Download Print this page

Siemens SINAMICS G130 Operating Instructions Manual page 33

Dv/dt filter plus voltage peak limiter
Hide thumbs Also See for SINAMICS G130:

Advertisement

Table 6- 3
Technical data for the dv/dt filter plus Voltage Peak Limiter, 3 AC 500 V ... 600 V, part 1
Article number
Suitable for Power Module
Unit rating of the Power
Module
I
thmax
Degree of protection
dv/dt reactor
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- to the Power Module
- Load
- PE
Max. permissible cable
length between dv/dt reactor
and motor
Dimensions
Width
Height
Depth
Weight, approx.
Voltage peak limiter
Power loss
- at 50 Hz
- at 60 Hz
- at 150 Hz
Connections
- to the dv/dt reactor
- DC
- PE
Dimensions
Width
Height
Depth
Weight, approx.
dV/dt filter plus Voltage Peak Limiter
Operating Instructions, 11/2017, A5E00692302A
6SL3000-
2DH32-2AA0
6SL3310-
1GF31-8AA3
1GF32-2AA3
kW
110
132
A
215
IP00
kW
0.578
kW
0.604
kW
0.645
M10
M10
M6
m
mm
460
mm
360
mm
275
kg
83
kW
0.032
kW
0.03
kW
0.027
Terminal 70 mm²
Terminal 70 mm²
Terminal 35 mm²
mm
392
mm
285
mm
210
kg
16
2DH33-3AA0
2DH34-1AA0
1GF32-6AA3
1GF34-1AA3
1GF33-3AA3
160
200
330
IP00
0.595
0.62
0.661
M10
M10
M6
300 (shielded)
450 (unshielded)
460
360
275
135
0.042
0.039
0.036
Terminal 70 mm²
Terminal 70 mm²
Terminal 35 mm²
392
285
1312.5
210
16
Technical specifications
2DH35-8AA0
1GF34-7AA3
1GF35-8AA3
250
315
400
410
575
IP00
IP00
0.786
0.862
0.826
0.902
0.884
0.964
M12
M12
M12
M12
M6
M6
460
460
385
385
312
312
147
172
0.051
0.063
0.048
0.059
0.043
0.054
M8
M8
M8
M8
M8
M8
309
309
1312.5
400
400
48
48
31

Advertisement

loading