GE Current Tetra GEPS12W-60 Instruction Manual page 4

Led systems power supply

Advertisement

Power Supply Specifications
Performance Data
Input Voltage (VAC)
Input Frequency (Hz)
Input Current (A)
THD
PF
Output Voltage (VDC)
Output Current (ADC)
Output Power (W)
Environmental Operating Temperature Range
Environmental Humidity (non-condensing)
Environmental Storage Temperature Range
Environmental Rating
Dimensions
Troubleshooting
Symptom
Solution
All letters are OFF
• Recycle AC power, turn it off, then turn on again.
• If still off, check the power supply DC output voltage using a voltmeter. It should be nominally
Some LEDs appear dim
• Ensure the overall length of the Tetra
• Ensure the length of supply wire is equal to or below the recommended remote mounting distance.
Some of the letters
• Inspect and correct the wires of the non-illuminated letters for damage/polarity issues; If no issues are found, see the
are not illuminated
Shadows
• Re-route supply wire and secure to the back of the can with electrical grade RTV silicone. Adjust wire connector
• Adjust LED layout to ensure uniformity of illumination of the face of the letter.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may
cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.
This Class [A] RFLD complies with the Canadian standard ICES-005. Ce DEFR de la classe [A] est conforme à la NMB-005 du Canada.
This product is intended to be used as a lamp control gear that is installed after the mains control switch.
All trademarks are the property of their respective owners. Information provided is subject to
change without notice. All values are design or typical values when measured under laboratory
conditions. Current, powered by GE is a business of the General Electric Company.
© 2019 GE.
www.currentbyge.com
» If there is DC output, inspect and correct all DC wire damage/polarity issues; If no issue is found, replace the
OFF-module string.
» If there is no DC output, have a licensed electrician check the input AC voltage and if there is correct AC voltage,
replace the power supply.
» If there is no AC voltage, correct the upstream AC issue.
troubleshooting solution for "All letters are OFF."
orientation so that it does not cover any LEDs.
Conforms to the following standards:
SIGN186
Min
90
-
-
-
0.9
11.4
0.8
-
-40°C
0%
-40°C
IP66 Rated
12 in. x 2 in. x 1.25 in. (307 mm x 52 mm x 32 mm)
LED System does not exceed the maximum load.
®
(Rev
05/30/19
)
GE2022-3612
Typical
100-240
50/60
-
-
-
12.0
-
-
+25°C
+60°C*
-
-
*Maximum case temperature is
12
V.
Max
264
-
0.85
20
-
12.6
5.0
60
95%
+85°C
°C
80

Advertisement