Interface In The User Program (Status Of Blocks) - Siemens CP 342-5 Manual

Communications processor for connection of simatic s7-300 / to profibus dp
Hide thumbs Also See for CP 342-5:
Table of Contents

Advertisement

Notes on operation

4.3 Interface in the user program (status of blocks)

4.3
Interface in the user program (status of blocks)
Status displays with the program block AG_SEND
For the CP 342-5 (6GK7 342-5DA03-0XE0), note the following over and above the
information in /4/ (Page 48), Release 03/2010:
DONE
ERROR
0
1
Status displays with the program block DP_DIAG
For the CP 342-5 (6GK7 342-5DA03-0XE0), note the following over and above the
information in /4/ (Page 48), Release 03/2010:
DONE
ERROR
STATUS
1
0
0000
1
0
8248
38
STATUS
Meaning
8315
Possible additional meaning:
H
This error code can also occur with bus problems (for example physical disturb-
ances due to bad cable connections or different settings for the transmission speed
on the nodes).
Possible
Meaning
with DTYPE
0, 1
Job completed without error
H
and 4-9
Note:
With DTYPE 2, 3 and 10, error-free execution is indicated by a status
code other than "0". Below (see table DP_DIAG codes in /4/ (Page 48)),
you will see the detailed status codes for error-free execution for the
range:
82XX
If an error occurs in execution, you receive status codes in the following
ranges:
80XX
2, 3, 10
Job completed without error
H
Note: This is the default code for the named diagnostics types if there is
no special situation to signal.
H
, 83XX
, 8FXX
H
H
H
CP 342-5 / CP 342-5 FO