1200-2000 Series Fire Panels, Repeaters, and Emulators
26
Interconnection and Wiring Guide

4 First-time start-up and configuration

This section describes first-time start-up, the DIP switch, software, and protocol configuration options
for your product.
4.1

First-time start-up

When first starting up the control panel the FC12xx / FC20xx CPU module (located inside the control
panel door) must be configured as follows:
Memory switch LOCKED
Service Mode switch OFF
The memory should only be unlocked when prompted during the initial start-up procedure.
4.2

Configuration of 2000 series panels

Use the panel DIP switch located on the host power supply board to set the system protocol, mode,
and language.
4.2.1
Protocol selection
Use DIP switches 7 and 8 to select the protocol.
Table 3: Protocol selection (DIP switches 7 and 8)
1
2
3
4.2.2
Mode selection
Use DIP switches 4 to 6 to select the panel operating mode.
Table 4: Mode selection (DIP switches 4 to 6)
1
2
3
4
5
6
7
8
ON
OFF
OFF
OFF
4
5
6
7
8
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
Protocol
900 series protocol
2000 series protocol
Mode
EN mode
VdS mode (if VdS module installed)
NEN mode
EP mode
BS mode