Download Print this page

Advertisement

Quick Links

s
WAC 12

Installation Instructions

Fig. 1
Fig. 2a
Fig. 2b
Fig. 3
1. Product description
The WAC 12 is used to verify audio alarms. It is fitted with a
speaker and microphone. It can be controlled through the E-
Bus, with the audio signal connected to the central control unit
via an audio module (e.g. WMA 11). The WAC 12 also serves as
a master for the unaddressable WAC 11 and WAS 11.
2. Supply package
The WAC 12 UK package contains the following
- One WAC 12
- One WLC 12 UK language kit complete with:
- Installation instructions.
3. Mounting instructions
The WAC 12 is designed for mounting in dry indoor rooms.
To ensure good acoustics, note the following points.
- Mount 2 to 2.5 m above floor level.
- Maintain adequate distance from noise sources (ven ti la tion
openings, fans etc.).
- Direct towards the centre of the space to be monitored.
- Do not mount on vibrating surfaces.
- The maximum length of the audio connection between the
WAC 12 and central control unit is 200 m.
3.1 Opening the housing (Fig.1)
1 - Using screwdriver Q, press locking tab to release.
2 - Lift off cover W.
3.2 Product overview (Fig. 2)
- Knockouts Q, T for cable inlet.
- Knockouts W, E for attachment of housing.
- Knockout R back tamper contact.
- Speaker Y.
- WMC 12 circuit board U.
3.3 WMC 12 circuit board (Fig. 3)
- E-Bus connection }.
- Audio connection { to central control unit.
- Audio connection I to WAC 11 or WAS 11.
- Tamper input O for WAC 11 or WAS 11.
- LED Q, flashes when E-Bus is o.k.
- LED R, flashes to outside during monitoring (microphone
active).
- Address button W.
- Switch E for "microphone active" LED.
- Tamper switch P.
- Microphone Y.
- Potentiometer T for speaker volume.
- Potentiometer U for microphone sensitivity.

Advertisement

loading

Summary of Contents for Siemens WAC 12

  • Page 1: Installation Instructions

    Installation Instructions 1. Product description The WAC 12 is used to verify audio alarms. It is fitted with a speaker and microphone. It can be controlled through the E- Bus, with the audio signal connected to the central control unit via an audio module (e.g.
  • Page 2 4.1 E-Bus (Fig. 5a) The use of type 24 AWG 7x0,2 mm dia. cable is recommended. The E-Bus cable shall not be more than 500 m long. The WAC 12 must be connected to the central control unit via the E-Bus (B1-, B2, B3, B4+).