General Information - LG THERMA V HA031M E1 Installation Manual

Backup heater
Hide thumbs Also See for THERMA V HA031M E1:
Table of Contents

Advertisement

1,MFL68681815,영어 2018. 9. 22. 오전 8:26 페이지 8
INSTALLATION METHOD
8
CAUTION
!
• Electric Heater has to be installed vertically like the below figure.
WARNING
!
Followings should be kept before installation.
• Main power must be turned off during installing 3rd party accessories.
• 3rd party accessories should be comply with supported specification.
• Proper tools should be chosen for installation.
• Never do installation with wet hands.

General Information

Electric Heater is supported by LG Electronics.
Electric Heater is installed on the outside of the unit. It is recommended to install it in the indoor.
1
Description
No
Name
1
Leaving Water Pipe
2
Entering Water Pipe
3
Control Box
4
Thermal switch
5
Air vent
6
Electric Heater
Capacity (kW)
3
6
3
2
Male PT 1 inch
Male PT 1 inch
Terminal blocks, Magnetic switch, Circuit breaker
Cut-off power input to electric heater at 90 °C (manual return at 55°C )
Air purging when charging water
Power Source
50 Hz 220-240 V~
50 Hz 220-240 V~
4
Remark
5
6