Installing the Device
2.6.1 Connecting AC or DC Power
4.
5.
6.
16
Connect the positive wire from the power source to the positive/live (+/L) termi-
nal on the terminal block.
1
3
4
5
6
7
Screw-Type Terminal Block
1
Pluggable Terminal Block
2
Jumper
3
Positive/Live (+/L) Terminal
4
Negative/Neutral (-/N) Terminal (-/N)
5
Surge Ground Terminal
6
Chassis Ground Terminal
7
Figure 2.6
Terminal Block Wiring
Connect the negative wire from the power source to the negative/neutral (-/N)
terminal on the terminal block.
Install the supplied metal jumper between terminals 2, 4 and 6 to connect the
surge ground terminals to the chassis ground terminal. The surge ground termi-
nals are used as the ground conductor for all surge and transient suppression cir-
cuitry internal to the unit.