Internal Components
(1) Outdoor air outlet port
(2) Electric control box
(3) ELV control box
(4) Outdoor air outlet fan
(5) Compressor
(6) Spray water tank
(7) Condenser
2
Preparations
2.1
Preparing Materials
Materials delivered with
equipment
Optional components
Water pipe •
Engineering
purchase
Cable
Special Tools
2.2
Indoor installation scenario: Crane (lifting capacity ≥ 15 tons), ground tank, electric forklift (with
long arm)
Outdoor installation scenario: Crane (lifting capacity ≥ 15 tons)
(8) Evaporator
(9) Pump
(10) Condensate water pan
(11) Indoor air fan
(12) Indoor air supply port
(13) air supply fan driver
(14) Differential pressure switch
Combined hexagon head bolts M12 x 30, cable tie, cord end terminal of the
power cable, OT ground terminal of the power cable, condensate drainage
water seal (DN25), drainage blowdown water seal (DN40), angle steel and
fixing screws, expansion bolt M16 x 150, sealing mud, self-tapping nail,
color swatch
Motorized damper (air exhaust/air supply), rainproof canopy, and electric
heater components
Spray water refill pipe: G 3/4 inch inner screw thread (DN20)
Spray drainpipe: G 1-1/2 inch inner screw thread (DN40)
Condensate drainpipe: G 1 inch inner screw thread (DN25)
Power cable: 3 x 95 mm² (L1/L2/L3) + 50 mm² (PE), active and standby
power cables
OT ground terminal: 50 mm² , M12, 3 PCS
OT terminal: 95 mm² , M12, 7 PCS
Ground cable: 95 mm² , 2 PCS
(15) Outdoor air intake port
(16) Spray system
(17) Heat exchanger core
(18) Air return filter
(19) Air outlet fan driver
(20) Compressor driver
2