Fujitsu ETERNUS DX8100 S3 Site Planning Manual

Hybrid
Hide thumbs Also See for ETERNUS DX8100 S3:
Table of Contents

Advertisement

Quick Links

P3AM-9422-13ENZ0
FUJITSU Storage
ETERNUS DX8100 S3/DX8700 S3/DX8900 S3
Hybrid Storage Systems
Site Planning Guide
Requirements for transportation/installation

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu ETERNUS DX8100 S3

  • Page 1 P3AM-9422-13ENZ0 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Requirements for transportation/installation...
  • Page 2: Table Of Contents

    Power Cord Connection ............................54 Frontend Cable Connection ...........................58 Backend Cable Connection ............................74 Installable Racks ........................... 78 Fujitsu Racks .................................78 Non-Fujitsu Racks ..............................78 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 3 Frontend Cable Connection ........................58 Figure 39 Frontend Cable Connection Example (When Connecting Two DEs for Each Node in a 19-inch Rack [2000mm]) ..............................60 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 4 Backend Cable Connection Example (When Installing 16 DEs for Each Node Connected between Multiple Racks) ..............................77 Figure 54 Unit Installation Area ..........................79 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 5 Required Cable Length/Quantity (When Connecting 15 to 16 DEs per Node) ...........73 Table 32 Backend Cable Connection Usage......................74 Table 33 Specifications for the Unit Installation Area .....................79 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 6 Preface Fujitsu would like to thank you for purchasing the FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 (hereinafter referred to as ETERNUS DX). The ETERNUS DX is designed to be connected to Fujitsu servers (Fujitsu SPARC Servers, PRIMEQUEST, PRIMERGY, GS21 series, and other servers) or non-Fujitsu servers.
  • Page 7 Indicates information that you need to observe when using the ETERNUS storage system. Make sure to read the information. Indicates information and suggestions that supplement the descriptions included in this manual. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 8 - Be careful that no liquid seeps into the ETERNUS storage system when using cleaners, etc. - Do not use alcohol or other solvents to clean the ETERNUS storage system. Warning layout ribbon FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 9 Mainframe connections are not supported. • • GS racks are not supported. The power distribution units described in this manual are not available. • FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 10: Eternus Dx Installation

    1,300kJ/h Maximum Controller enclosure 6.2m /min amount of ex- Drive enclosure (*4) 2.5" type 4.0m /min haust air 3.5" type 4.0m /min FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 11 *5: These values are measured when a single controller enclosure and four drive enclosures are configured in an environment in which the temperature is 23 ± 2°C at 0 meters above sea level. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED...
  • Page 12: Eternus Dx8700 S3

    Maximum amount of ex- Frontend enclosure 7.0m /min haust air Controller enclosure 6.2m /min Drive enclosure (*5) 2.5" type 4.0m /min 3.5" type 4.0m /min FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 13 *6: These values are measured when a single frontend enclosure, two controller enclosures, and four drive en- closures are configured in an environment in which the temperature is 23 ± 2 °C at 0 meters above sea level. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 14: Eternus Dx8900 S3

    Maximum amount of ex- Frontend enclosure 7.0m /min haust air Controller enclosure 6.2m /min Drive enclosure (*5) 2.5" type 4.0m /min 3.5" type 4.0m /min FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 15 *6: These values are measured when a single frontend enclosure, two controller enclosures, and four drive en- closures are configured in an environment in which the temperature is 23 ± 2 °C at 0 meters above sea level. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 16: 19-Inch Racks

    Dimensions (W ´ D ´ H) 700 ´ 1,050 ´ 1,400mm Maximum weight 108kg Service area Refer to Figure 12 "Installation Area" (page 29). Number of units FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 17: Table 7 19-Inch Rack (For Gs21 1600/1400, 1800Mm) Installation Specifications

    700 ´ 1,110 ´ 1,800mm Maximum weight 144kg 120kg Service area Refer to Figure 13 "Installation Area" (page 29). Number of units FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 18: Storage System Dimensions

    The following diagrams show the dimensions of a frontend enclosure. The dimension values do not include any protruding parts (approximation). Figure 1 Frontend Enclosure Dimensions Side 482mm FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 19: Figure 2 Controller Enclosure Dimensions

    The following diagrams show the dimensions of a controller enclosure. The dimension values do not include any protruding parts (approximation). Figure 2 Controller Enclosure Dimensions Side 482mm Front FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 20: Figure 3 2.5" Type Drive Enclosure Dimensions

    The diagrams below show the dimensions of a 2.5" type drive enclosure. The dimension values do not include any protruding parts (approximation). Figure 3 2.5" Type Drive Enclosure Dimensions Side 482mm Front FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 21: Rack Dimensions

    Rack Dimensions The following diagrams show the dimensions of a 19-inch rack. The dimension values do not include any pro- truding parts (approximation). FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 22: Figure 5 19-Inch Rack (With Standard Door, 2000Mm) Dimensions

    Figure 15 under "Installation Methods" (page 33). Figure 5 19-inch Rack (with Standard Door, 2000mm) Dimensions 700mm 1,050mm Front Side Rear Bottom FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 23: Figure 6 19-Inch Rack (With A Dx8000 Series Dedicated Door, 2000Mm) Dimensions

    "Installation Methods" (page 33). Figure 6 19-inch Rack (with a DX8000 Series Dedicated Door, 2000mm) Dimensions 700mm 1,090mm Front Rear Side Bottom FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 24: Figure 7 19-Inch Rack (For Gs, 1400Mm) Dimensions

    For specification information that is required for securing a rack, refer to Figure 17 under "Installation Methods" (page 33). Figure 7 19-inch Rack (for GS, 1400mm) Dimensions 700mm 1,050mm Front Side Rear Bottom FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 25: Figure 8 19-Inch Rack (For Gs21 1600/1400, 1800Mm) Dimensions

    Figure 18 under "Installation Methods" (page 33). Figure 8 19-inch Rack (for GS21 1600/1400, 1800mm) Dimensions 700mm 1,050mm Front Side Rear Bottom FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 26: Figure 9 19-Inch Rack (For Gs21 2600/2400, 1800Mm) Dimensions

    Figure 19 under "Installation Methods" (page 33). Figure 9 19-inch Rack (for GS21 2600/2400, 1800mm) Dimensions 700mm 1,110mm Front Side Rear Bottom FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 27: Compliance Standards

    Environmental compliance • RoHS-compliant (Restriction of hazardous substances) 2011/65/EU WEEE-compliant (Waste electrical and electronic equipment) ® • 80PLUS GOLD (power conversion efficiency) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 28: Package Size

    *4: These values are for product ID ETSPDHU / ETSPDHU-L. *5: These values are for product ID ETSPDJU / ETSPDJU-L. *6: These values are for product ID ETSPDVU / ETSPDVU-L. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 29: Installation Area

    (Rear door) 1,090mm 1,013mm ETERNUS DX 80mm or more (*1) 59mm (Front door) 59mm or more (*1) Front service area 850mm or more FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 30: Figure 12 Installation Area And Service Area Of A 19-Inch Rack (For Gs, 1400Mm) And A 19-Inch Rack (For Gs21

    (Rear door) 1,110mm 1,013mm ETERNUS DX 80mm or more (*1) (Front door) 79mm 79mm or more (*1) Front service area 850mm or more FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 31: Figure 14 Example Of Fujitsu 19-Inch Racks Placed Side By Side

    (with standard door) Alignment with the front rack frame 19-inch rack 19-inch rack (for GS21 2600/2400) (with standard door) Alignment with the front doors FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 32: Installation Environment

    Estimate the amount of heat in the exhaust air from the ETERNUS DX by using the heat generation amount and exhaust air amount that are listed in "Installation Specifications" (page 10). FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 33: Installation Methods

    Figure 15 Floor Dimensions of the Rack (of 19-inch Racks (with Standard Door, 2000mm)) 47mm 919mm (leveling feet) 140mm 733mm (caster) 826mm Front Rear 1,013mm 95mm 1,050mm Caster Leveling feet Cable slot FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 34: Figure 16 Floor Dimensions Of The Rack (Of 19-Inch Racks (With A Dx8000 Series Dedicated Door, 2000Mm))

    Figure 16 Floor Dimensions of the Rack (of 19-inch Racks (with a DX8000 Series Dedicated Door, 2000mm)) 47mm 919mm (leveling feet) 140mm 733mm (caster) 826mm Rear Front 95mm 1,013mm 1,090mm Caster Leveling feet Cable slot FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 35: Figure 17 Floor Dimensions Of The Rack (Of 19-Inch Racks (For Gs, 1400Mm))

    33mm 906mm (leveling feet) 124mm 724mm (caster) 925mm Front Rear 50 mm 5 0 mm 975mm 1,050mm Caster Leveling feet Cable slot FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 36: Figure 18 Floor Dimensions Of The Rack (Of 19-Inch Racks (For Gs21 1600/1400, 1800Mm))

    33mm 906mm (leveling feet) 124mm 724mm (caster) 925mm Front Rear 50 mm 5 0 mm 975mm 1,050mm Caster Leveling feet Cable slot FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 37: Load Bearing Capacity For Floors

    If the condition above is not satisfied, additional measures are required to ensure sufficient load bearing capaci- Contact your installation contractor for details about the necessary measures that must be taken. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED...
  • Page 38: Outlet/Socket Specifications

    "Power Cord Connection" (page 54). • AC100V connections or AC200V connections can be selected for the ETERNUS DX8100 S3. Only AC200V connections can be selected for the ETERNUS DX8700 S3/DX8900 S3. • FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide...
  • Page 39: Specifications For Optional Power Supply Products

    NEMA L6-15P NEMA L6-15R 4.0m Rating: 250V 10A tween the ETERNUS DX (Normal usage rating: and the socket (IEC60320 C13 n NEMA L6-15P) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 40: Table 13 Specifications For Ac100V And Ac200V Power Cords

    0.5m Rating: 250V 10A tween the ETERNUS DX 1.0m (Normal usage rating: and the socket 1.5m (IEC60320 C13 n 3.0m IEC60320 C14) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 41: Figure 20 Power Distribution Unit (Ac200V, Horizontal Type)

    Plug type Cable length (Socket) (Socket) IEC60320 C13 NEMA L6-30P NEMA L6-30R 4.0m Rating: 250V 30A (Normal usage rating: 24A [12A ´ 2]) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 42: Figure 22 Power Distribution Units (Ac200V, Vertical Type)

    Socket type rating Plug type Cable length (Socket) (Socket) IEC60320 C13 NEMA L6-30P NEMA L6-30R 4.0m Rating: 250V 30A (Normal usage rating: 24A) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 43: Required Number Of Outlets/Sockets

    Power distribution unit (AC200-240V, vertical type) AC 200 – 240V — ETERNUS DX (without power distribution units) AC 100 – 120V AC 200 – 240V FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 44: Figure 23 Breaking Characteristics Of Distribution Board Circuit Protectors

    Figure 23 Breaking Characteristics of Distribution Board Circuit Protectors 0.06 0.04 0.02 0.01 1.5 2 6 7 8 15 20 80 100 Current (ratio for the current rating) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 45: Figure 24 Example Of A Power Supply Connection When A Power Distribution Unit (Ac200-240V, Horizontal Type) Is

    Line 1 Distribution Distribution board board ↓ To power supply facility ↓ To power supply facility PSU: Power Supply Unit Circuit Protector FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 46: Figure 25 Example Of A Power Supply Connection When A Power Distribution Unit Is Not Used

    Frontend enclosure Line 0 Line 1 PSU: Power Supply Unit Circuit Protector Only connect the ETERNUS DX to circuit protectors. • FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 47: Input Power Supply Lines

    Power distribution unit ETERNUS DX Power distribution unit Drive enclosure Controller enclosure Line 0 Line 1 Frontend enclosure FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 48: Rack Installation Specifications

    (horizontal type) must be selected. ■ Installation Example (ETERNUS DX8100 S3) The following figures show examples of when the ETERNUS DX8100 S3 is installed in a 19-inch rack. The power control device SCCI/PPC is provided with a 2m cable. •...
  • Page 49: Figure 28 Example Of An Installation To 19-Inch Racks (For Gs, 1400Mm)

    For AC100V connections For AC200V connections Base rack (rear) Base rack (rear) PDU#2 PDU#1 PDU#1 PDU#0 PDU#0 SCCI / PPC SCCI / PPC FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 50: Figure 30 Example Of An Installation To 19-Inch Racks (With Standard Door, 2000Mm)

    CE#6 CE#A CE#1 CE#5 CE#9 CE#0 CE#4 CE#8 PDU#5 PDU#4 PDU#3 PDU#3 PDU#3 PDU#2 PDU#2 PDU#2 PDU#1 PDU#1 PDU#1 PDU#0 PDU#0 PDU#0 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 51: Figure 31 Example Of An Installation To 19-Inch Racks (With Standard Door, 2000Mm) (When Connecting Three Or Four Drive Enclosures Per Node)

    PDU#3 PDU#3 PDU#3 PDU#3 PDU#2 PDU#2 PDU#2 PDU#2 PDU#2 PDU#2 PDU#1 PDU#1 PDU#1 PDU#1 PDU#1 PDU#1 PDU#0 PDU#0 PDU#0 PDU#0 PDU#0 PDU#0 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 52: Figure 33 Example Of An Installation To 19-Inch Racks (With A Dx8000 Series Dedicated Door, 2000Mm) (When Connecting Seven Or More Drive Enclosures Per Node)

    DE#88 DE#98 DE#A8 DE#B8 DE#64 DE#74 DE#84 DE#94 DE#A4 DE#B4 DE#60 DE#70 DE#80 DE#90 DE#A0 DE#B0 CE#6 CE#7 CE#8 CE#9 CE#A CE#B FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 53: Figure 34 Example Of An Installation To 19-Inch Racks (For Gs, 1800Mm) (When Connecting Two Or Less Drive En- Closures Per Node)

    Base rack (rear) Expansion rack #0 CE#2 CE#2 CE#1 CE#1 CE#0 CE#0 CE#3 PDU#3 SCCI / PPC PDU#2 PDU#1 PDU#1 PDU#0 PDU#0 FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 54: Power Cord Connection

    Do not use a 3m power cable. Space for the excess cable will not be sufficient, and therefore the cable cannot be stored in the rack. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED...
  • Page 55: Figure 36 Ac Cable Connection

    Connect to the outlets using the connection order to the power distribution units which is the same as the • installation order in the rack. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 56: Figure 37 Power Distribution Unit (Horizontal Type) Installation Example

    OUT5 to OUT8 exceeds 12A and then the connection fails. Current consumption Connection enclosures (total for OUT1 to OUT4 or OUT5 to OUT8) 18.4A — 13.8A 16.5A 14.6A 12.7A FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 57 Specifications" (page 38). • For mainframe connections, power distribution units (vertical type) cannot be installed. Power distribution units (horizontal type) must be selected. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 58: Frontend Cable Connection

    "management cables". Select the most appropriate frontend cable depending on the dis- tance between the frontend enclosure and the controller enclosure. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED...
  • Page 59: Table 18 Frontend Cable Connection Usage (19-Inch Racks [2000Mm] With Unix/Industry Standard Server Connec- Tions)

    (For extensions) Used as extension cables when the connection length is more than 10m. 30m (QSFP active optical cable) 30m (management cable) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 60: Figure 39 Frontend Cable Connection Example (When Connecting Two Des For Each Node In A 19-Inch Rack [2000Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 61: Figure 40 Frontend Cable Connection Example (When Connecting Four Des For Each Node In A 19-Inch Rack [2000Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 62: Figure 41 Frontend Cable Connection Example (When Connecting Six Des For Each Node In A 19-Inch Rack [2000Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 63 (when facing the rear) of the base rack, the 3m QSFP copper cable cannot connect between the base rack and the third expansion rack (or Expansion Rack#2). The 10m QSFP active optical cable is required instead. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED...
  • Page 64: Figure 42 Frontend Cable Connection Example (When Connecting 16 Des For Each Node In A 19-Inch Rack [2000Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 65: Table 23 Frontend Cable Connection Usage (For Gs, 1800Mm Racks, With Mainframe Connections)

    (For extensions) Used as extension cables when the connection length is more than 10m. 30m (QSFP active optical cable) 30m (management cable) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 66: Figure 43 Frontend Cable Connection Example (When Connecting Two Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    PDU#0 QSFP copper cable (supplied as standard) Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 67: Figure 44 Frontend Cable Connection Example (When Connecting Four Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    PDU#0 QSFP copper cable (supplied as standard) Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 68: Figure 45 Frontend Cable Connection Example (When Connecting Six Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    PDU#0 QSFP copper cable (supplied as standard) Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 69: Figure 46 Frontend Cable Connection Example (When Connecting Eight Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    PDU#0 QSFP copper cable (supplied as standard) Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 70: Figure 47 Frontend Cable Connection Example (When Connecting 10 Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 71: Figure 48 Frontend Cable Connection Example (When Connecting 12 Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 72: Figure 49 Frontend Cable Connection Example (When Connecting 14 Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 73: Figure 50 Frontend Cable Connection Example (When Connecting 16 Des For Each Node In A 19-Inch Rack [For Gs, 1800Mm])

    Management cable (supplied as standard) 1.1m QSFP copper cable (for extensions) Management cable (for extensions) QSFP active optical cable (for extensions) Management cable (for extensions) FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 74: Backend Cable Connection

    Used as extension cables when the connection length between the racks is more than 6.0m. Used as extension cables when the connection length between the racks is more than 15.0m. FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED...
  • Page 75: Figure 51 Backend Cable Connection Example (Eternus Dx8100 S3 Connections In The Same Rack)

    The following figure shows an example when one controller enclosure and four drive enclosures (2U) are instal- led in a rack. For the ETERNUS DX8100 S3, the required length of cable is the same for Controller 0 (CM#0) and Controller 1 (CM#1) so the cables that are supplied as standard can be use for connections.
  • Page 76: Figure 52 Backend Cable Connection Example (Eternus Dx8700 S3/Dx8900 S3 Connections In The Same Rack)

    Figure 52 Backend Cable Connection Example (ETERNUS DX8700 S3/DX8900 S3 Connections in the Same Rack) Base rack (rear) CE#0 Cables that are supplied as standard 1.1m Extension cables 3.5m FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 77: Figure 53 Backend Cable Connection Example (When Installing 16 Des For Each Node Connected Between Multiple Racks)

    Figure 53 Backend Cable Connection Example (When Installing 16 DEs for Each Node Connected between Multi- ple Racks) Base rack (rear) Expansion rack#0 CE#0 CE#1 Cables that are supplied as standard 1.1m Extension cables 3.5m FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 78: Installable Racks

    This section explains the racks in which the ETERNUS DX can be installed. Fujitsu Racks The ETERNUS DX can be installed in a Fujitsu 19-inch rack. For information about whether the ETERNUS DX can be installed in an EOLed rack or not, contact your sales representative.
  • Page 79: Figure 54 Unit Installation Area

    Make sure to perform the installation according to the placement requirements described in "Installation Specifi- cations" (page 10) "Installation Environment" (page 32). FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide Copyright 2020 FUJITSU LIMITED P3AM-9422-13ENZ0...
  • Page 80 However, Fujitsu shall assume no responsibility for any operational problems as the result of errors, omissions, or the use of information in this manual. Fujitsu assumes no liability for damages to third party copyrights or other rights arising from the use of any information •...