9
Operation
9.1
Control elements
Local operation on the device
The manual operation on the device is activated with a press of the button longer than 2
■
seconds.
The manual operation is exited automatically after 5 minutes. This time is reset with every
■
press of the button during manual operation.
Telegrams that are received via the bus are not carried out during manual operation. After
■
completion, the last status received via the bus is set.
9.2
Status indication
Fig. 18:
Status indication
Status indication [1]
Green
Off
Yellow
Table 1: Status indication
Product manual 9AKK107680A3585
Status
After activation of the mains voltage and the free@home bus:
The LED lights up permanently green.
■
– Flashes fast (5 Hz), if only the free@home bus is connected.
– Flashes slowly (1 Hz) during manual operation.
The device has no free@home connection.
Lights up permanently during an error on the DALI bus.
■
Flashes fast (5 Hz) during initialization and address assignment.
■
Displays the status (On/Off) during manual operation.
■
1
Operation
│32