UPS2000-MBS-16A PDU &
Maintenance Bypass Switch Module
Quick Guide
Issue: 01
Date: 2016-03-25
1
Overview
NOTICE
To safely operate this unit, read and follow all instructions carefully. Read this manual
thoroughly before attempting to unpack, install, or operate. You may keep this quick guide for
further reference.
1. The unit must be used indoor only.
2. Do not place the unit near liquid or in an excessively damp environment.
3. Do not place the unit directly in the sun or near a hot source.
4. Do not let liquid or foreign objects enter the unit.
5. Ground the unit using a 2P + ground outlet.
6. When installing the unit, ensure that the sum of the leakage currents of the unit and the
devices it powers does not exceed 3.5 mA.
Model
UPS2000-MBS-16A
(1) Slave outlets
(5) Bypass switch
(9) Circuit breaker
2
Inspection
Remove the unit from the shipping package and check it for damage that may occur during
transportation. Notify the carrier and place of purchase if any damage is found. The shipping
package contains:
PDU & Maintenance bypass switch module x 1
Packing list x 1
Quick guide x 1
Screws and mounting brackets
Weight
1.5 kg
(2) Master outlets
(6) Outlet for UPS
output
(10) Master/slave
function switch
Dimensions (H x W x D)
50 mm x 438 mm x 80 mm
(3) Power indicator
(7) Outlet for UPS
input
Mains power cord x 1
Power cord for 1 kVA/2 kVA UPS x 2
Power cord for 3 kVA UPS x 3
Output power cables x 2
1
Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved.
(4) Slave on indicator
(8) AC input

Advertisement

loading

Summary of Contents for Huawei UPS2000-MBS-16A

  • Page 1 Power cord for 1 kVA/2 kVA UPS x 2 • • Quick guide x 1 Power cord for 3 kVA UPS x 3 • • Screws and mounting brackets Output power cables x 2 Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved.
  • Page 2 Installing the Unit Scenario Rack-mounting NOTICE Front When installing, ensure that the PDU rear panel is aligned with the UPS rear panel. Rear Installing Cables Connecting the UPS NOTE 1. Connect a power cable from UPS input to UPS input outlet on the unit. Use another power cable to connect UPS output to UPS output outlet on the unit.
  • Page 3 Connecting Equipment NOTICE 1. The master/slave function is disabled by default. Ensure that the master/slave function switch is on the disable status before operation. 2. Only when the master/slave function is enabled, loads connected to slave outlets will be shut down after load is detected lower than 10 W in master outlet.
  • Page 4 Master Load < 10 W Output Status Master/slave Slave On indicator function is enabled Slave output Slave On indicator Master/slave function is disabled Slave output HUAWEI TECHNOLOGIES CO., LTD. Huawei Industrial Base, Bantian, Longgang Shenzhen 518129 People's Republic of China www.huawei.com...