Oil Supply - Bosch 12/18 Instruction Manual

Floor standing external oil fired condensing combination boiler using balanced flue system
Table of Contents

Advertisement

A
- Oil storage tank
B
- Isolating valve
C
- Oil strainer & water seperator
D
- Fire valve to BS5410
E
- External casing
F
- Fire valve sensor
G
- Oil burner
NOTE: All dimensions are in metres unless stated otherwise.
The maximum pipe run figures are based on using copper pipe with an inside diameter of
2mm less than the Ø.
a)
K
MAXIMUM PIPE RUN FOR SINGLE PIPE GRAVITY FEED SYSTEM
HEAD
10mmØ
12mmØ
0.5
12
30
1.0
25
69
1.5
37
91
2.0
49
100
b)
150mm
MAXIMUM PIPE RUN FOR DOUBLE PIPE SUB-GRAVITY FEED SYSTEM
HEAD
10mmØ
12mmØ
0
50
100
0.5
44
100
1.0
38
95
1.5
32
80
c)
MAXIMUM PIPE RUN FOR SINGLE PIPE SUCTION LIFT WITH DE-AERATOR
FUEL FLOW RATE
HEAD
2.5kg/h
5kg/h
8mmØ
8mmØ 8mmØ 10mmØ
0
100
55
0.5
95
45
1.0
80
40
1.5
70
35
The table and illustration above is a guide only and does not in any way override the de-
aerator manufacturers instructions.
9

OIL SUPPLY

H
- Oil supply pipe
J
- Oil pump
K
- Full base (plastic tanks)
L
- Non-return valve
M
- De-aerator
N
- Oil filter (16µm max filtration size)
A
B C
H
B D
HEAD
10mmØ
2.5
62
3.0
74
3.5
87
4.0
99
B
D
L
A
B
C
L
H
K
HEAD
10mmØ
2.0
26
2.5
20
3.0
14
3.5
8
M
A
B
C
H
B
D
K
HEAD
2.5kg/h
10kg/h
10kg/h
8mmØ
26
100
2.0
60
2.5
45
23
100
20
90
3.0
35
17
75
3.5
25
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR HEATSLAVE EXTERNAL 12/18-18/25-25/32
OIL SUPPLY
This appliance is suitable for kerosene (28
second oil) only, no other fuel must be used.
OIL SUPPLY:
• Plastic or steel tanks should be installed to
• Do not use galvanised steel tanks or
• Do not use soldered joints on the oil
a) Single pipe gravity feed system:
The oil storage tank (A) must be positioned so
F
that the oil level does not exceed 4 metres above
the level of the burner oil pump (J) and in addi-
tion the oil level must be at least 300mm above
the oil pump (J). Where the maximum oil level in
the oil storage tank exceeds 4 metres, a head
breaking device must be installed between the
B N G
J
tank (A) and the burner oil pump (J).
b) Double pipe sub-gravity feed system:
E
12mmØ
Maximum suction height 3.5 metres. Non-return
100
valves must be fitted to the inlet and return oil
100
line between the oil pump (J) and oil storage
100
tank (A).
100
c) Single pipe suction lift with de-aerator
Maximum suction height 3.5 metres. The oil
tank (A) must be positioned below the oil pump
(J). Create an inlet and return loop between the
F G
de-aerator (M) and oil pump (J).
A non-return valve must be incorporated within
the de-aerator or fitted to the oil line between
the oil storage tank (A) and the de-aerator (M).
A top feed oil tank fitted with a de-aerator
J
B
N
using an internal non-return valve should have
any non-return valves fitted in the base of the
tank to the suction line removed to assist
E
purging air from the oil line.
Pipework
12mmØ
66
50
37
22
F
G
J
E
FUEL FLOW RATE
5kg/h
10kg/h
10kg/h
8mmØ 8mmØ 10mmØ
30
14
65
25
11
50
15
8
35
10
5
20
BS 5410. A steel tank should conform to
BS 799: part 5 and have a slope of 1 in 24
away from the outlet valve with a sludge cock
at its lower end.
pipework for the oil supply system.
supply pipework.
Use copper pipe of the correct diameter
according to the information shown opposite.
Use flexible hoses to connect to the oil pump (J).
Lay the oil supply pipe (H) as straight and
level as possible to avoid air pockets and
unnecessary friction losses. Route away
from the boiler access door or other hot
surfaces.
Install a manual isolating valve (B) to the oil
supply pipe (H), as close to the oil storage
tank (A) as possible.
Fit an oil strainer and water seperator (C) to
the oil supply pipe, near the oil storage tank.
Fit an additional oil filter (N, 16µm max
filtration size) close to the boiler, but not
inside the boiler casing.
Fit a fire valve in accordance with BS 5410.
The fire valve (D) must be fitted externally
at least 1 metre from the appliance with the
fire valve sensor (F) located within the
appliance case.
A capillary type valve provides a neat and
simple installation. Alternatively, a fusible
link or electrical system may be used.
Under no circumstances should a
combination isolating/fire valve be used
as the sole fire protection device.