Preparing Materials; Special Tools - Huawei NetCol8000-E220 Series Quick Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for NetCol8000-E220 Series:
Table of Contents

Advertisement

Internal Components
(1) Outdoor air outlet port
(2) Electric control box
(3) Indoor air supply port
(4) Indoor air supply fan
(5) Evaporator
(6) Gas-liquid separator
2
Preparations
2.1

Preparing Materials

Materials delivered with
equipment
Optional components
Water pipe •
Engineering
purchase
Cable
a: Only active and standby power cables are usually used. If you need to separately power the
compressor, an external cooling power supply is required.

Special Tools

2.2
Indoor installation scenario: Crane (lifting capacity ≥10T), ground tank, electric forklift (with long arm)
Outdoor installation scenario: Crane (lifting capacity ≥10T)
(7) Compressor
(8) Pump
(9) Water inlet and outlet electric valve
(10) Water tank
(11) Water spraying system
(12) Outdoor air intake port (on the side)
Combined hexagon head bolts, Cable tie, OT ground terminal of the power
cable, condensate trap DN20, drainage drain pipe trap DN40, angle steel
and fixing screws, expansion bolt M16×150, sealing mud, sealing sheet
metal for water inlet and drainage, self-tapping nail, T-bolt, color swatch
Air duct assembly, temperature and humidity sensor,etc
Spray water refill pipe: G 3/4 inch outer screw thread (DN20)
Spray drainpipe: G 1-1/2 inch inner screw thread (DN40)
Condensate drainpipe: G 3/4 inch inner screw thread (DN20)
Power cable: 4 x 70 mm² (L1/L2/L3/N) + 35 mm² (PE), active and
standby power cables
OT terminal: 35 mm² , M10, 6 PCS
OT terminal: 70 mm² , M10, 14 PCS
Ground cable: 35 mm² , 2 PCS
Cable tie: 10 PCS
a
2
(13) Outdoor air intake port
(at the end)
(14) Indoor air return port
(15) Air return filter
(16) Condenser
(17) Outdoor air outlet fan
(18) Light