4.0

Specifications

4.1

BLACK GOLD TB Series Specifications

General
Model Number
Information
Rated Output Capacity
External Dimensions
Input
Rated Voltage
Voltage Variation
Rated Frequency
Power Factor
Harmonic Currents
Battery
DC Nominal (Voltage Range)
Float Charge (Regulation)
Ripple Voltage
Rated Back-up Time when fully
charged with .7pF at 77°F (25°C)
Recharge Time
Rated Charge Current
Type of Batteries
Output
Rated Voltage (Single phase)
Output Voltage Regulation
Output Frequency
Output Voltage Waveform
Rated Current (RMS)
Rated Power Factor
Maximum overload capacity
Voltage Transient Characteristic
Crest Factor
Environment
Operating Temperature
Storage Temperature
Operating Humidity
Altitude (****)
Net. Weight
Acoustical Noise
Efficiency (AC-DC-AC)
Bypass
An automatic transfer of load to bypass switch (with 4mS-transfer time) may be caused by an
overload of the inverter output, or by an internal fault condition. Also, the load can be manually
transferred to bypass by putting the rocker switch in the STOP position.
Interface
IBM ™ AS/400
LAN Manager
Fault detect and input power loss
RS232 ASCII
Options
Software for unattended computer
shutdown.
(*) Output capacity reduced when input voltage is between –15% and –30% of nominal.
(**) Battery backup time may vary depending on the operating conditions and ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs is necessary to obtain proper battery performance level before
unit is used for battery backup.
(****) At 6000-ft (2000 m) above sea level, output capacity should be de-rated by 3%.
TOSHIBA
UC1A1A020C6RKBIG
16.75W X 24D X 5.25H in.
(425W x 610D x 133H mm)
120Vac, Single Phase (*)
50/60 Hz
Greater than .98 when in inverter mode
Less than 10% THD
72Vdc (57.6 to 82.8 Vdc)
6 min. at full load (**)
18 min. at half load (**)
Maximum 24hrs. to 100% (90% recharge after 8Hrs.) (***)
120 Vac
Within than +/- 3%, steady state
50/60Hz +/- 0.5% in free
running mode (Line sync
range +/- 1Hz)
Computer-grade sinewave with less than 3.0% THD with
16.6 Amps
150% for 90 seconds
+/-5% under 100% load step change
32 to 104° F (0 to 40°C), optimal at 77°F (25°C)
-4 to 104° F (-20 to 40°C)
30% to 90% (no condensation)
Less than 3000 ft (1000 m) above sea level
119.00 lbs. (53.98 kg)
<45 dB at max. output, measured 3.3 ft (1 m) from front
Pins 5 through 9
Pins 2 and 3
Pins 1 and 4
Pins 1 through 8
Contact Toshiba for details on this option
12
UC1E1E020C5RKBIG
2000 VA (1.4 kW)
230Vac, Single Phase (*)
+10% to –30% (*)
50 Hz
82.8Vdc (± 2%)
2% R.M.S.
0.40 Amps
Sealed lead-acid
230Vac
50Hz +/- 0.5% in free
running mode (Line sync
range +/- 1Hz)
linear load.
8.6 Amps
.7 lagging
3.0
111.00 lbs. (50.35 kg.)
panel
82%
DB9 male connector
DB9 female
connector
(Pin 9 not used)