Download Print this page

Advertisement

Quick Links

Operating Instructions en
RDG2..KN – Room thermostat with KNX communications allowing users to set both ideal temperature
and relative humidity. The thermostat offers the operating modes Comfort, Economy and Protection.
In addition, it can operate in Auto mode as per a schedule via KNX bus.
The fan operates either in Auto mode or at the selected speed in Manual mode.
Users can either use the factory settings or adjust settings as desired.
Morning: 12-hour format (via bus);
Afternoon: 12-hour format (via bus)
Additional user information, such as outside
temperature, time of day from KNX bus, relative
humidity
Digits for room temperature and setpoint display
Operating mode button
Fan mode button
Rotary knob
Protection hospitality mode button
Changing the room temperature
Turn the rotary knob clockwise to increase, or counterclockwise to decrease the
current room temperature setpoint.
Note: The setting range is 5...40 °C; it can be limited by parameters P013 and P016.
(for parameter settings, see Control parameters on page 2).
Adjusting the fan speed
·
·
·
Speed
Speed
Speed
I
II
III
Changing the operating mode
1. Comfort mode
·
In Comfort mode, the thermostat maintains the room temperature at the setpoint
which can be adjusted with the rotary knob.
2. Economy mode
·
In Economy mode, the thermostat maintains the room temperature at a lower or
higher setpoint, thus saving energy and money.
·
The thermostat can be set to Economy mode either by pressing the operating
mode button if enabled (P002 = 2), or via an external signal (switch or KNX bus
command) such as keycard.
·
The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.
They can be adjusted via parameters P019 and P020 (for parameter settings, see
Control parameters on page 2).
3. Protection mode
·
In Protection mode, the thermostat stops operating. However, if the room
temperature drops below 8 °C, heating is switched on to protect the room against
frost.
·
The thermostat switches to Protection mode when the window contact (local or on
KNX) is activated.
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer: !
Heating protection: __________ ˚C
4. Auto mode
·
In Auto mode, the thermostat automatically switches over between Comfort and
Economy mode as per the KNX bus.
If no schedule is available, Comfort replaces Auto.
Important: If setpoints are set to Off, there is no protective heating or cooling function. Risk of frost!
Green leaf indication
The green leaf indication is an energy-efficient setting and indicates the end user settings.
Green leaf: Settings are within the
preset energy-efficient range.
Reminder to clean filter, display of external faults
This message reminds you to clean the filter on your HVAC equipment.
It appears after ! _______ "fan operating hours" and disappears when the thermostat is
FIL *
set to Protection.
AL1 *
These fault messages tell you an external fault has occurred *:
AL2 *
AL1 :! _______________________
AL3 *
AL3 :! _______________________
* Needs to be configured by HVAC installer
Button lock
·
·
Commissioning (by qualified HVAC installer)
To adapt the thermostat to your system and optimize control performance, a number of control
parameters can be adjusted. This can be done during operation, either via the buttons on the
thermostat or via a commissioning tool.
Main display
Operating mode selection
Fan speed selection
Escape
Confirm parameters
Outside temperature
Relative humidity
Degrees Celsius or Fahrenheit
Parameter
Green leaf
Press the right button repeatedly until the desired fan mode is reached.
In Auto mode
, the fan speed is automatically selected by the thermostat
depending on setpoint and current room temperature.
In Manual mode, the fan operates independently and runs at the speed set by
the user: speed I / speed II / speed III.
If the button lock function is enabled (parameter P028 = 2), pressing the right
button for 3 seconds locks or unlocks the buttons respectively.
Locked buttons are indicated by the key symbol
If "Auto lock" is configured (P028 = 1), the thermostat automatically locks the
buttons 10 seconds after the last adjustment.
Frost protection: _________ ˚C
Red leaf: Settings exceed the preset
energy-efficient range.
End users can press the red leaf and
return to the energy-efficient range.
AL2 :! __________________________
RDG200KN
RDG260KN
Operating mode
Protection mode
Economy mode
Comfort mode
Cooling mode
Electric heater active
Heating mode
Manual changeover
Auto mode
Temporary timer
Fault
Button lock
Condensation in room
(dewpoint sensor active) or
humidity control active
Automatic fan
Fan speed I
Fan Speed II
Fan Speed III
.

Advertisement

loading

Summary of Contents for Siemens RDG2 KN Series

  • Page 1 RDG200KN Operating Instructions en RDG260KN RDG2..KN – Room thermostat with KNX communications allowing users to set both ideal temperature and relative humidity. The thermostat offers the operating modes Comfort, Economy and Protection. In addition, it can operate in Auto mode as per a schedule via KNX bus. The fan operates either in Auto mode or at the selected speed in Manual mode.
  • Page 2 *** Parameter P027 is displayed only for application 2-pipe with electric heater. All temperature settings are in increments of 0.5 °C. ! Remember to record all changes! Issued by © Siemens Switzerland Ltd, 2020 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure...

This manual is also suitable for:

Rdg200knRdg260kn