INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
SINGLE PACKAGE TYPE AIR CONDITIONER
P/NO : MFL67445803
Copyright © 2012 - 2018 LG Electronics Inc. All Rights Reserved.
www.lg.com

Advertisement

Table of Contents
loading

Summary of Contents for LG AK-Q240BC01

  • Page 1 Installation work must be performed in accordance with the national wiring standards by authorized personnel only. Please retain this installation manual for future reference after reading it thoroughly. SINGLE PACKAGE TYPE AIR CONDITIONER www.lg.com P/NO : MFL67445803 Copyright © 2012 - 2018 LG Electronics Inc. All Rights Reserved.
  • Page 2 TIPS FOR SAVING ENERGY TIPS FOR SAVING ENERGY Here are some tips that will help you minimize the power consumption when you use the air conditioner. You can use your air conditioner more efficiently by referring to the instructions below: •...
  • Page 3: Important Safety Instructions

    IMPORTANT SAFETY INSTRUCTIONS IMPORTANT SAFETY INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE INSTALLING THE APPLIANCE. Always comply with the following precautions to avoid dangerous situations and ensure peak performance of your product. WARNING It can result in serious injury or death when the directions are ignored. CAUTION It can result in minor injury or product damage when the directions are ignored.
  • Page 4 IMPORTANT SAFETY INSTRUCTIONS • Be sure the installation area does not deteriorate with age. - If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury. • Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and Do not use Flammable gases.
  • Page 5 IMPORTANT SAFETY INSTRUCTIONS • Take care to ensure that nobody could step on or fall onto the unit. - This could result in personal injury and product damage. CAUTION Installation • Always check for gas (refrigerant) pressure after installation or repair of product. - Low refrigerant levels may cause failure of product.
  • Page 6: Table Of Contents

    TABLE OF CONTENTS TABLE OF CONTENTS TIPS FOR SAVING ENERGY IMPORTANT SAFETY INSTRUCTIONS INTRODUCTION Features (10 / 12.5 / 15 RT) Features (20 / 23 / 25 RT) DIMENSIONAL DATA(10 / 12.5 / 15 RT) DIMENSIONAL DATA(20 / 23 / 25 RT) INSTALLATION OF UNIT Inspection Location and Recommendations...
  • Page 7: Introduction

    INTRODUCTION INTRODUCTION Features (10 / 12.5 / 15 RT) Front View Air outlet vents Return Drain Hole Motor Access Panel Supply Air outlet Rear View vents Control access panel Compressor Air intake vents access panel...
  • Page 8: Features (20 / 23 / 25 Rt)

    INTRODUCTION Features (20 / 23 / 25 RT) Front View Air outlet vents Return Drain Hole Motor Access Panel Supply Rear View Air outlet vents Control access panel Compressor access panel Air intake vents...
  • Page 9: Dimensional Data(10 / 12.5 / 15 Rt)

    DIMENSIONAL DATA DIMENSIONAL DATA (10 / 12.5 / 15 RT) Single packaged cooling Units are designed CLEARANCE 1 160mm CLEARANCE 860mm for outdoor mounting with vertical condenser discharge. They can be located either at ground level or on roof. Each unit contains an operating charge of Refrigerant as shipped.
  • Page 10: Dimensional Data(20 / 23 / 25 Rt)

    DIMENSIONAL DATA DIMENSIONAL DATA (20 / 23 / 25 RT) Single packaged cooling Units are designed CLEARANCE 860mm CLEARANCE 1 160mm for outdoor mounting with vertical condenser discharge. They can be located either at ground level or on roof. Each unit contains an operating charge of Refrigerant as shipped.
  • Page 11: Installation Of Unit

    INSTALLATION OF UNIT INSTALLATION OF UNIT Inspection Lifting Beam Recommended Check for damage after unit is unloaded. Rigging Method Report promptly, to the carrier, any damage found to unit. Do not drop unit. Spreader Bar Check the unit nameplate to determine if the unit voltage is correct for the application.
  • Page 12: Ductwork

    INSTALLATION OF UNIT Ductwork Change Airflow Horizontal flow to Down flow Conversion Ductwork construction guidelines Remove the covers from the down flow Connections to the unit should be made with openings on the base panel by unscrewing 76mm(3’) canvas connectors to minimize as shown.
  • Page 13: Condensate Drain Piping

    INSTALLATION OF UNIT Condensate Drain Piping Down flow filter bracket installation guide A 1 inch female condensate drain connection is located on the corner of the unit next to the Use a screw to connect the product to motor access panel. A trap should be installed Bracket_1.
  • Page 14 INSTALLATION OF UNIT Fit the filter. TOP View Filter Use a screw to connect the Bracket_2 to Bracket_3. TOP View Bracket_3 Bracket_2...
  • Page 15: Installation Of Remote Controller(Accessory)

    INSTALLATION OF UNIT Installation of Remote <20 / 23 / 25 RT> Controller(Accessory) Please insert wired remote controller connection cable to the CN-REMO in indoor PCB, or connect directly local connection cable to terminal block in control box. - It should be use supplied local connection cable permitted in each national standard.
  • Page 16 INSTALLATION OF UNIT Please fix tightly using provided screw Please fix remote controller upper part into after placing remote controller setup board the setup board attached to the surface of on the place where you like to setup. the wall, as the picture below, and then, connect with setup board by pressing - Please set it up not to bend because poor lower part.
  • Page 17 INSTALLATION OF UNIT Please connect indoor unit and remote controller using connection cable. Please check if connector is normally connected. Product side Connecting cable <Meaning of wire color> Signal Yellow Black Please use extension cable if the distance between wired remote controller and the product is more than 10m(32.8ft).
  • Page 18 INSTALLATION OF UNIT Wired remote controller installation - Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
  • Page 19: Electronic Wiring

    INSTALLATION OF UNIT Electronic Wiring CAUTION Follow ordinance of your governmental • Provide a circuit breaker between power organization for technical standard related to source and the unit as shown below. electrical equipment, wiring regulations and guidance of each electric power company. Main power source WARNING •...
  • Page 20: Field Wiring

    INSTALLATION OF UNIT Field Wiring 10/12.5/15 RT – 220 V 3~ 60 Hz Power supply 3 Phase 3 Wires 60Hz 220V (Main Switch) R(L1) S(L2) T(L3) Switch ELCB Power Line (3 Wires Cable) CAUTION • Unit ground Lines are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
  • Page 21 INSTALLATION OF UNIT 15RT - 460 V 3~ 60 Hz Power supply 3 Phase 3 Wires 60Hz 460V (Main Switch) R(L1) S(L2) T(L3) Switch ELCB Power Line (3 Wires Cable) CAUTION • Unit ground Lines are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
  • Page 22 INSTALLATION OF UNIT 20/23/25 RT – 220 V 3~ 60 Hz - When the power source is supplied to Each outdoor unit individually. (Main Switch) Power supply 3 Phase 3 Wires 60Hz 220V R(L1) S(L2) T(L3) Switch ELCB Power Line (3 Wires Cable) CAUTION •...
  • Page 23 INSTALLATION OF UNIT 20/25 RT – 460 V 3~ 60 Hz (Main Switch) Power supply 3 Phase 3 Wires 60Hz 460V R(L1) S(L2) T(L3) Switch ELCB Power Line (3 Wires Cable) CAUTION • Unit ground Lines are required for preventing electrical shock accident during current leakage, Communication disorder by noise effect and motor current leakage (without connection to pipe).
  • Page 24: Connect The Cable To The Product

    INSTALLATION OF UNIT Connect the cable to the Product Remove the cover control from the unit by loosening the screw. Connect the wires to the terminals on the control board individually as the following. Secure the cable onto the control board with the holder (clamper). Refix the cover control to the original position with the screw.
  • Page 25 INSTALLATION OF UNIT 10/12.5/15 RT 20/23/25 RT Conduit panel Conduit panel Lock nut Lock nut Conduit Conduit WARNING • Ground Lines to the product are required for preventing electrical shock accident during current leakage, Transmission disorder by noise effect and motor current leakage (without connection to pipe).
  • Page 26: Dip Switch Setting In Indoor Main Pcb

    INSTALLATION OF UNIT Dip Switch Setting in Indoor Main PCB Function Description Setting "Off" Setting "On" Default Selection of Master or Group Control Master Slave Slave Selection of Dry Contact Dry Contact Mode Variable Auto Mode Return Air Sensor Installed Sensor or Not Not installed Installed Installed CTI or not...
  • Page 27: Evaporator Fan Adjustment

    INSTALLATION OF UNIT Evaporator Fan Adjustment Use the following procedure to determine the proper adjustment of the evaporator fan for a specific application. Determine total system external static pressure (In mm water column) with accessories installed. to accomplish this: 1) Obtain the design airflow rate and the design external static pressure drop through the distribution system.
  • Page 28: Trial Run Mode

    INSTALLATION OF UNIT To Increase Belt Tension Loosen adjustment nut(4places). Pull motor back until belt is tight. Tighten adjustment bolt after belt has correct tension. FORCE(F) HEIGHT(S) REMARK 2.5(kgf) 8~11mm 1.5(kgf) 7~9 mm Trial Run Mode After installing the product, you must run a Test Run mode. For details related to this operation, refer to the product manual.
  • Page 29: Self-Diagnosis Function

    INSTALLATION OF UNIT Self-Diagnosis Function Error Indicator - This function indicates types of failure in self-diagnosis and occurrence of failure for air condition. - Error mark is displayed on wired remote controller, and 7-segment LED of outdoor unit control board as shown in the table.
  • Page 30 INSTALLATION OF UNIT Display Title Cause of Error Master Inverter Compressor High System is turned off by Master Inverter Compressor Discharge Temperature High Discharge Temperature Slave Inverter Compressor High Discharge System is turned off by Slave Inverter Compressor High Temperature (For 20/23/25RT Only) Discharge Temperature Master Constant Speed Compressor1 System is turned off by Master Constant Speed...
  • Page 31 INSTALLATION OF UNIT Display Title Cause of Error Master Outdoor Unit Faulty IPM Master Outdoor Unit IPM Temperature Sensor Temperature Sensor short/open Slave Outdoor Unit Faulty IPM Slave Outdoor Unit IPM Temperature Sensor short/open Temperature Sensor Omitting connection of R, S, T power of Omitting connection of Master Master Omitting connection of R, S, T power of...
  • Page 32 INSTALLATION OF UNIT Display Title Cause of Error 1 Master Fan CT Sensor Error Master Fan CT Sensor open or short Slave Fan CT Sensor Error (For Slave Fan CT Sensor open or short 20/23/25RT Only) Master Fan DC Link High Voltage Error Master Fan Current is abnormal 2 Slave Fan DC Link High Voltage Error Slave Fan Current is abnormal...
  • Page 33 INSTALLATION OF UNIT Display Title Cause of Error Communication Error between Master Failing to receive Slave signal at main PCB of and Slave (For 20/23/25RT Only) 1 0 4 2 Master 1 Master Fan PCB Communication Error Failing to receive fan signal at main PCB of unit. 1 0 5 Slave Fan PCB Communication Failing to receive fan signal at main PCB of unit.
  • Page 34: Starting The Unit

    INSTALLATION OF UNIT Starting the Unit Voltage With the compressor operating, check the line Heating Mode voltage at the unit. The voltage should be within the range shown on the unit (If unit is equipped with electric heater.) nameplate. If low voltage is encountered, Check to ensure all grilles and registers are check the size and length of the supply line open and all unit access doors are closed...
  • Page 35: Final Installation Checklist And Maintenance

    INSTALLATION OF UNIT Final Installation Checklist and Maintenance - Is the condenser fan and indoor blower operating correctly, with proper rotation and without undue noise? - Have voltage and running currents been checked to determine if it is within limits? - Have the air discharge grilles been adjusted to balance the system? - Has the ductwork been checked for air leaks and condensation? - Has the indoor airflow been checked and adjusted if necessary?
  • Page 36 INSTALLATION OF UNIT Maintenance Performed by Serviceman-Cooling Season To keep your unit operating safely and efficiently, the manufacturer recommends that a qualified serviceman check the entire system at least once each year, or more frequently if conditions warrant. Your serviceman may examine these areas of your unit: ‘...
  • Page 37: Installation Guide At The Seaside

    Install the outdoor unit on - If you can’t meet above guide line in the the opposite side of the sea wind direction. seaside installation, please contact LG Electronics for the additional anticorrosion. - Periodic ( more than once/year ) cleaning...
  • Page 38 INSTALLATION OF UNIT...