Haier HACI-RP Series Installation, Use And Maintenance Manual page 27

Heat recovery units

Advertisement

15 TABE A DI I DIRI
ModBus Address
Useless
00
01
Useless
02
By-pass opening temperature X
03
By-pass opening temperature range Y
04
Defrosting interval
05
Defrosting enter temperature
06
Defrost duration time
07
CO2 sensor
08
ModBus address
09
ERV ON/OFF
10
Supply fan speed
11
Exhaust fan speed
12
Room temperature
13
Outdoor temperature
14
Exhaust air temperature
15
Defrosting temperature
16
External ON/OFF signal
17
CO2 ON/OFF signal
18
Fire alarm signal/bypass/defrosting signal
19
Electrical heater stage
20
Error symbol
21
ERV models selection
22
Defrosting models
DBUS
Content
5-30
2-15
15-99
-9...+5
2-20
28-C8 (392-1960ppm)
1-
0-OFF 1-ON
Fan speed:
0= stop,
3= speed 2,
8= speed 4,
10= speed 6, 11= speed 7,
12= speed 8, 13= speed 9,
14= speed 10.
Fan speed:
0= stop,
3= speed 2,
8= speed 4,
10= speed 6, 11= speed 7,
12= speed 8, 13= speed 9,
14= speed 10.
observed value
observed value
observed value
observed value
query value
query value
query value:
B0 - 1- fire alarm ON
B1 - 1- bypass on
B2 - 1- bypass off
B3 - 1- defrosting
query value:
B2 - OA - temperature error
B5 - EEPROM error
B4 - RA - temperature error
B3 - Fr - temperature error (auto defrosting)
a ua e di I sta a i e Us e a ute i e I sta ati
15 TAB E F
Range
66 (1000ppm)
2= speed 1
5= speed 3,
9= speed 5,
2= speed 1
5= speed 3,
9= speed 5,
Use a d ai te a ce a ua
DBUS ADDRESS
Default
Record Position
Main Control
Main Control
19 °C
Main Control
3 °C
Main Control
30 min
Main Control
-1 °C
Main Control
10 min
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control
Main Control