Number Of Client Instructions That Can Be Used Simultaneously - Siemens SIMATIC S7-1500 Function Manual

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

OPC UA communication
9.4 Using the S7-1500 CPU as an OPC UA client
Information about the client instructions
The client instructions are described in detail in the help to the Instructions > Communication
> OPC UA > OPC UA client.
Application example in Online Support
This application example (https://support.industry.siemens.com/cs/ww/en/view/109762770)
provides you with an S7 user block "OpcUaClient" that summarizes the most important
functions of the OPC UA instructions, accelerates the implementation for you and simplifies
the programming. The OPC UA server in the example is an S7-1500 controller with a simple
simulation program for process values.
The S7 user block performs the following:
● Establishment and termination of the connection to the server
● Diagnostics of the connection and automatic reconnection after connection terminations
● Registered Read
● Registered Write
● Registered Method Call
9.4.3

Number of client instructions that can be used simultaneously

SIMATIC error codes for OPC UA client instructions
The following limits apply to the simultaneous use of OPC UA client instructions (up-to-date
technical specifications of the CPUs can be found on the Internet
(https://support.industry.siemens.com/cs/ww/en/ps/td)):
Table 9- 5
Quantity structures for OPC UA client instructions
OPC UA instruction
OPC_UA_Connect
OPC_UA_NamespaceGetIndexList 4*
OPC_UA_NodeGetHandleList
OPC_UA_MethodGetHandleList
OPC_UA_TranslatePathList
OPC_UA_ReadList
248
Maximum number for
Maximum number for
CPU 1510SP (F)
CPU 1505 (S/SP/SP F/SP T/SP TF)
CPU 1511 (C/F/T/TF)
CPU 1515 (F/T/TF)
CPU 1512C
CPU 1515 SP PC (F/T/TF)
CPU 1512SP (F)
CPU 1516 (F/T/TF)
CPU 1513 (F)
4
10
10*
4*
10*
4*
10*
4*
10*
20 in total (max. 5 per
50 in total (max. 5 per connection,
connection, see
see OPC_UA_Connect)
OPC_UA_Connect)
Maximum number
for
CPU 1507S (F)
CPU 1517 (F/T/TF)
CPU 1518 (F)
40
40*
40*
40*
40*
200 in total (max. 5
per connection, see
OPC_UA_Connect)
Function Manual, 11/2019, A5E03735815-AH