11. The water heat exchanger unit is equipped with built-in circuits that cause the cold-hot water circulation pump
to operate automatically when the outside temperature drops and the water temperature inside the unit de-
clines to prevent freezing inside the unit. However, when either the unit installation location or cold-hot water
pipe insulation is inadequate, the water temperature inside the pump or cold-water pipes may decline prior to
the water temperature in the unit, resulting in freezing.
In the following cases, install circuits capable of detecting the outdoor temperature at the locations where the
water temperature declines most rapidly throughout the entire water pipe system, prompting automatic opera-
tion of the cold-hot water circulation pump.
12. Attach proper hoisting fixtures to the water pipes to prevent an unreasonable load from being placed on the
water heat exchanger unit.
13. For freezing protection, always turn on the flow switch contact serially with the operational signal.
Flow switch rating:
Turn the contact ON (closed) at flow of;
3m
/h or above for WE80M1 and
S-250WX2E5
3
4m
/h or above for WE170M1.
3
S-500WX2E5, S-710WX2E5
5. DRAIN PIPES
• Because the drain consists of natural drainage, always set the drain at a downgrade (1/100 or above).
Setting the drain at an upgrade will cause a backflow in the drain water, which can result in water
leakage.
• Upon completing the pipe work, confirm drainage and check for leaks, then insulate the drain pipe
section installed inside the room. Failure to take these steps can result in water leakage or dew
dripping.
• • • • • Do not share the exhaust drain pipe of the outdoor unit with the drain pipe of the water heat
exchanger unit. The exhaust gas will flow in the water heat exchanger unit and cause a corrosion.

6. INDOOR INSTALLATION

1. Indoor installation of the water heat exchanger unit will result in dew condensation on the facing,
leading to dripping in some cases. As a countermeasure, a dew catcher or other type of drain pan
should be installed at the bottom of the unit.
Chiller side
Exhaust drain hose
Open to air
(Nominal pipe diameter 50A+)
9