6.18 PWM carrier frequency

Load reduction (current reduction) by carrier frequency, ambient temperature and input voltage
VFS15-
temperature
40°C or less
Above 40 ∼ 50°C
4004PL1-W1
Above 50 ∼ 60°C
40°C or less
Above 40 ∼ 50°C
4007PL1-W1
Above 50 ∼ 60°C
40°C or less
Above 40 ∼ 50°C
4015PL1-W1
Above 50 ∼ 60°C
40°C or less
Above 40 ∼ 50°C
4022PL1-W1
Above 50 ∼ 60°C
40°C or less
Above 40 ∼ 50°C
4037PL1-W1
Above 50 ∼ 60°C

9.1.2 Measures to satisfy the EMC Directive

Inverter type
VF S15-4004PL1-W1
VF S15-4007PL1-W1
VF S15-4015PL1-W1
VF S15-4022PL1-W1
VF S15-4037PL1-W1
11.4 Default settings by inverter rating
■ Default settings
The default setting of motor parameters are adapted to Toshiba IE3 motor.
In case of using Toshiba standard IE1 motor, the parameters values should be adjusted according to Table 4
(VFS15-4004PL to 4037PL) in E6582165 (VF-S15 motor control parameter default setting update information).
Torque
boost
Inverter type
value
/

VFS15-
(%)
4004PL1-W1
6.0
4007PL1-W1
4.8
4015PL1-W1
4.8
4022PL1-W1
3.1
4037PL1-W1
3.1
*1: When region setting is JP,  is set to 3.7(kW).
If the parameters and the adjustment range, which are not shown in the manuals (E6581611 and additional
sheet), are displayed in the inverter, those parameters and adjustment range are "the factory specific
coefficient parameters". Do not change or set the value of these parameters and adjustment range.
Input voltage 480V or less
Ambient
PWM carrier frequency [kHz]
2.0~4.0
1.5 A
1.5 A
1.4 A
2.3 A
2.3 A
2.2 A
4.1 A
4.1 A
3.9 A
5.5 A
5.5 A
5.2 A
9.5 A
9.5 A
9.0 A
Combination of inverter and filter
Conducted noise
IEC61800-3, category C2
(Motor wiring length of 5m or less)
Built-in filter
Dynamic
Dynamic
braking
braking
resistor
resistance
capacity
     
(Ω)
(kW)
200.0
0.12
200.0
0.12
200.0
0.12
200.0
0.12
160.0
0.12
4.1~12.0
12.1~16.0
1.5 A
1.5 A
1.5 A
1.5 A
1.2 A
1.2 A
2.1 A
2.1 A
2.1 A
2.1 A
1.7 A
1.7 A
3.7 A
3.3 A
3.7 A
3.3 A
3.0 A
2.6 A
5.0 A
4.5 A
5.0 A
4.5 A
4.0 A
3.6 A
8.6 A
7.5 A
8.6 A
7.5 A
6.9 A
6.0 A
Conducted noise
IEC61800-3, category C1
(Motor wiring length of 20m
Automatic
Motor
Motor
torque
rated
rated
boost
capacity
current
value
*1
(%)
(kW)
(A)
6.2
0.40
1.0
4.3
0.75
1.7
4.4
1.50
3.2
2.9
2.20
4.7
2.8
4.00
7.3
6
Input voltage above 480V
PWM carrier frequency [kHz]
2.0~4.0
4.1~12.0
1.5A
1.5A
1.5A
1.5A
1.4A
1.2A
2.1A
1.9A
2.1A
1.9A
2.0A
1.5A
3.8A
3.4A
3.8A
3.4A
3.6A
2.5A
5.1A
4.6A
5.1A
4.6A
4.8A
3.7A
8.7A
7.9A
8.7A
7.9A
8.3A
5.6A
Conducted noise
IEC61800-3, category C2
(Motor wiring length of 50m
or less)
EMFS11-4015BZ
EMFS11-4015BZ
EMFS11-4015BZ
EMFS11-4025CZ
EMFS11-4025CZ
Over-voltage
Motor
stall
no-load
protection
current
level

(%)
(%)
65
141
55
141
42
141
50
141
38
141
E6582185
12.1~16.0
1.2A
1.2A
1.0A
1.9A
1.9A
1.5A
3.1A
2.6A
1.5A
4.2A
4.2A
3.4A
6.9A
5.5A
3.3A
or less)
Integrating
wattmeter
display unit
selection

0
0
0
0
1