Siemens SITRANS L Series Operating Instructions Manual
Siemens SITRANS L Series Operating Instructions Manual

Siemens SITRANS L Series Operating Instructions Manual

Radar transmitters, probe with ma/hart
Hide thumbs Also See for SITRANS L Series:
Table of Contents

Advertisement

SITRANS L
Radar transmitters
SITRANS Probe LR with mA/HART
Operating Instructions
7ML5430 (SITRANS Probe LR with mA/HART)
05/2019
A5E32337711-AC
Introduction
Safety notes
Description
Installing/mounting
Connecting
Commissioning
Parameter assignment
Service and maintenance
Troubleshooting
Technical data
Dimension drawing
Technical reference
HART communication
Application examples
Hazardous area installations
Certificates and support
1
2
3
4
5
6
7
8
9
10
11
A
B
C
D
E

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS L Series

  • Page 1 Introduction Safety notes Description SITRANS L Installing/mounting Radar transmitters SITRANS Probe LR with mA/HART Connecting Commissioning Operating Instructions Parameter assignment Service and maintenance Troubleshooting Technical data Dimension drawing Technical reference HART communication Application examples 7ML5430 (SITRANS Probe LR with mA/HART) Hazardous area installations Certificates and support 05/2019...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Introduction ..............................8 Purpose of this documentation ....................8 Checking the consignment ....................... 8 Industrial use ..........................8 Product compatibility ......................... 9 Security information ........................9 Transportation and storage ..................... 10 Notes on warranty ........................10 Safety notes ............................. 11 Preconditions for use ......................
  • Page 4 Table of contents Commissioning ............................26 Basic safety notes ........................26 Local commissioning ......................26 6.2.1 Activating SITRANS Probe LR ....................26 6.2.2 Operating SITRANS Probe LR ....................26 6.2.3 Low temperature effects on RUN/PROGRAM modes ............27 6.2.4 RUN mode ..........................27 6.2.5 PROGRAM mode........................
  • Page 5 Table of contents 7.16 P069 Unlocked value ......................51 7.17 Failsafe (P070 to P073) ......................52 7.17.1 P070 Failsafe timer ......................... 52 7.17.2 P071 Failsafe material level ....................52 7.17.3 P073 Failsafe level ........................52 7.18 mA output (P201 to P215) ...................... 53 7.18.1 P201 mA Output function ......................
  • Page 6 Table of contents 7.27.4 P838 Auto false echo suppression distance ................67 7.27.5 P839 TVT hover level ......................69 7.28 Test (P900 to P924) ....................... 69 7.28.1 P900 Software revision number ..................... 69 7.28.2 P901 Memory test ........................69 7.29 Measurement .........................
  • Page 7 Table of contents TVT (Time varying threshold) curves ..................88 Auto false-echo suppression ....................88 Output ............................. 90 A.10 Failsafe ........................... 91 A.11 Chemical compatibility ......................91 HART communication ..........................92 HART communication for SITRANS Probe LR ............... 92 HART electronic device description (EDD) ................92 SIMATIC process device manager (PDM)................
  • Page 8: Introduction

    Introduction Purpose of this documentation These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation. The instructions are aimed at persons mechanically installing the device, connecting it electronically, configuring the parameters and commissioning it, as well as service and maintenance engineers.
  • Page 9: Product Compatibility

    In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
  • Page 10: Transportation And Storage

    The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
  • Page 11: Safety Notes

    Safety notes Preconditions for use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device.
  • Page 12: Industry Canada Conformity

    Safety notes 2.2 Laws and directives 2.2.1 Industry Canada conformity Canada Installations only: Industry Canada (IC) rules NOTICE Use on a "no-interference, no-protection" basis This device shall be installed and operated in a completely enclosed container to prevent RF emission, which otherwise can interfere with aeronautical navigation. Installation shall be done by trained installers, in strict compliance with the manufacturer’s instructions.
  • Page 13: Radio Equipment Directive (Red) Compliance (Europe)

    2.2.3 Radio Equipment Directive (RED) compliance (Europe) Hereby, Siemens declares that the SITRANS Probe LR is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU. The Probe LR complies with EN 302 372 for use in closed storage vessels, when installed according to the installation requirements of EN 302 372, and may be used in all EU countries.
  • Page 14: Ce Electromagnetic Compatibility (Emc) Conformity

    Safety notes 2.3 Use in hazardous areas 2.2.5 CE electromagnetic compatibility (EMC) conformity This equipment has been tested and found to comply with the following EMC standards: EMC standard Title CISPR 11:2009 + A1:2010/EN Limits and methods of measurements of radio disturbance 55011:2009 + A1:2010, CLASS A characteristics of industrial, scientific, and medical (ISM) radio- frequency equipment.
  • Page 15: Loss Of Safety Of Device With Type Of Protection "Intrinsic Safety Ex I

    Safety notes 2.3 Use in hazardous areas 2.3.1 Loss of safety of device with type of protection "Intrinsic safety Ex i" WARNING Loss of safety of device with type of protection "Intrinsic safety Ex i" If the device or its components have already been operated in non-intrinsically safe circuits or the electrical specifications have not been observed, the safety of the device is no longer ensured for use in hazardous areas.
  • Page 16: Description

    Description SITRANS Probe LR SITRANS Probe LR is a 2-wire loop-powered, continuous level measuring instrument that utilizes advanced pulse radar technology operating at a frequency of approximately 6 GHz. The instrument consists of an electronic component coupled to the antenna and process connection.
  • Page 17: Sitrans Probe Lr System Implementation

    Description 3.2 SITRANS Probe LR system implementation SITRANS Probe LR system implementation SITRANS Probe LR supports HART communication protocol and SIMATIC PDM software. Typical PLC/mA configuration with HART ① Power supply Depending on the system design, the power supply may be separate from the PLC, or integral to A 250 Ohm resistor may be required if the loop resistance is less than 250 Ohms.
  • Page 18: Installing/Mounting

    Installing/mounting Basic safety notes 4.1.1 Incorrect disassembly WARNING Incorrect disassembly The following risks may result from incorrect disassembly: - Injury through electric shock - Risk through emerging media when connected to the process - Risk of explosion in hazardous area In order to disassemble correctly, observe the following: •...
  • Page 19: Installation Notes

    Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 20 Installing/mounting 4.2 Installation notes Precautions ● Avoid proximity to high voltage or current wiring, high voltage or current contacts, and to variable frequency motor speed controllers. ● Avoid interference to the emission cone from obstructions or from the fill path. ●...
  • Page 21: Nozzle Location

    Installing/mounting 4.3 Nozzle location Nozzle location Beam angle ● Beam angle is the width of the cone where the energy density is half of the peak energy density. ● The peak energy density is directly in front of and in line with the rod antenna. ●...
  • Page 22: Mounting Instructions

    Installing/mounting 4.5 Mounting instructions The end of the shield section or end of the horn should protrude a minimum of 10 mm (0.4”) to avoid false echoes being reflected from the nozzle. ① Locking ring secured by three 2 mm Allen set-screws ②...
  • Page 23: Connecting

    Connecting Power Note DC terminals DC terminals shall be supplied from an SELV (Safety Extra Low Voltage) source in accordance with IEC-1010-1 Annex H. Note Insulation All field wiring must have insulation suitable for rated voltages. Connecting SITRANS Probe LR Unscrew the two lid screws to access the terminal block.
  • Page 24: Nameplates For Hazardous Area Installations

    Connecting 5.3 Nameplates for hazardous area installations Note • Use shielded, twisted pair cable (wire gauge AWG 14 to 22). • Separate cables and conduits may be required to conform to standard instrumentation wiring practices or electrical codes. • The non-metallic enclosure does not provide a continuous ground path between conduit connections: use grounding type bushings and jumpers.
  • Page 25: Fm And Csa Connection Drawings

    The FM Intrinsically Safe connection drawing (A5E01003040) listed on the device nameplate can be downloaded from our website: Product page (www.siemens.com/ProbeLR) Go to Technical Info > Images, graphics, drawings. The CSA Intrinsically Safe connection drawing (A5E01003039) listed on the device nameplate can be downloaded from our website: Product page (www.siemens.com/ProbeLR)
  • Page 26: Commissioning

    Commissioning Basic safety notes WARNING Loss of explosion protection Risk of explosion in hazardous areas if the device is open or not properly closed. • Close the device as described in Connecting SITRANS Probe LR (Page 23). WARNING Loss of type of protection Risk of explosion.
  • Page 27: Low Temperature Effects On Run/Program Modes

    Commissioning 6.2 Local commissioning 6.2.3 Low temperature effects on RUN/PROGRAM modes If the internal temperature falls to –30 °C (–22 °F) or below, it will affect both RUN and PROGRAM modes. RUN mode will operate normally, with the following exceptions: ●...
  • Page 28: Program Mode

    ● Activate PROGRAM mode at any time, to change parameter values and set operating conditions. ● For local programming, use the Siemens handheld programmer. ● For programming from a distance, use either a PC running SIMATIC PDM, or a HART handheld communicator.
  • Page 29: Handheld Programmer

    Commissioning 6.2 Local commissioning Lithium batteries are primary power sources with high energy content designed to provide the highest possible degree of safety. WARNING Potential hazard Lithium batteries may present a potential hazard if they are abused electrically or mechanically. Observe the following precautions when handling and using lithium batteries: •...
  • Page 30: Handheld Programmer: Function Keys In Program Mode

    Commissioning 6.2 Local commissioning ① Numeric and auxiliary keys ② Function keys 6.2.6.2 Handheld programmer: function keys in PROGRAM mode FUNCTION Values Decimal point Negative value CLEAR value TOGGLE between Units and % on parameter value End PROGRAM session and enable RUN mode Update echo quality parameters Parameter scroll-up Parameter scroll-down...
  • Page 31: Handheld Programmer: Function Keys In Run Mode

    Commissioning 6.2 Local commissioning 6.2.6.3 Handheld programmer: function keys in RUN mode RUN mode mA output value displayed in auxiliary reading field. Internal enclosure temperature displayed in auxiliary reading field. Parameter for auxiliary readings Press to display the auxiliary reading field when in RUN mode. Displays the value representing Echo Confidence (P805).
  • Page 32 Commissioning 6.2 Local commissioning 1. Press PROGRAM then DISPLAY , to activate the PROGRAM mode. ① PROGRAM icon ① Parameter value ② Parameter number 2. Either use the ARROW keys to scroll to a different parameter, or: 3. Press DISPLAY to open the Parameter Number field.
  • Page 33: Security

    Commissioning 6.2 Local commissioning 6.2.7 Security The Lock parameter, P000, secures SITRANS Probe LR against changes via the handheld programmer. To enable programming, set P000 to the Unlocked Value stored in P069. To disable programming, enter a different value. Note Configuration change A remote master can still change configuration, if P799 is set to allow this.
  • Page 34: Using Units Or Percent (%)

    Commissioning 6.2 Local commissioning 3. Key in 999. Press CLEAR then ENTER , to Clear All and initiate reset. The LCD displays C.ALL. 4. Reset complete. (Reset takes several seconds to complete.) 6.2.10 Using units or percent (%) Many parameters can be viewed either as a percentage, or in measurement units (P005). View the parameter, then press MODE to toggle between units and percentage.
  • Page 35: P001: Operation

    Commissioning 6.2 Local commissioning 6.2.11.2 P001: Operation Select the measurement mode required for the application (P001: Operation) To measure how full the vessel is, select Level: the reading can be returned as level or as volume: ● for a level reading, ensure P050 is set to 0: the reading returns the distance from process empty level (Empty) to the current level ●...
  • Page 36: P003: Measurement Response

    Commissioning 6.2 Local commissioning 6.2.11.3 P003: Measurement response Set response time to filling/emptying rate (P003: Measurement Response) Set P003 to a measurement response speed just faster than the maximum filling or emptying rate (whichever is greater). Parameter Values Description Parameters affected by P003 Slow 0.1m/minute P070, P700, P701, P709, P711...
  • Page 37: P007: Span

    Commissioning 6.2 Local commissioning ① Reference point ② Span ③ Level setup ④ Level ⑤ Empty Note P006 and P007 are interlinked: see notes attached to P007. 6.2.11.6 P007: Span Set the range to be measured (P007: Span) Value Range 0.0000 to 20.00 Default 19.56 (see note below)
  • Page 38: P010: Language

    Commissioning 6.2 Local commissioning 6.2.11.7 P010: Language The parameter title appears in the language selected, for parameters P000 to P010. If a language is selected, parameter titles for the Quick Start parameters are displayed in the auxiliary reading field. Parameter Value Description Numeric/None...
  • Page 39: Additional Settings

    Commissioning 6.2 Local commissioning 6.2.11.9 Additional settings ● Convert readings to volume (P050 to P055) ● Stored unlock value (P069) ● Set Failsafe timer conditions (P070 to P073) ● Control Analog Output (P201 to P215, and P911) ● Check installation records (P341 to P346) ●...
  • Page 40: Parameter Assignment

    Parameter assignment Note • Keep infrared devices such as laptops and cell phones away from SITRANS Probe LR to prevent inadvertent operation. • Do not use the Handheld Programmer at the same time as SIMATIC PDM, or erratic operation may result. SITRANS Probe LR is configured through its parameters, and the application determines the parameter values which are entered into the instrument.
  • Page 41: P000 Lock

    Parameter assignment 7.1 P000 Lock To access a secondary index and change a value: Note • In a parameter with a secondary index, the ARROW keys control whichever index was most recently changed. • When you first access a parameter, the ARROW keys control the primary index (parameter number).
  • Page 42: Quick Start (P001 To P010)

    Parameter assignment 7.2 Quick start (P001 to P010) To unlock the instrument and enable programming changes: 1. Key in 0, and press ENTER 2. Key in the Unlocked Value (P069). 3. Press ENTER to set the value: PROGRAM mode is now active for programming. Quick start (P001 to P010) P001 Operation Note...
  • Page 43: P003 Measurement Response

    Parameter assignment 7.3 P003 Measurement response ① ④ Reference point Empty ② ⑤ Span Space ③ ⑥ Level Distance Note • Setting P001 resets Span (P007), unless Span has previously been set to a different value. Span is set to Empty distance minus 110% of Blanking unless P001 is set to 3 (distance measurement).
  • Page 44: P004 Antenna Type

    Parameter assignment 7.4 P004 Antenna type Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Slower settings provide higher accuracy: faster settings allow for more level fluctuation. ● Echo Verification (P711): discriminates between agitator blades in motion (spurious noise) and the target surface (true echo).
  • Page 45: P007 Span (Process Full Level)

    Parameter assignment 7.7 P007 Span (process full level) ① Reference point ② Span ③ Level setup ④ Level ⑤ Empty Note • Default setting is maximum range. • P006 and P007 are interlinked: see note attached to P007. P007 Span (process full level) Sets the range to be measured (referenced from Empty) in units selected at P005.
  • Page 46: P010 Language

    Parameter assignment 7.8 P010 Language P010 Language Values Numeric/None English German French Spanish If a language is selected, parameter titles for the parameters P000 to P010 are displayed. P050 to P055 Volume Note Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly described.
  • Page 47 Parameter assignment 7.10 P050 Vessel shape Enter the value for the vessel shape matching the monitored vessel or reservoir. P050 Vessel shape Description Also required Value ---- no volume calculation required flat bottom P051 conical or pyramidal bottom P051, P052 parabolic bottom P051, P052 spherical bottom...
  • Page 48: P051 Maximum Volume

    Parameter assignment 7.11 P051 Maximum volume P050 Vessel shape Description Also required Value sphere P051 universal linear level/volume break- P051, P054, P055 points 7.11 P051 Maximum volume For readings in volumetric units instead of percentage values, enter the vessel volume between Empty (P006) and Span (P007).
  • Page 49: P053 Vessel Dimension L

    Parameter assignment 7.13 P053 Vessel dimension L 7.13 P053 Vessel dimension L Dimension L as used in P050 Vessel Shape. Values Range 0.0000 to 99999 in units (P005) Default Related parameters P050 Vessel Shape Enter the vessel length L (excluding both end sections) if P050 = 7. Use the units selected in P005.
  • Page 50: P055 Volume Breakpoints

    Parameter assignment 7.15 P055 Volume breakpoints 7. Key in the level value for breakpoint 2, and press ENTER . (Use units defined in P005.) 8. Repeat steps 6 and 7 until level values have been entered for all the required breakpoints.
  • Page 51: P069 Unlocked Value

    • After a new value has been stored at P069, that value will be recalled after a master reset (P999). • Consult your Siemens representative, if you have forgotten the unlocked value. SITRANS Probe LR with mA/HART Operating Instructions, 05/2019, A5E32337711-AC...
  • Page 52: Failsafe (P070 To P073)

    Parameter assignment 7.17 Failsafe (P070 to P073) 7.17 Failsafe (P070 to P073) Note Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly described. 7.17.1 P070 Failsafe timer Note The last valid reading is maintained until the Failsafe timer expires. After the timer expires, the reading is set based on P071.
  • Page 53: Ma Output (P201 To P215)

    Parameter assignment 7.18 mA output (P201 to P215) 7.18 mA output (P201 to P215) Note Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly described. 7.18.1 P201 mA Output function Alters the mA output/measurement relationship, and allows the output to be set independently from P001.
  • Page 54: P210 4 Ma Setpoint (Low Output)

    Parameter assignment 7.18 mA output (P201 to P215) 7.18.2.1 P210 4 mA setpoint (low output) Note P210 is used to set the 4 mA loop current for the HART common module. Sets the process level corresponding to the 4 mA value. 4 mA always defaults to 0, and P201 determines whether this is a Level, Space, Distance, or Volume measurement.
  • Page 55: P211 20 Ma Setpoint (High Output)

    Parameter assignment 7.18 mA output (P201 to P215) 7.18.2.2 P211 20 mA setpoint (high output) Note P211 is used to set the 20 mA loop current for the HART common module. Sets the process level corresponding to the 20 mA value. 20 mA always defaults to 100%, and P201 determines whether this is a Level, Space, or Distance measurement.
  • Page 56: P214 4 Ma Output Trim

    Parameter assignment 7.19 Installation records (P341 to P346) 7.18.4 P214 4 mA output trim Note This parameter is for use only by Siemens service personnel. Calibrates the 4 mA output. 7.18.5 P215 20 mA output trim Note This parameter is for use only by Siemens service personnel.
  • Page 57: P342 Power-On Resets

    Parameter assignment 7.20 Range calibration (P652 to P655) 7.19.2 P342 Power-on resets The number of times power has been applied since the date of manufacture. Values (view only) Range 0 to 99999 (days) Related parameters P341 RUN Time This parameter is updated every time the instrument is reset or is powered up. 7.19.3 P343 Internal temperature WARNING...
  • Page 58: P652 Offset Correction

    200 mm (8”) 0.990 Contact your Siemens representative for other sizes and propagation factor numbers. The propagation factor is constant for a given pipe diameter, or can be determined by comparing the radar distance reading to the actual process material distance (measured from the reference point).
  • Page 59: Rate (P700 And P701)

    Parameter assignment 7.21 Rate (P700 and P701) 7.21 Rate (P700 and P701) Note Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly described. These parameters determine how material level changes are reported. 7.21.1 P700 Maximum fill rate Allows you to further adjust the SITRANS Probe LR response to increases in the actual material level (or an advance to a higher Failsafe Material Level, P071).
  • Page 60: Measurement Verification (P709 To P713)

    Parameter assignment 7.22 Measurement verification (P709 to P713) Enter a value slightly greater than the vessel’s maximum emptying rate, in Units (P005) or percent of Span (P007) per minute. P003 value Meters/minute 7.22 Measurement verification (P709 to P713) Note Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly described.
  • Page 61: P712 Echo Lock Sampling

    Parameter assignment 7.22 Measurement verification (P709 to P713) Use this feature to select the measurement verification process. Values Maximum verification Material agitator Total lock Related P700 Maximum Fill Rate parameters P701 Maximum Empty Rate P712 Echo Lock Sampling P713 Echo Lock Window P820 Algorithm If a material agitator or mixer is used in the monitored vessel, set Echo Lock for Maximum Verification or Material Agitator, to avoid agitator blade detection.
  • Page 62: P713 Echo Lock Window

    Parameter assignment 7.22 Measurement verification (P709 to P713) Example: ● Set P711 to 2 (material agitator) ● The preset values for P712 in this case are 5:2 ● Result: a new reading will not be validated unless 5 consecutive measurements higher or 2 consecutive measurements lower than the current reading occur.
  • Page 63: P752 Hart Address

    Restricted access - read only except for P799 which is read/write Note • P799 controls the access if you are using a HART master. • P000 controls the lock access if you are using the Siemens handheld programmer. 7.25 Echo processing (P800 to P807)
  • Page 64: P800 Near Blanking

    Parameter assignment 7.25 Echo processing (P800 to P807) 7.25.1 P800 Near blanking Defines the distance from the reference point to be ignored by the transmitter/receiver. Values Range 0.00 to 20 (m: selected in P005) Default 0.30 m (plus the shield length) Related parameters P006 Empty P007 Span...
  • Page 65: P805 Echo Confidence

    Parameter assignment 7.26 Algorithm (P820) 7.25.4 P805 Echo confidence Measures echo reliability. It displays the echo confidence of the measurement echo from the last measurement. P804 defines the minimum criterion for echo confidence. Values (view only) Range 0 to 99 ---- Shot not used Related parameters...
  • Page 66: Tvt (Time Varying Threshold) Adjustment Parameters (P831 To P839)

    First SITRANS Probe LR learns the echo profile. Then the learned profile, or part of the learned profile, is used to screen out false echoes. The following parameters are for authorized Siemens Service personnel or technicians familiar with Siemens echo processing techniques. View the echo profile first, before attempting to modify these parameters. 7.27.1...
  • Page 67: P838 Auto False Echo Suppression Distance

    Parameter assignment 7.27 TVT (Time Varying Threshold) adjustment parameters (P831 to P839) P837 instructs SITRANS Probe LR to learn the echo profile at that moment, and use the learned profile instead of the default TVT curve. Parameter Values Description P837 Use "learned"...
  • Page 68 Parameter assignment 7.27 TVT (Time Varying Threshold) adjustment parameters (P831 to P839) Display before Auto false-echo suppression (or when P837=0) ① Default TVT ② P839 Hover level Example after auto false-echo suppression ① TVT curve (learned) ② False echo ③ Material level SITRANS Probe LR with mA/HART Operating Instructions, 05/2019, A5E32337711-AC...
  • Page 69: P839 Tvt Hover Level

    Parameter assignment 7.28 Test (P900 to P924) 7.27.5 P839 TVT hover level Defines (in percent) how high the TVT curve is placed above the profile, relative to the largest echo. When SITRANS Probe LR is located in the center of the vessel, lower this parameter to prevent multiple echo detections.
  • Page 70: P920 Reading Measurement

    Parameter assignment 7.29 Measurement 7.29.2 P920 Reading measurement P920 corresponds to the final reading after all programming is applied. It is a copy of one of P921 to P924, depending on the setting for Operation (P001). Operation P001 Source parameter for P920 ---- Level P921 if P050 = 0, otherwise P924...
  • Page 71: P999 Master Reset

    Parameter assignment 7.29 Measurement 7.29.7 P999 Master reset Note Following a Master Reset, complete reprogramming is required. Resets all parameters to their factory settings, with the following exceptions: ● P000 and P069 are not reset. ● The learned TVT curve is not lost. Use this feature after upgrading software: 1.
  • Page 72: Service And Maintenance

    Service and maintenance WARNING Impermissible repair and maintenance of the device • Repair and maintenance must be carried out by Siemens authorized personnel only. Maintenance and repair work SITRANS Probe LR requires no maintenance or cleaning under normal operating conditions.
  • Page 73: Disposal

    – Number of returned devices/replacement parts – Reason for returning the item(s) ● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."...
  • Page 74: Troubleshooting

    Correct range calibration range. calibration. If fault persists, contact your local Siemens representative. * The device is operating in a low power condition Correct the power supply (resistance or that is outside its operating range. As a result, a voltage).
  • Page 75 Relocate device and/or lower process specifications: it is operating outside its temper- temperature enough to cool device. ature range. Inspect for heat related damage and contact your local Siemens representa- tive if repair is required. S:17 Calibration interval as defined in Maintenance Perform calibration.
  • Page 76: Fault Codes (Firmware Revision 1.05 Or Earlier)

    If fault range. persists, or for 1) and 2), contact your local Siemens representative. S:53 * Configuration lost: one or more parameter set- Restore user parameters using tings have been lost. This may occur after a SIMATIC PDM.
  • Page 77 Troubleshooting 9.3 Fault codes (firmware revision 1.05 or earlier) During a memory check, a problem with the memory has Replace unit. occurred. Explanation: The device periodically validates RAM, Flash, and EEPROM memory. If any fault is found, Fault 29 is displayed. Potential causes are: normal wear and tear operating outside temperature range other elec- trical damage The device was unable to get a measurement for the...
  • Page 78: Operation Troubleshooting

    Troubleshooting 9.4 Operation troubleshooting Operation troubleshooting Symptom Cause Action Display flashes LOE level or target is out of range check specifications • and status symbol check P006 • shows increase range extension P805 • Display flashes LOE material build-up on antenna clean antenna •...
  • Page 79 • ensure P820 is set to 12 (First echo) • nozzle too narrow for length shielded antenna required: discuss with your Siemens representative. internal seam in nozzle inspect and remove seam • use P837/P838 • longer shield required •...
  • Page 80: Technical Data

    Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. Note Operating temperature Check the ambient and operating temperatures under Construction (Page 82) and Approvals (Page 83).
  • Page 81: Performance

    Technical data 10.2 Performance 10.2 Performance Performance Reference operating conditions according to IEC 60770-1 Ambient temperature +15 to +25 °C (+59 to +77 °F) Humidity 45% to 75% relative humidity Ambient pressure 860 to 1060 mbar g (86000 to 106000 N/m Measurement Accuracy (measured in accordance with IEC 60770-1) From end of antenna to 600mm 40mm (1.57")
  • Page 82: Construction

    Technical data 10.3 Construction 10.3 Construction Process threaded connection 1.5” NPT, BSP, or G (BS EN ISO 228-1) connections Antenna polypropylene rod hermetically sealed construction standard 100 mm (4") shield for maximum 100 mm (4") nozzle, or optional 250 mm (10") long shield Note •...
  • Page 83: Approvals

    Technical data 10.6 Approvals 10.6 Approvals Note Conduit glands The use of approved watertight conduit hubs/glands is required for Type 4X, Type 6, IP67, IP68 (outdoor applications). General , CE, RCM Radio Europe (RED), FCC, Industry Canada Hazardous Intrinsic safety Europe ATEX II 1 G Ex ia IIC T4 Ga 06ATEX2354X...
  • Page 84: Dimension Drawing

    Dimension drawing 11.1 SITRANS Probe LR dimensions ① Std. 552 mm (21.7") min. option 702 mm (27.6") max. ② Std. 273 mm (10.8") min. option 423 mm (16.7") max. ③ 1/2" NPT thread (or M20 plastic strain relief) ④ Hinged lid ⑤...
  • Page 85 Dimension drawing 11.1 SITRANS Probe LR dimensions SITRANS Probe LR with mA/HART Operating Instructions, 05/2019, A5E32337711-AC...
  • Page 86: Technical Reference

    Technical reference Principles of operation SITRANS Probe LR is a sophisticated radar instrument that uses advanced microwave pulse technology to provide non-contacting continuous level measurement in liquids or slurries. Radar level measurement uses the time of flight principle to determine distance to a material surface.
  • Page 87: Near Blanking

    Technical reference A.3 Near blanking Typical receiver signal ① End of transmit ② P800 Near blanking ③ Distance from process empty level to reference point P006 ④ Empty level ⑤ Range extension (P801) as % P006 Near blanking Near Blanking programs SITRANS Probe LR to ignore the zone in front of the antenna.
  • Page 88: Range Extension

    Technical reference A.5 Range extension Range extension In applications where the base of the vessel is conical or parabolic, a reliable echo may be available below the vessel empty distance, due to an indirect reflection path. Increasing the range extension to 30% or 40% can provide stable empty vessel readings. Range extension is entered as a percentage of P006 (process empty level).
  • Page 89 Technical reference A.8 Auto false-echo suppression Display before Auto False-Echo Suppression (or when P837 = 0) ① Default TVT ② P839 Hover level Example After Auto False-Echo Suppression ① TVT curve (learned) ② False echo ③ Material level SITRANS Probe LR with mA/HART Operating Instructions, 05/2019, A5E32337711-AC...
  • Page 90: Output

    Technical reference A.9 Output Output The mA output is proportional to the level, in the range 4 to 20 mA. Generally, the output is set so that the output for 0% is 4 mA, and the output for 100% is 20 mA. 0 and 100% are percentages of the full-scale reading (m, cm, mm, ft, in).
  • Page 91: Failsafe

    Technical reference A.10 Failsafe A.10 Failsafe The Failsafe function can be activated either if there is not a valid measurement, or by one of the faults marked by an asterisk in the table General Fault Codes on page 84. In Failsafe mode, the device will output one of the four options determined by P071 (Failsafe Material Level).
  • Page 92: Hart Communication

    Description for the device in question. HART EDD’s are controlled by the HART Communication Foundation. Please contact your local Siemens representative concerning the availability of the HART EDD for SITRANS Probe LR. Older versions of the library will have to be updated in order to use all the features in the SITRANS Probe LR.
  • Page 93: Maintenance Settings (Accessible Via Pdm Only)

    HART communication B.4 Maintenance settings (accessible via PDM only) Maintenance settings (accessible via PDM only) Device lifetime Service interval • Total device operating time • Time elapsed since last service • Remaining device lifetime • Maintenance required limit • Maintenance required limit •...
  • Page 94: Application Examples

    Application examples Application examples introduction The application examples used in this manual illustrate typical installations using SITRANS Probe LR. Because there is often a range of ways to approach an application, other configurations may also apply. In all examples, substitute your own application details. If the examples do not apply to your application, check the applicable parameter reference for the available options.
  • Page 95 Application examples C.2 Example 1: Liquid resin in storage vessel, level measurement ① Reference point ② Span ③ 100% Level ④ 0% Level ⑤ Empty Parameter Description Value Function P001 Mode of measurement Level P003 Measurement response 1 m/minute P005 Units meters P006...
  • Page 96: Example 2: Horizontal Vessel With Volume Measurement

    Application examples C.3 Example 2: Horizontal vessel with volume measurement Example 2: Horizontal vessel with volume measurement Note • The minimum distance from the flange face to the target is limited by Near Blanking P800. • Only set P837 if the product is at least 2 m (78”) away from the flange face. If it is closer, leave P837 at 1 until the level drops and the distance increases beyond 2 m (78”).
  • Page 97 Application examples C.3 Example 2: Horizontal vessel with volume measurement Parameter Description Value Function P838 Auto False-Echo Sup- Distance Sets length of learned TVT curve to use pression Distance minus 0.5 m P837 Auto False-Echo Sup- 2, then 1 Enables the use of learned TVT curve pression Distance to product from reference point.
  • Page 98: Hazardous Area Installations

    Hazardous area installations Wiring details Intrinsically safe model FM (reference drawing A5E01003040) CSA (reference drawing A5E01003039) Under the entity evaluation concept, SITRANS Probe LR has the following characteristics: (input voltage) U = 30 V DC (max.) (input current) I = 120 mA DC (max.) (input power) Pi = 0.8 W (internal capacitance) C...
  • Page 99: Eu Equivalency

    Hazardous area installations D.3 EU equivalency ① Zone 0,1 or 2 Load 4-20 mA ② Certified barrier ③ PLC (active) ④ HART handheld communicator EU equivalency Any zener diode safety barrier, certified by an EU approved certification body to [ EEx ia ] IIC, its output voltage (U ) not exceeding 30 V and its output current (I ) limited by load...
  • Page 100: Loop Voltage Versus Loop Resistance

    Hazardous area installations D.4 Loop voltage versus loop resistance Loop voltage versus loop resistance IS safety barrier selection Selecting a suitable barrier or power supply requires knowledge about Intrinsic Safety and the application. It is the responsibility of the installer to ensure that the intrinsically safe installation complies with both the apparatus approval requirements and the relevant national code of practice.
  • Page 101 • The barriers listed below have all been tested and are functionally compatible with the SITRANS Probe LR. • The barriers listed below are all HART compatible. PLC Input Modules Manufacturer Part number Siemens SM331 PCS7 HART Input Module Passive shunt diode barriers Note A well-regulated supply voltage is required. Manufacturer...
  • Page 102: Instructions Specific To Hazardous Area Installations (Reference European Atex Directive 2014/34/Eu Annex Ii, 1/0/6)

    Hazardous area installations D.6 Instructions specific to hazardous area installations (reference European ATEX Directive 2014/34/EU Annex II, 1/0/6) Instructions specific to hazardous area installations (reference European ATEX Directive 2014/34/EU Annex II, 1/0/6) The following instructions apply to equipment covered by certificate number SIRA 06ATEX2354X: 1.
  • Page 103: Certificates And Support

    In addition to our documentation, Siemens provides a comprehensive support solution at: ● Partner (http://www.automation.siemens.com/partner) Personal contact If you have additional questions about the device, please contact your Siemens personal contact at: ● Support request (http://www.siemens.com/automation/support-request) To find the personal contact for your product, go to "All Products and Branches" and select "Products &...
  • Page 104: Glossary

    Glossary accuracy degree of conformity of a measure to a standard or a true value. algorithm a prescribed set of well-defined rules or processes for the solution of a problem in a finite number of steps. ambient temperature the temperature of the surrounding air that comes in contact with the enclosure of the device. antenna an aerial which sends out and receives a signal in a specific direction.
  • Page 105 Glossary confidence describes the quality of an echo. Higher values represent higher quality. Confidence threshold defines the minimum value. damping term applied to the performance of a device to denote the manner in which the measurement settles to its steady indication after a change in the value of the level. dB (decibel) a unit used to measure the amplitude of signals.
  • Page 106 Glossary Echo Processing the process by which the radar unit determines echoes. echo profile a graphical display of a processed echo. Echo Strength describes the strength of the selected echo in dB referred to 1 μV rms. electrical noise unwanted electrical signals that produce undesirable effects in the circuit or the control systems in which they occur.
  • Page 107 Glossary multiple echoes secondary echoes that appear as double, triple, or quadruple echoes in the distance from the target echo. Near Blanking see Blanking. nozzle a length of pipe mounted onto a vessel that supports the flange. parameters in programming, variables that are given constant values for specific purposes or processes. propagation factor (pf) where the maximum velocity is 1.0, pf is a value that represents a reduction in propagation velocity as a result of the wave travelling through a pipe or medium.
  • Page 108 Glossary relative permittivity see dielectric constant repeatability the closeness of agreement among repeated measurements of the same variable under the same conditions. stilling-well a pipe that is mounted inside a vessel, parallel to the vessel wall and open to the vessel at the bottom.
  • Page 109: Index

    Index Agitators, 61 Echo Algorithm confidence, 65 select for true echo, 65 strength, 65 Analog output verification, 44 in run mode, 90 Emission cone response rate, 86 illustration, 21 Application examples horizontal tank with volume, 96 liquid resin in storage vessel, 94 Approvals Failsafe specifications, 83...
  • Page 110 Index Lock value, 51 Scope of delivery, 8 Loss of echo, 87 Secondary index, 40 accessing, 41 changing a value, 41 Security unlocked value, 41 Manuals, 103 Service, 103 Master reset, 33, 71 Service & Support, 103 Material mixers, 61 Internet, 103 mounting SIMATIC PDM, 92...
  • Page 111 Index SITRANS Probe LR with mA/HART Operating Instructions, 05/2019, A5E32337711-AC...

This manual is also suitable for:

Sitrans lr7ml5430

Table of Contents