Toshiba CD332 User Manual page 19

Toshiba change detect dc input module user's manual
Table of Contents

Advertisement

3.2 Interrupt generation timing setting
The interrupt generation timing of each input point can be selected either rising, falling
or both edges.
• Rising edge (OFF to ON)
Input
Interrupt
• Falling edge (ON to OFF)
Input
Interrupt
• Both edges (OFF to ON and ON to OFF)
Input
Interrupt
This setting is made by the DIP switches provided on the front of the CD332.
CHANGE DETECT
UP
IN0
1
2
3
4
5
6
7
DOWN
IN0
1
2
3
4
5
6
7
OFF
ON
OFF
ON
OFF
ON
Rising edge
Falling edge
Both edges
ON
NOTE
ON
OFF
OFF
OFF
Mode
UP
ON
OFF
ON
(1) This setting is available for each input
point individually.
(2) The factory setting is all ON.
(Both edges)
(3) Changes of the DIP switches are
effective while power on.
3. Mode Setting
DOWN
OFF
ON
ON
15