Download Print this page
Siemens SENTRON SUPERSWITCH 3KL83 Series Operating Instructions Manual

Siemens SENTRON SUPERSWITCH 3KL83 Series Operating Instructions Manual

Switch disconnector fuse - size 3

Advertisement

Quick Links

SENTRON SUPERSWITCH
Switch Disconnector Fuse - Size 3
3KL83...-.. (200A-400A)
3KA83...-.. (200A-400A)
Required tools
2.5 mm
13 mm
16 mm
Contents
Assembly
Mounting Details:
1 mm
3
0.5 x 3 mm
PZ 5
2P: 2x
3P: 3x
4P: 4x
2P/3P/4P : M8 x 20 (4x)
Torque 10....14 Nm
(Not in scope of supply)
EN
Hazardous voltage will cause death or serious injury. Turn off and
lock out all power supplying this device before working on this device.
Replace all covers before power supplying this device is turned on.
Installation & Maintenace must be carried out by qualified personnel.
1x
3K.83..-5
M10X30
For 3KL8
Permissible mounting position
IEC 60947-1
IEC 60947-3
DANGER
!
NOTICE
1x
2P: 4x
3P: 6x
4P: 8x
3K.83..M10X30
15
A
M8 (4x)
Center of
Shaft
Drilling Plan for mounting plate
L1V30606645003-01 | 01

Advertisement

loading

Summary of Contents for Siemens SENTRON SUPERSWITCH 3KL83 Series

  • Page 1 SENTRON SUPERSWITCH Switch Disconnector Fuse - Size 3 3KL83...-.. (200A-400A) IEC 60947-1 3KA83...-.. (200A-400A) IEC 60947-3 DANGER Hazardous voltage will cause death or serious injury. Turn off and lock out all power supplying this device before working on this device. Replace all covers before power supplying this device is turned on.
  • Page 2 Connection 3KL831.../3KA831..3KL8322.../3KA822..Max. Lug Size..2X120 mm M10 x 30 1 mm Torque 20 Nm to 28 Nm 1 mm 3KL83...5.../3KA83..5_Netrual Link Max. Lug Size..120 mm M10 x 30 Torque 10 Nm to 28 Nm Provision for Fuse monitoring Assembly Installation of Shaft 2.5 mm...
  • Page 3 Assembly Mounting Details for Front Drive 8UC6314-1BB00 2.5 mm 285...310 Panel Door 1.5..4Thk Coupler PZ 5 PZ5 x 13.5 2.1...2.4Nm 45.5 1 8UC Coupler depth adjustment Use Depth Setting Templet - 8UC6046-2 Adjust Depth of Drive as per dimensional plan Assembly Phase Barrier: 3KX83430AE...
  • Page 4: Terminal Cover

    Assembly Terminal cover 2P : 3KX83410AF 3P : 3KX83410AE 4P : 3KX83410AG 0.5 x 3 mm Rear cover 2P : 3KX83460AF 3P : 3KX83460AE 4P : 3KX83460AG Rear Phase Barrier Kit 2P/3P/4P : 3KX83469AE 0.5 x 3 mm L1V30606645003-01 | 04...
  • Page 5 Assembly Fuse Cover: 2P:3KX83400AF 3P:3KX83400AE 4P:3KX83400AG Fuse Cover Phase Barrier Kit 3KX83409AE 0.5 x 3 mm 2P/3P/4P : Replace phase barrier in position 1 with Fuse Cover Phase Barrier 2P : Add Fuse Cover Phase Barrier in position 3 3P : Add Fuse Cover Phase Barrier in position 4 4P : Add Fuse Cover Phase Barrier in position 5 Assembly Mounting Aux.
  • Page 6 Information Dimension Details for SDF in Enclosure Information Overall Dimensional details 3KL8/3KA8 : 3P(3KL8)/3P+N 13.2 287...313 3 THICK 32.5 INTERLOCKING LEVER AUXLIARY SWITCH OFF POSITION FUSE PHASE 55.2 INDICATOR NEUTRAL TERMINAL COVER BARRIER LINK TERMINAL COVER 3KL8/3KA8 : 2P 3KL8/3KA8 : 4P For missing Dimension refer 3P/3P+N For missing Dimension refer 3P/3P+N L1V30606645003-01 | 06...

This manual is also suitable for:

Sentron superswitch 3ka83 series