Advanced Settings
Heating & Cooling
u To access the Heating and Cooling, select Advanced Settings from the Menu, then select Heating and Cooling.
u Enter the Professional Access Code and select a parameter to modify the default value. From this menu you can adjust:
Title
Default
Fan Delay On
0 Seconds
Fan Delay On Elec
0 Seconds
Fan Delay Off
60 Seconds
Min. Run Time
5 Minutes
Anti Short Cycle
5 Minutes
180
Cycle Time
Seconds
Zero Energy
1° F/ 0.5° C
Band Heating
Zero Energy
1° F/ 0.5° C
Band Cooling
Deadband
5°F/3°C
Max
Min
Description
The fan's lag time after the heating or cooling call is initiated when in Fossil Fuel,
120
0 Seconds
Seconds
Heat Pump, or Cooling operation.
The fan's lag time after the heating or cooling call is initiated when in Electric,
5 Seconds
0 Seconds
Auxiliary heat, or Emergency heat operation.
120
30 Seconds
The fan's lag time after the heating or cooling call is terminated.
Seconds
The minimum amount of time a heating or cooling call will run after the initial call.
Stage Delay
3 Minutes
This timer resets and must be met after each stage up condition.
The minimum amount of time a heating or cooling call will run after a stage down
5 Minutes
0 Minutes
condition. This timer resets and must be met after each stage down condition.
Time delay required between system mode changes before active heating or
300
60 Seconds
Seconds
cooling calls can begin.
A temperature range between the current temperature and the heating set point,
0.5° F/
2° F/ 1° C
0.3° C
where heating is not engaged.
A temperature range between the current temperature and the cooling set point,
0.5° F/
2° F/ 1° C
0.3° C
where cooling is not engaged.
A temperature range between the heating set point and cooling set point in Auto
9°F/5°C
2°F/1°C
Mode, where heating/cooling is not engaged.