Setting and using method

2. Setting of Contact Signal Input

n For input contact closure only(No power input)
CHANGE
OVER_SW
RESET_SW
Notes
Do not input the voltage signal in
"NON VOLT" setting mode otherwise
it will cause serious damage
n For input contact voltage : DC 12 V, 24 V~
Connect separate
External voltage of
DC 12 V, 24 V~
CHANGE
OVER_SW
RESET_SW
10 Dry contact for thermostat
Thermostat
LG does not
supply this section
(Field supply)
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Thermostat
LG does not
supply this section
(Field supply)
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT

3. Setting of 'SETTING_SW'

n Using 'SETTING_SW' , select the Option of control Function
as described below
CN_Ther/Oper
CN_MODE
CHANGEOVER_SW
RESET_SW
DISPLAY_LED
TEMP_SW
CN_OUT
<SETTING_SW Function>
WIND Signal
Thermal
No.
en/disable
en/disable
0
Disable
Disable
1
Disable
Disable
2
Disable
Disable
3
Disable
Disable
4
Disable
Enable
5
Disable
Enable
6
Disable
Enable
7
Disable
Enable
8
Enable
1)
Disable
9
Enable
Disable
A
Enable
Disable
B
Enable
Disable
C
Enable
Enable
D
Enable
Enable
E
Enable
Enable
F
Enable
Enable
1) Enable CN_WIND signal – Amount of wind flow (Low, Middle, High) signal enable
2) Enable Thermo ON/OFF input signal
- Desired Temperature 18 ℃ in cooling mode
- Desired Temperature 30 ℃ in heating mode
- No function in FAN mode
3) Enable CN_MODE signal – Operation mode (Cool, Heat, Fan) signal enable
4) Enable Thermostat priority control mode – Indoor's remote-controller signal will be disregarded
Notes
• Information of 'SETTING_SW' is sensed only initial step by Dry contact module therefore , once the
configuration changed , Reset of Dry contact module is required.
• After power input or unit's reset , wait 25~30 sec(Display LED 10 times blinking) for unit stabilization
then Dry contact module will operate normally.
Setting and using method
CN_WIND
SETTING_SW
SETTING_SW
Oper Mode
Dry Contact Control
en/disable
Priority
Disable
Disable
Disable
Enable
Enable
3)
Disable
Enable
Enable
2)
Disable
Disable
Disable
Enable
Enable
Disable
Enable
Enable
Disable
Disable
Disable
Enable
Enable
Disable
Enable
Enable
Disable
Disable
Disable
Enable
Enable
Disable
Enable
Enable
Installation manual 11