
AWG or kcmil at 75º C Temp. Rating
(1) x 8 / (1) x 6
(1) x 4 / (1) x 2
(1) x 3 / (1) x 1
(1) x 1/0 / (1) x 4/0
(1) x 4/0 / (1) x 400
Approximate Full-Load Heat Loss
kBTU's / Hr
5.7
7.6
9.1
17.7
40.0
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
70
70
70
70
70
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
Feet
380
380
380
380
380
4200FA-IPG-208v-XT1