Operator Interface - ABB SACE Emax E2.2 Installation, Operation And Maintenance Instructions For The Installer And The User

Low voltage air circuit-breakers
Table of Contents

Advertisement

3 - Operator interface

Introduction The operator interface of the Ekip Dip protection trip unit allows you to:
Components of the interface The Ekip Dip operator interface appears as follows:
33 | © 2019 ABB | 1SDH001000R0002 - ECN000109166 - Rev. D
• Set the parameters relating to the available protections.
• View the status of the trip unit and alarms.
• Connect to the frontal connector to communicate and perform the opening test.
Figure 76
The following table provides a description of the components of the interface:
Position
Type
A
B
C
LED
D
E
F
G
H
Protections:
thresholds
I
L
M
N
Protections: times
O
P
Settings
Q
Test
R
IMPORTANT: the figure above refers to an Ekip Dip, LSIG version. In the case of Ekip
Dip LI or LSI versions, LEDs and dip-switches related only to the protections present
are available.
Description
L Protection LED (alarm and trip)
L Protection LED (pre-alarm)
S Protection LED (alarm and trip)
I Protection LED (trip)
G Protection LED (alarm and trip)
Power-on LED (trip unit powered and on)
L Protection dip-switch (threshold I1)
S Protection dip-switch (threshold I2)
I Protection dip-switch (threshold I3)
G Protection dip-switch (threshold I4)
L Protection dip-switch (time t1)
S Protection dip-switch (time t2 and type of curve)
G Protection dip-switch (time t4 and type of curve)
Neutral and frequency dip-switch
Test pushbutton
Test connector
ABB | SACE Emax 2
Ekip Dip | 3 - Operator interface