Assembling And Connecting The Safety Ground Wire For Dc Power Supply - Dell S5000 Getting Started Manual

Hide thumbs Also See for S5000:
Table of Contents

Advertisement

Figure 16. Connecting AC Power Supply Cords
1. AC3 Prong
NOTE: The system is powered-up as soon as you connect the power cord between the system and the power
source.
CAUTION: Always disconnect the power cable before you service the power supply slots.
CAUTION: Use the power supply cord as the main disconnect device on the AC system. Ensure that the
socket-outlet is located/installed near the equipment and is easily accessible.
4.
Repeat steps 1 through 3 above using the second PSU.
NOTE: Ensure that the PSU is correctly installed. When you correctly install the PSU, the power connector is on the
left side of the PSU.

Assembling and Connecting the Safety Ground Wire for DC Power Supply

WARNING: For equipment using –(48–60) V DC power supplies, a qualified electrician must perform all connections
to DC power and to safety grounds. Do not attempt connecting to DC power or installing grounds yourself. All
electrical wiring must comply with applicable local or national codes and practices. Damage due to servicing that
Dell Networking did not authorize is not covered by your warranty.
1.
Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm (0.175 inch) of copper
wire.
2.
Using a hand-crimping tool (Tyco Electronics, 58433-3 or equivalent), crimp the ring-tongue terminal (Jeeson
Terminals Inc., R5-4SA or equivalent) to the green/yellow wire (safety ground wire).
3.
Connect the safety ground wire to the grounding post on the back of the system using a #6–32 nut equipped with a
locking washer.
20