Names And Functions Of Main Parts - Toshiba RS-485 Operation Manual

Option unit for tosvert vf-s7
Hide thumbs Also See for RS-485:
Table of Contents

Advertisement

5

3. Names and functions of main parts

Switch for communication speed
& Termination resistor setting
(Note) Set the switch before power on
(Back side of the UNIT)
OFF (OPEN)
ON
1 2 3 4
(Front side of the UNIT)
(1) Communication speed setting (SW1, 2)
Setting
SW1
SW2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Set the communication speed to the
same as ASD's (F800).
(2) Terminating resistor setting (SW3, 4)
SW3-ON : Connecting receiving side
SW4-ON : Connecting transmitting side
Connect the terminating resistor to both
end of system.
Connector terminal (removal side)
Terminal pitch : 5.08mm
Wire size (shielded twisted-pair cable recommended)
Bare wire (without stick lug) : 0.2~1.5mm
Phoenix Contact TWIN terminal : (wire size below) × 2
Part number: AI-TWIN2×0.5-8WH, AI-TWIN2×0.75-8GY, AI-TWIN2×1-8RD, AI-
TWIN2×1.5-8BK
Removable terminal block
COMBICON terminal blocks such as the Phoenix Contact TMSTBP series that allows
signal branching can be used in place of included terminal.
Baud
rate
1200
2400
4800
9600
7mm
Receiving
Transmitting
terminal
terminal
RXA, RXB
TXA, TXB
SW
R
R
T
T
X
X
X
A
B
A
INVERTER 1
RS485
OPTION UNIT
INVERTER 2
Communication connector: INVERTER 1, INVERTER 2
Connect with the communication connector CN1 of the
ASD with communication cable.
2
5
Signal common
terminal
SG
Shield
terminal
SHIELD
S
S
Connector
X
G
H
terminal
B
I
(socket side)
E
L
Insert removal
D
terminal block
M3
Connector terminal
(removal side)
Insert socket
terminal block

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tosvert vf-s7

Table of Contents