Solid Core and Split Core 4-20 mA
Output Current Sensors
CTS-A AND CTP-A SERIES
APPLICATION
The 4-20 mA Output Analog Current Sensors are designed
for use in any AC current monitoring application in which
you are looking to monitor a particular piece of equipment.
SPECIFICATIONS
Monitored Current Type: AC Current
Maximum AC Voltage: 600 VAC
Isolation Voltage: 2200 VAC
Supply Voltage:
+8.5 to 30 VDC (Reverse Polarity Protected)
250 Ohm Load (1-5 VDC): +13.5 to 30 VDC
500 Ohm Load (2-10 VDC): +18.5 to 30 VDC
STANDARD ORDERING
Model #
Selectable Ranges Measurement
CTS-A-250
0 to 100/200/250A
CTP-A-200
0 to 100/150/200A
CTP-A-50-RMS
0 to 10/20/50A
NOTE: The 4-20 mA Output Current Sensors are not intended to be used in life/safety applications or in hazard-
ous/classified locations.
Table 1. Standard Ordering.
Average
Average
True RMS
20
INSTALLATION INSTRUCTIONS
Operating Temperature Range: 5 to 104ºF (-15 to 40ºC)
Operating Humidity Range: 0 to 95%, non-condensing
Wire Recommendations: 2 Conductor (Shielded Cable)
Wire Size:
18 to 24 AWG (0.823 mm
only
Terminal Block Torque Rating: 4.43 to 5.31 in-lbs. (0.5 to
0.6 Nm)
Minimum Mounting Distance:
1" (2.6 cm) between current sensor & other magnetic
devices (Relays, Contactors, Transformers)
Agency Approvals:
CE (-RMS Versions): CE to IEC 61326-1: 2012 Class A,
UL/CUL US Listed (UL 508) Ind. Control Equipment
(File # E309723), RoHS2, WEEE
AC Waveform
Solid-Core Split-Core
Pure Sinusoidal
Pure Sinusoidal
Distorted & Pure
Sinusoidal
2
to 0.205 mm) Copper Wires
Output
Signal
•
4 to 20 mA
•
4 to 20 mA
4 to 20 mA
•
31-00142-01