Haier CA0035AANC Installation, Operation And Technical Manual page 21

Air cooled module water chiller
Table of Contents

Advertisement

Antifreeze Temp followed by [CHANGE] 5or6 to set between 0 to 9
4. To enable the system to automatically restart after interruption of power supply, press [SELECT]
5or6 for Auto-restart followed by [CHANGE] 5or6 to set "ENABLE". If "DISABLE" is chosen,
the system will remain shutdown after power resumes.
4.4. LOAD CONTROL
To apply suitable time duration for starting up or shutting down according to varying numbers of chiller
modules in use, press SELECT to move to Load Control setting menu to change the Load or Unload
Parameter. This program is normally preset for self-adaptive application as denoted by --.
1. To program the startup duration, press [SELECT] for Startup Parameter followed by [CHANGE]
5or6 to set from 01 to 16. If the parameter appears as "――", the setting is invalid and is on
self-adaptive mode.
2. To program the shutdown duration, press [SELECT] 5or6 for Shutdown Parameter and
repeat the above process.
3. To access the manufacturer's setting, press [SELECT] 5or6 for Mfg Parameter followed by
[ENTER], and key in the password provided by the manufacturer.
The default password is "2008". To key in password, repeat password entry process. Press
[ENTER] to access the Mfg parameter to check for the number of days the system has been
operating and the remaining number of days under the current setting. User may change the
parameters and password if required.
Note: To enter the Manufacturer's Password, use only [SELECT] 6and6 and
[CHANGE]5or6 process to input the password.
LOAD CONTROL
Load Parameter :——
Unload Parameter:——
Mfg Parameter
Set Password
MFG PARAMETER PASSWORD
Version
GS1.1
Enter password
****
HAIER CHILLER
.